Plan Review Details - Permit 16070441
Plan Review Stops For Permit 16070441
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-20 Cont ID  
Sent By ccole Date 2016-07-20 Time 15:45 Rev Time 0.00
Received By ccole Date 2016-07-19 Time 11:03 Sent To  
Notes
2016-07-20 11:03:20RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-14 Cont ID  
Sent By ccole Date 2016-07-14 Time 08:11 Rev Time 0.00
Received By ccole Date 2016-07-13 Time 13:32 Sent To  
Notes
2016-07-13 13:33:00REVISION ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-07-20 Cont ID  
Sent By ccole Date 2016-07-20 Time 15:45 Rev Time 0.00
Received By ccole Date 2016-07-20 Time 15:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-14 Cont ID  
Sent By ccole Date 2016-07-14 Time 08:11 Rev Time 0.00
Received By ccole Date 2016-07-14 Time 08:11 Sent To  
Notes
2016-07-14 08:19:551ST REVIEW MECHANICAL
 PERMIT REVISION #16070441
 MASTER #15061466
 7/14/16
  
 1) SHEET M1: REFER TO SECTION M1601.6 FBC-14
 RESIDENTIAL AND REMOVE THE AC DROP IN THE VESTIBULE TO
 AVOID AIR FROM THE GARAGE/BIKE SHOP TO BE RETURNED INTO
 THE MAIN HOUSE SYSTEM. THE SYSTEMS MUST BE INDEPENDENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  