Plan Review Details - Permit 16070440
Plan Review Stops For Permit 16070440
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-19 Cont ID  
Sent By ccole Date 2016-07-19 Time 16:47 Rev Time 0.00
Received By ccole Date 2016-07-13 Time 13:17 Sent To  
Notes
2016-07-13 13:17:56REVISION ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-19 Cont ID  
Sent By ccole Date 2016-07-19 Time 16:38 Rev Time 0.00
Received By ccole Date 2016-07-19 Time 16:38 Sent To  
Notes
2016-07-19 16:43:271ST REVIEW MECHANICAL
 PERMIT #16070440
 7/19/16
  
 1) PROVIDE A NARRATIVE FROM THE ENGINEER OF RECORD
 ITEMIZING ALL CHANGES MADE TO THE APPROVED PLANS UNDER
 PERMIT #15060911. IT APPEARS THAT NEW EVAPORATIVE
 COOLING SYSTEMS HAVE REPLACED THE ORIGINAL SPLIT AIR
 CONDITIONING SYSTEMS. PLEASE CLARIFY WHY THIS CHANGE
 WAS MADE AND SUBMIT REVISED SYSTEM AND ENERGY
 CALCULATIONS. IS THE SPACE NOW BEING USED FOR
 REFRIGERATED STORAGE?
  
 2) SUBMIT REVISED ELECTRICAL PLANS, AND ALL OTHER
 BUILDING PLANS AFFECTED BY THE OCCUPANCY AND COOLING
 SYSTEM CHANGES.CHANGES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  