Plan Review Details - Permit 16070408
Plan Review Stops For Permit 16070408
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-08-15 Cont ID  
Sent By jwitmer Date 2016-08-15 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2016-08-15 Time 07:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-02 Cont ID  
Sent By jwitmer Date 2016-08-02 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2016-08-02 Time 06:45 Sent To  
Notes
2016-08-02 07:10:47BUILDING PLAN REVIEW/ AUDIT
 W. P. B. PERMIT: 16070408
 ADD: 1801 S. FLAGLER DR. SUITE # 1807
 CONT: SYKES CUSTOM BUILDERS
 TEL: 561-676-8202
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. AUGUST 02/2016
 ACTION: DENIED
  
 NOTICE!!!!! FLORIDA STATUTE 553.80 (2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
  
 1) 2ND REQUEST. PLEASE NOTE THE SUBMITTED PLANS DO NOT
 MEET THE CRITERIA FOR COMMERCIAL BUILDINGS MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS/ BUILDING. 107.3.5.1.1.
  
 COMMERCIAL BUILDINGS MINIMUM PLAN REVIEW CRITERIA/
 BUILDING 107.3.5.1.1
 OCCUPANCY TYPE
 BUILDING TYPE
 FIRE SRINKLERED OR NOT
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
  
 2) COMPLIED.
  
 3) 2ND REQUEST. THE PLAN INDICATES THE FLOORS TO BE
 RECOVERED WITH WOOD FLOORING THROUGH OUT AND TILE IN
 THE BATHROOMS. TO REMAIN. THE PLANS FAIL TO IDENTIFY
 WHAT TYPE OF WOOD FLOORING( LAMINATE, 3/4 INCH PLANK).
 THE SUBMITTED TEST REPORTS FOR SOUND ARE QEP PREMIMUM
 CORK WITH BADGER CORK FLAME SPREAD (2) DIFFERENT
 COMPANIES AND PLEASE NOTE THE TEST SUBMITTED FOR SOUND
 IS FOR TILE NOT WOOD OR WOOD LAMINATE.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING.
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 3A) 2ND REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) 2ND REQUEST. FLAME SPREAD- FBC-B 2014 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
 L

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-18 Cont ID  
Sent By jwitmer Date 2016-07-18 Time   Rev Time  
Received By jwitmer Date 2016-07-18 Time 07:29 Sent To  
Notes
2016-07-18 07:51:10BUILDING PLAN REVIEW/ AUDIT
 W. P. B. PERMIT: 16070408
 ADD: 1801 S. FLAGLER DR. SUITE # 1807
 CONT: SYKES CUSTOM BUILDERS
 TEL: 561-676-8202
 E-MAIL: SYKESCUSTOM [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 18/2016
 ACTION: DENIED
  
 1) PLEASE NOTE THE SUBMITTED PLANS DO NOT MEET THE
 CRITERIA FOR COMMERCIAL BUILDINGS MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS/ BUILDING. 107.3.5.1.1.
  
 COMMERCIAL BUILDINGS MINIMUM PLAN REVIEW CRITERIA/
 BUILDING 107.3.5.1.1
 OCCUPANCY TYPE
 BUILDING TYPE
 FIRE SRINKLERED OR NOT
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
  
 2) PLEASE NOTE THE PLANS SUBMITTED APPEAR TO BE DRAWN
 BY THE GENERAL CONTRACTOR OF RECORD, THE FLOOR PLAN,
 ELEVAIONS, AS WELL AS THE ELECTRICAL AND PLUMBING
 DRAWINGS. UNDER THE CITY AMENDMENT 107.3.4.3
 CERTIFICATIONS BY CONTRACTORS AUTHORIZED. PLEASE NOTE
 THE EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDIVUAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 3) THE PLAN INDICATES THE FLOORS TO BE RECOVERED WITH
 WOOD FLOORING THROUGH OUT AND TILE IN THE BATHROOMS.
 THE PLANS FAIL TO IDENTIFY WHAT TYPE OF WOOD FLOORING(
 LAMINATE, 3/4 INCH PLANK).
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING.
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
 L

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-01 Cont ID  
Sent By albarran Date 2016-08-01 Time 14:44 Rev Time 0.00
Received By albarran Date 2016-08-01 Time 14:29 Sent To  
Notes
2016-08-01 14:45:10ALL PREVIOUSLY MENTIONED COMMENTS HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-14 Cont ID  
Sent By albarran Date 2016-07-14 Time 11:52 Rev Time 0.00
Received By albarran Date 2016-07-14 Time 11:09 Sent To  
Notes
2016-07-14 11:52:581ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. FBC-RE3905.6.2/NEC 314.27(A) LUMINAIRE OUTLETS.
 BOXES USED AT LUMINAIRE OR LAMPHOLDER OUTLETS IN A
 CEILING SHALL BE REQUIRED TO SUPPORT A LUMINAIRE
 WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE NOTES ON
 CEILING BOXES ON PAGE.
 2. FBC-RE3905.8/NEC 314.27(D) PADDLE FANS. BOXES USED
 FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY
 THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND
 INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED
 TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS.
 3. FBC-R4001.15/NEC 404.2(C). WHERE SWITCHES
 CONTROLLING LIGHTING LOADS SUPPLIED BY A GROUNDED
 BRANCH CIRCUIT, THE GROUNDED BRANCH CIRCUIT CONDUCTOR
 FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED
 AT THE SWITCH.
 4. FBC-RE3901.2.1/NEC 210.52 (A)(1) SPACING.
 RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL
 SPACE IS MORE THAN 6 FT. FROM A RECEPTACLE OUTLET. THIS
 INCLUDES THE DISTANCE FROM THE EDGE OF THE WALL. THERE
 ARE MISSING OUTLETS BOTH IN THE MASTER BEDROOM AND
 ALONG THE NEW WALL OF THE DINING AREA.
 5. FBC-RE3901.6/NEC 210.52(D) BATHROOMS. IN DWELLING
 UNITS, AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED IN BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE
 OF EACH BASIN. MISSING OUTLET IN THE GUEST BATHROOM.
 6. FBC-R314: IF NOT ALREADY COMPLIANT WITH THE LATEST
 SMOKE DETECTOR REQUIREMENTS, THIS ARTICLE REQUIRES THAT
 YOU COME INTO COMPLIANCE WITH THE LATEST REQUIREMENTS
 AS IF NEW CONSTRUCTION.
 7. NFPA 72 SECTION 18.4.5: ASCERTAIN CONTINUED
 COMPLIANCE WITH THE FIRE ALARM NOTIFICATION
 REQUIREMENTS OF THIS SECTION.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-07-28 Cont ID  
Sent By wjolin Date 2016-07-28 Time 12:38 Rev Time 0.00
Received By wjolin Date 2016-07-28 Time 11:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-07-14 Cont ID  
Sent By wjolin Date 2016-07-14 Time 14:28 Rev Time 0.00
Received By wjolin Date 2016-07-14 Time 14:17 Sent To  
Notes
2016-07-14 14:20:521801 SOUTH FLAGLER DRIVE - #1807
 PERMIT #16070408
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EXISTING APARTMENT BUILDINGS NOT PROTECTED BY AUTOMATIC
 SPRINKLERS SYSTEM SHALL HAVE SINGLE STATION OR
 MULTI-STATION SMOKE ALARMS (HARD-WIRED OR BATTERY
 POWERED) INSTALLED INSIDE EACH BEDROOM AND DIRECTLY
 OUTSIDE BEDROOM DOORS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-15 Cont ID  
Sent By jwitmer Date 2016-08-15 Time 08:01 Rev Time 0.00
Received By jwitmer Date 2016-08-10 Time 11:08 Sent To  
Notes
2016-08-11 11:08:30B07

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-02 Cont ID  
Sent By   Date 2016-08-02 Time 07:15 Rev Time 0.00
Received By skennedy Date 2016-07-26 Time 11:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-26 Cont ID  
Sent By skennedy Date 2016-07-26 Time 10:47 Rev Time 0.00
Received By skennedy Date 2016-07-13 Time 15:13 Sent To  
Notes
2016-07-13 15:14:09B35

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-07-18 Cont ID  
Sent By jwitmer Date 2016-07-18 Time 08:11 Rev Time 0.00
Received By jwitmer Date 2016-07-18 Time 08:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-08-01 Cont ID  
Sent By gjohnson Date 2016-08-01 Time 14:24 Rev Time 0.00
Received By tklarge Date 2016-08-01 Time 14:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-07-26 Cont ID  
Sent By skennedy Date 2016-07-26 Time 10:47 Rev Time 0.00
Received By skennedy Date 2016-07-26 Time 10:47 Sent To  
Notes
2016-07-26 10:49:05THE APPLICANT HAS ADVISED THE PLUMBING HAS BEEN
 REDESIGNED FOR THE SECOND CYCLE REVIEW. I FAILED THE
 PLUMBING WITHOUT FULL REVIEW TO ALLOW FOR RE-SUBMITTAL.
  
 STEVEN KENNEDY