Plan Review Details - Permit 16070402
Plan Review Stops For Permit 16070402
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-11-23 Cont ID  
Sent By cthroop Date 2016-11-23 Time 12:02 Rev Time 0.00
Received By cthroop Date 2016-11-23 Time 12:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-18 Cont ID  
Sent By shill Date 2016-08-18 Time 06:45 Rev Time 0.00
Received By shill Date 2016-08-18 Time 06:45 Sent To  
Notes
2016-08-18 06:46:46****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 5TH EDITION
  
  
 PHOTOGRAPHS WERE PROVIDED. REVISE PLAN TO INCORPORATE
 INFORMATION.
 COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED:
  
 1. REVISE THE PLAN TO PROVIDE THE FOLLOWING
 INFORMATION:
  
 LOCATION OF ACCESSIBLE ENTRANCES
 LOCATION OF ACCESSIBLE SPACES AND ACCESS AISLES
 SHOW ACCESSIBLE ROUTE FROM PUBLIC WAY
 ACCESSIBLE ROUTE FROM ACCESSIBLE SPACE TO ACCESSIBLE
 ENTRANCE
  
 THE PLAN PROVIDED DEPICTS SIX ACCESSIBLE SPACES, TWO
 ACCESS AISLES, AND STATES THAT THERE ARE FIVE
 ACCESSIBLE SPACES. IT IS NOT CLEAR HOW MANY ARE
 PROPOSED. THE PLAN IS NOT CLEAR AS TO ACCESSIBLE ROUTE.
 IT IS NOT CLEAR WHETHER THERE IS A SIDEWALK IN FRONT OF
 BOTH ACCESS AISLES, OR IF THIS IS A LANDSCAPE ISLAND.
 IF THIS IS A SIDEWALK, WIDTH IS NOT SHOWN.
  
 THE DESIGN APPEARS TO COMPEL OCCUPANTS TO TRAVEL BEHIND
 PARKED CARS (NOT PERMITTED). (2ND REVIEW, REVISE PLAN
 TO SHOW ACCESSIBLE ROUTE.)
  
 NO ACCESSIBLE PARKING IS SHOWN SERVING THE SIX STORY.
 PARKING IS TO BE DISPERSED WHEN SERVING MULTIPLE
 ACCESSIBLE ENTRANCES. DOES THE SIX STORY HAVE
 ENTRANCES? (2ND REVIEW, NOT ADDRESSED, SAME PLAN
 SUBMITTED)
  
 ACCESSIBLE SPACES ARE SHOWN IN COLOR. PLANS ARE SCANNED
 AND RETAINED IN BLACK AND WHITE. REVISE THE PLAN TO
 SHOW ALL PERTINENT INFORMATION GRAPHICALLY RATHER THAN
 USING HIGHLIGHTER/COLOR, FBC 107. (2ND REVIEW, SAME
 PLAN SUBMITTED, REVISE)
  
 SEE FBC 5TH EDITION ACCESSIBLITY 202.3 (ALTERATIONS),
 208.2 (PARKING SPACES), 502 (PARKING SPACES), 206
 (ACCESSIBLE ROUTE).
  
 YOU MAY FIND THE FOLLOWING DOCUMENT USEFUL,
 PARTICULARLY THE INTRODUCTION: "WHEN A BUSINESS
 RESTRIPES A PARKING LOT, IT MUST PROVIDE ACCESSIBLE
 PARKING SPACES AS REQUIRED BY THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN."
  
 HTTP://WWW.ADA.GOV/RESTRIPE.HTM
  
 2ND REVIEW, PLAN STATES THAT RESTRIPE WILL BE DONE THE
 SAME AS EXISTING. IT APPEARS THAT "EXISTING" MAY HAVE
 BEEN DONE WITHOUT A PERMIT. I WAS UNABLE TO FIND A
 RECENT RESTRIPE PERMIT FOR THIS PROPERTY. THE PERMIT
 APPLICATION IN 2013 WAS DENIED WITH THE SAME COMMENTS
 AS THIS REVIEW.
  
 SEE REFERENCED DOCUMENT. A RESTRIPE IS CONSIDERED "NEW
 CONSTRUCTION" BY ADA. A NON COMPLIANT INSTALLATION IS
 NOT PERMITTED TO BE REINSTALLED AS "EXISTING". AN
 INSTALLATION DONE WITHOUT A PERMIT IS NOT CONSIDERED
 "EXISTING." PLEASE REVISE PLAN TO PROVIDE REQUESTED
 INFORMATION.
  
 2. FBC 2014 ACCESSIBILITY ADVISORY 502.3, WHERE THE
 ACCESSIBLE ROUTE MUST CROSS VEHICULAR TRAFFIC LANES,
 MARKED CROSSINGS ENHANCE PEDESTRIAN SAFETY; PLEASE
 INDICATE LOCATION ON PLAN.
  
 3. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE
 THEIR PRINTED NAME AND SIGNATURE ON THE PLAN, FBC 107.
  
 NOT ENOUGH INFORMATION WAS PROVIDED TO PERFORM A
 COMPLETE REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-27 Cont ID  
Sent By Mgonzale Date 2016-07-20 Time   Rev Time 0.00
Received By shill Date 2016-07-27 Time 07:31 Sent To Z
Notes
2016-07-27 07:41:18****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 5TH EDITION
  
 1. REVISE THE PLAN TO PROVIDE THE FOLLOWING
 INFORMATION:
  
 LOCATION OF ACCESSIBLE ENTRANCES
 LOCATION OF ACCESSIBLE SPACES AND ACCESS AISLES
 SHOW ACCESSIBLE ROUTE FROM PUBLIC WAY
 ACCESSIBLE ROUTE FROM ACCESSIBLE SPACE TO ACCESSIBLE
 ENTRANCE
  
 THE PLAN PROVIDED DEPICTS SIX ACCESSIBLE SPACES, TWO
 ACCESS AISLES, AND STATES THAT THERE ARE FIVE
 ACCESSIBLE SPACES. IT IS NOT CLEAR HOW MANY ARE
 PROPSED. THE PLAN IS NOT CLEAR AS TO ACCESSIBLE ROUTE.
 IT IS NOT CLEAR WHETHER THERE IS A SIDEWALK IN FRONT OF
 BOTH ACCESS AISLES, OR IF THIS IS A LANDSCAPE ISLAND.
 IF THIS IS A SIDEWALK, WIDTH IS NOT SHOWN.
  
 THE DESIGN APPEARS TO COMPEL OCCUPANTS TO TRAVEL BEHIND
 PARKED CARS (NOT PERMITTED).
  
 NO ACCESSIBLE PARKING IS SHOWN SERVING THE SIX STORY.
 PARKING IS TO BE DISPERSED WHEN SERVING MULTIPLE
 ACCESSIBLE ENTRANCES. DOES THE SIX STORY HAVE
 ENTRANCES?
  
 ACCESSIBLE SPACES ARE SHOWN IN COLOR. PLANS ARE SCANNED
 AND RETAINED IN BLACK AND WHITE. REVISE THE PLAN TO
 SHOW ALL PERTINENT INFORMATION GRAPHICALLY RATHER THAN
 USING HIGHLIGHTER/COLOR, FBC 107.
  
 SEE FBC 5TH EDITION ACCESSIBLITY 202.3 (ALTERATIONS),
 208.2 (PARKING SPACES), 502 (PARKING SPACES), 206
 (ACCESSIBLE ROUTE).
  
 YOU MAY FIND THE FOLLOWING DOCUMENT USEFUL,
 PARTICULARLY THE INTRODUCTION: "WHEN A BUSINESS
 RESTRIPES A PARKING LOT, IT MUST PROVIDE ACCESSIBLE
 PARKING SPACES AS REQUIRED BY THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN."
  
 HTTP://WWW.ADA.GOV/RESTRIPE.HTM
  
 2. FBC 2014 ACCESSIBILITY ADVISORY 502.3, WHERE THE
 ACCESSIBLE ROUTE MUST CROSS VEHICULAR TRAFFIC LANES,
 MARKED CROSSINGS ENHANCE PEDESTRIAN SAFETY; PLEASE
 INDICATE LOCATION ON PLAN.
  
 3. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE
 THEIR PRINTED NAME AND SIGNATURE ON THE PLAN, FBC 107.
  
 NOT ENOUGH INFORMATION WAS PROVIDED TO PERFORM A
 COMPLETE REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2016-11-22 Cont ID  
Sent By mgonzale Date 2016-11-22 Time   Rev Time 1.00
Received By mgonzale Date 2016-11-22 Time   Sent To ENG
Notes
2016-11-22 15:35:21CONSIDER FOLLOWING CITY OF WPB ADA PARKING.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-07-20 Cont ID  
Sent By Mgonzale Date 2016-07-20 Time   Rev Time 1.00
Received By mgonzale Date 2016-07-20 Time   Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-23 Cont ID  
Sent By cthroop Date 2016-11-23 Time 12:02 Rev Time 0.00
Received By cthroop Date 2016-10-20 Time 10:00 Sent To  
Notes
2016-10-24 10:00:39RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-18 Cont ID  
Sent By shill Date 2016-08-18 Time 06:56 Rev Time 0.00
Received By shill Date 2016-08-16 Time 15:29 Sent To  
Notes
2016-08-16 15:29:22RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-27 Cont ID  
Sent By cpuell Date 2016-07-27 Time 14:19 Rev Time 0.00
Received By cpuell Date 2016-07-12 Time 16:08 Sent To  
Notes
2016-07-12 16:08:49ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2016-10-27 Cont ID  
Sent By njwira Date 2016-10-27 Time 11:04 Rev Time 0.00
Received By njwira Date 2016-10-24 Time 14:31 Sent To ENG
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-07-13 Cont ID  
Sent By shill Date 2016-07-27 Time 07:41 Rev Time 0.00
Received By njwira Date 2016-07-13 Time 11:01 Sent To ENG
Notes
2016-07-13 11:02:357/13/16- PASSED
  
 RESTRIPING CANNOT INCLUDE A CHANGE IN THE TOTAL NUMBER
 OF AVAILABLE PARKING SPACES.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  