Plan Review Details - Permit 16070383
Plan Review Stops For Permit 16070383
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-20 Cont ID  
Sent By mvaldes Date 2016-07-20 Time 17:13 Rev Time 0.00
Received By mvaldes Date 2016-07-20 Time 16:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-14 Cont ID  
Sent By mvaldes Date 2016-07-14 Time 10:53 Rev Time 0.00
Received By mvaldes Date 2016-07-14 Time 10:52 Sent To  
Notes
2016-07-14 11:10:52REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - TO FULLY PASS THE ELECTRICAL REVIEW THE PLANS SHALL
 BE IN COMPLIANCE WITH THE FIRE COMMENTS.
  
 - THE ADDRESS MUST MATCH BOTH APPLICATION AND SHOP
 DRAWINGS PLEASE VERIFY.
  
 - ADD THE DEVICES AS NOTED BY FIRE PLAN EXAMINER AND
 MODIFY RISER ACCORDINGLY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-07-20 Cont ID  
Sent By wjolin Date 2016-07-20 Time 12:47 Rev Time 0.00
Received By wjolin Date 2016-07-20 Time 12:38 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-13 Cont ID  
Sent By wjolin Date 2016-07-13 Time 15:01 Rev Time 0.00
Received By wjolin Date 2016-07-13 Time 14:56 Sent To E
Notes
2016-07-13 15:01:301721 PALM BEACH LAKES BOULEVARD - SUITE E419
 PERMIT #16070383
 MASTER #15110510
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS PROVIDED ON THE PLANS (1741 PALM BEACH
 LAKES BLVD) DOES NOT MATCH THE ADDRESS PROVIDED ON THE
 PERMIT APPLICATION (1721 PALM BEACH LAKES BLVD - SUITE
 E419).
  
 PROVIDE AN EXTERIOR HORN-STROBE DEVICE FOR THE EXTERIOR
 SEATING AREA.
  
 PROVIDE A HORN-STROBE DEVICE INSIDE COOLER #117.
  
 REVISE RISER DIAGRAM WITH DEVICES ADDED FROM PREVIOUS
 COMMENT.
  
 NOTE: OUTLET MALL FIRE ALARM DESIGN REQUIRES THE ENTIRE
 BUILDING (NOT JUST THE SUITE) TO GO INTO GENERAL ALARM
 MODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-20 Cont ID  
Sent By mvaldes Date 2016-07-20 Time 17:13 Rev Time 0.00
Received By mvaldes Date 2016-07-19 Time 14:19 Sent To  
Notes
2016-07-19 14:19:39RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-14 Cont ID  
Sent By mvaldes Date 2016-07-14 Time 11:10 Rev Time 0.00
Received By mvaldes Date 2016-07-12 Time 13:56 Sent To  
Notes
2016-07-12 13:56:17ROUTED TO FIRE