Plan Review Details - Permit 16070380
Plan Review Stops For Permit 16070380
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-08-25 Cont ID  
Sent By jwitmer Date 2016-08-25 Time 06:44 Rev Time 0.00
Received By jwitmer Date 2016-08-25 Time 06:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-13 Cont ID  
Sent By jwitmer Date 2016-08-13 Time 8:30 Rev Time 0.00
Received By jwitmer Date 2016-08-13 Time 7:45 Sent To P
Notes
2016-08-13 08:30:20BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070380
 ADD: 5200 N. FLAGLER DR. SUITE # 2501
 CONT: AMERICAN CONTRACTING INC. (CFC056715)
 TEL: 305-987-5608
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. AUGUST 13/2016
 ACTION: DENIED
  
 NOTE: A SET OF PLANS MAY BE RETAINED TO TAKE TO THE
 DEPARTMENT OF BUSINESS & PROFESSIONAL REGULATION
 !!!!!!!!!!!!!!!!!!!!!!!!
  
 1) PLEASE CLARIFY WHAT WORK IS BEING ACCOMPLISHED UNDER
 THIS PERMIT. DO NOT SHOW WORK THAT IS GOING TO BE
 COMPLETED UNDER A DIFFERENT PERMIT. EXAMPLE
 THE EXTERIOR DOORS AND HURRICANE SHUTTERS. IF THIS WORK
 IS GOING TO BE COMPLETED UNDER THIS PERMIT, THE
 CONTRACTOR OF RECORD, CFC CAN NOT DRAW THESE PLANS
 BECAUSE YOU ARE NOT LICENSED TO DESIGN THE THE WIND
 DESIGN CRITERIA ON THE NEW DOOR LOCATION AND STORM
 SHUTTERS.
 107.1 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 107.3.4.3 CERTIFICATIONS BY CONTRACTORS AUTHORIZED
 UNDER THE PROVISIONS OF SECTION 489.115 FLORIDA
 STATUTES, SHALL BE CONSIDERED EQUIVALENT TO SEALED
 PLANS AND SPECIFICATIONS BY A PERSON LICENSED UNDER
 CHAPTER 471, FLORIDA STATUTES, OR CHAPTER 481 FLORIDA
 STATUTES, BY LOCAL ENFORCEMENT AGENCIES FOR PLANS
 REVIEW FOR PERMITTING PURPOSES RELATING TO COMPLIANCE
 WITH THE WIND-RESISTANCE PROVISIONS OF THE CODE OR
 ALTERNATE METHODOLOGIES APPROVED BY THE FLORIDA
 BUILDING COMMISSION FOR ONE AND TWO-FAMILY DWELLINGS.
  
 107.3.4.3 CERTIFICATIONS BY CONTRACTORS AUTHORIZED.
 PLEASE NOTE THE EXCEPTION TO ENGINEERED PLANS UNDER
 471.003(H) ELECTRICAL/ PLUMBING/ MECHANICAL,
 481.229(1)(C) (BUILDING) REQUIRES THE CONTRACTOR FOR
 THAT TRADE THAT WILL BE LICENSED IN THAT TRADE, WILL
 ALSO BE THE CONTRACTOR THAT DESIGNS THE SYSTEM UNDER
 THAT TRADE. FOR EACH TRADE THE CONTRACTOR RESPONSIBLE
 FOR THE DESIGN UNDER THE TRADE LICENSED IN MUST PRINT
 THEIR NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE
 THESE PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THIS IS
 A CFC LICENSE THAT CAN ONLY DRAW PLUMBING PLANS.
  
 2) SCOPE OF WORK REMOVED.
  
 3) OUT OF THE SCOPE OF LICENSURE FOR A STATE CERTIFIED
 CFC LICENSE!!!!!! PLANS INDICATE NEW FLOOR FINISHES,
 PLEASE SPECIFY THE TYPE OF FLOORS, SEPARATE TEST
 REPORTS ARE REQUIRED FOR TILE VERSES WOOD OR WOOD
 VENEER FLOORING.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 3A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) OUT OF THE SCOPE OF WORK FOR A STATE LICENSED CFC
 CONTRACTOR. !!!! THE PLANS DO NOT HAVE ANY INFORMATION
 FOR THE DROPPED CEILING THROUGHOUT THE SUITE. TYPE OF
 FRAMING MATERIAL, SIZE AND SPACING OF THE FRAMING
 MATERIAL, SPACING FOR CEILING JOIST, IF STIFF BACKS ARE
 REQUIRED FOR THE SPANS NOR THE THICKNESS OF THE FINISH
 CEILING MATERIAL AND TYPE OF FINISH CEILING MATERIAL.
 WILL ALSO NEED TO KNOW THE DEFLECTION LIMITATION OF THE
 FINISH CEILING MATERIAL. 2014 FBC-B TABLE 2506.2 STEEL
 STUDS, NON-LOAD BEARING ASTM C 645 , TABLE 2508.1 STEEL
 FRAMING FOR GYPSUM BOARD ASTM 745 & TABLE 1604.3
 DEFLECTION LIMITATIONS.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-20 Cont ID  
Sent By jwitmer Date 2016-07-20 Time 07:32 Rev Time  
Received By jwitmer Date 2016-07-20 Time 06:45 Sent To  
Notes
2016-07-20 07:32:04BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070380
 ADD: 5200 N. FLAGLER DR. SUITE # 2501
 CONT: AMERICAN CONTRACTING INC.
 TEL: 305-987-5608
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 20/2016
 ACTION: DENIED
  
 1) PLEASE CLARIFY WHAT WORK IS BEING ACCOMPLISHED UNDER
 THIS PERMIT. DO NOT SHOW WORK THAT IS GOING TO BE
 COMPLETED UNDER A DIFFERENT PERMIT. EXAMPLE
 THE EXTERIOR DOORS AND HURRICANE SHUTTERS. IF THIS WORK
 IS GOING TO BE COMPLETED UNDER THIS PERMIT, THE
 CONTRACTOR OF RECORD, CGC CAN NOT DRAW THESE PLANS
 BECAUSE YOU ARE NOT LICENSED TO DESIGN THE THE WIND
 DESIGN CRITERIA ON THE NEW DOOR LOCATION AND STORM
 SHUTTERS.
 107.1 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 107.3.4.3 CERTIFICATIONS BY CONTRACTORS AUTHORIZED
 UNDER THE PROVISIONS OF SECTION 489.115 FLORIDA
 STATUTES, SHALL BE CONSIDERED EQUIVALENT TO SEALED
 PLANS AND SPECIFICATIONS BY A PERSON LICENSED UNDER
 CHAPTER 471, FLORIDA STATUTES, OR CHAPTER 481 FLORIDA
 STATUTES, BY LOCAL ENFORCEMENT AGENCIES FOR PLANS
 REVIEW FOR PERMITTING PURPOSES RELATING TO COMPLIANCE
 WITH THE WIND-RESISTANCE PROVISIONS OF THE CODE OR
 ALTERNATE METHODOLOGIES APPROVED BY THE FLORIDA
 BUILDING COMMISSION FOR ONE AND TWO-FAMILY DWELLINGS.
  
 107.3.4.3 CERTIFICATIONS BY CONTRACTORS AUTHORIZED.
 PLEASE NOTE THE EXCEPTION TO ENGINEERED PLANS UNDER
 471.003(H) ELECTRICAL/ PLUMBING/ MECHANICAL,
 481.229(1)(C) (BUILDING) REQUIRES THE CONTRACTOR FOR
 THAT TRADE THAT WILL BE LICENSED IN THAT TRADE, WILL
 ALSO BE THE CONTRACTOR THAT DESIGNS THE SYSTEM UNDER
 THAT TRADE. FOR EACH TRADE THE CONTRACTOR RESPONSIBLE
 FOR THE DESIGN UNDER THE TRADE LICENSED IN MUST PRINT
 THEIR NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE
 THESE PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL,
  
 2) UNKNOWN AT THIS TIME IF WIND DESIGN CRITERIA WILL BE
 REQUIRED FOR THIS PROJECT IF THE EXTERIOR DOORS AND
 SHUTTERS ARE BEING MOVED THEN THE WIND DESIGN CRITERIA
 WILL BE REQUIRED, PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING AS WELL EXPOSURE D ADJUSTMENT FACTORS FOR
 HEIGHT AND EXPOSURE. ASCE 7-10 FIGURE 30.5-1.THE PLANS
 DO NOT HAVE ANY INFORMATION FOR THE DROPPED CEILING
 THROUGH OUT THE SUITE. TYPE OF FRAMING MATERIAL, SIZE
 AND SPACING OF THE FRAMING MATERIAL, SPACING FOR
 CEILING JOIST, IF STIF BACKS ARE REQUIRED FOR THE SPANS
 NOR THE THICKNESS OF THE FINISH CEILING MATERIAL AND
 TYPE OF FINISH CEILING MATERIAL. WILL ALSO NEED TO KNOW
 THE DEFLECTION LIMITATION OF THE FINISH CEILING
 MATERIAL. 2014 FBC-B TABLE 2506.2 STEEL STUDS, NON-LOAD
 BEARING ASTM C 645 , TABLE 2508.1 STEEL FRAMING FOR
 GYPSUM BOARD ASTM 745 & TABLE 1604.3 DEFLECTION
 LIMITATIONS.
  
 3) PLANS INDICATE NEW FLOOR FINISHES, PLEASE SPECIFY
 THE TYPE OF FLOORS, SEPARATE TEST REPORTS ARE REQUIRED
 FOR TILE VERSES WOOD OR WOOD VENEER FLOORING.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 3A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) THE PLANS DO NOT HAVE ANY INFORMATION FOR THE
 DROPPED CEILING THROUGH OUT THE SUITE. TYPE OF FRAMING
 MATERIAL, SIZE AND SPACING OF THE FRAMING MATERIAL,
 SPACING FOR CEILING JOIST, IF STIF BACKS ARE REQUIRED
 FOR THE SPANS NOR THE THICKNESS OF THE FINISH CEILING
 MATERIAL AND TYPE OF FINISH CEILING MATERIAL. WILL ALSO
 NEED TO KNOW THE DEFLECTION LIMITATION OF THE FINISH
 CEILING MATERIAL. 2014 FBC-B TABLE 2506.2 STEEL STUDS,
 NON-LOAD BEARING ASTM C 645 , TABLE 2508.1 STEEL
 FRAMING FOR GYPSUM BOARD ASTM 745 & TABLE 1604.3
 DEFLECTION LIMITATIONS.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-08 Cont ID  
Sent By mvaldes Date 2016-08-08 Time 11:22 Rev Time 0.00
Received By mvaldes Date 2016-08-08 Time 10:40 Sent To  
Notes
2016-08-08 11:24:57REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE RED LINED STAMPED PROVISO'S.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-14 Cont ID  
Sent By mvaldes Date 2016-07-14 Time 10:14 Rev Time 0.00
Received By mvaldes Date 2016-07-14 Time 09:25 Sent To  
Notes
2016-07-14 10:14:18REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - PROVIDE AN ELECTRICAL FLOOR PLAN SHOWING LOCATIONS OF
 SMOKE DETECTORS, KITCHEN COUNTERTOP GFCI, BATHROOM
 GFCI, LIGHTING IN ALL AREAS WITHIN THE SCOPE OF WORK.
 FBC 107 MINIMUM PLAN REVIEW.
  
 - FBC R E3901.2.4 COUNTERTOP RECEPTACLES, FBC R E3901.3
 SMALL APPLIANCE RECEPTACLES, FBC R E3902.6 KITCHEN
 RECEPTACLES, FBC R E3902.1 BATHROOM RECEPTACLES.
  
 - SMOKE DETECTORS SHALL BE INSTALLED PER RESIDENTIAL
 CODE SECTIONS 314 & 315. ALL NEW RECEPTACLES SHALL BE
 TAMPER RESISTANT IN ACCORDANCE WITH FBC R E4002.14
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-10 Cont ID  
Sent By wjolin Date 2016-08-10 Time 10:57 Rev Time 0.00
Received By wjolin Date 2016-08-10 Time 10:57 Sent To  
Notes
2016-08-10 10:57:295200 NORTH FLAGLER DRIVE - #2501
 PERMIT #16070380
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UNIT SMOKE ALARMS SHALL PROVIDE LOCAL NOTIFICATION ONLY
 AND SHALL NOT BE TIED INTO THE BUILDING FIRE ALARM
 SYSTEM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-07-14 Cont ID  
Sent By wjolin Date 2016-07-14 Time 13:55 Rev Time 0.00
Received By wjolin Date 2016-07-14 Time 13:46 Sent To  
Notes
2016-07-14 13:55:435200 NORTH FLAGLER DRIVE - #2501
 PERMIT #16070380
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UNIT SMOKE ALARMS SHALL PROVIDE LOCAL NOTIFICATION ONLY
 AND SHALL NOT BE TIED INTO THE BUILDING FIRE ALARM
 SYSTEM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-25 Cont ID  
Sent By jwitmer Date 2016-08-25 Time 06:44 Rev Time 0.00
Received By jwitmer Date 2016-08-23 Time 09:51 Sent To  
Notes
2016-08-24 09:51:55RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-19 Cont ID  
Sent By tklarge Date 2016-08-19 Time 13:57 Rev Time 0.00
Received By tklarge Date 2016-08-05 Time 14:32 Sent To  
Notes
2016-08-05 14:32:51B21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-31 Cont ID  
Sent By tklarge Date 2016-07-31 Time 07:49 Rev Time 0.00
Received By tklarge Date 2016-07-12 Time 14:57 Sent To  
Notes
2016-07-12 14:57:22B28

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-08-30 Cont ID  
Sent By jwitmer Date 2016-07-20 Time 07:32 Rev Time  
Received By jwitmer Date 2016-07-20 Time 06:45 Sent To  
Notes
2016-07-20 07:36:26UNKNOWN AT THIS TIME IF IMPACT FEES ARE DUE.

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-08-25 Cont ID  
Sent By tklarge Date 2016-08-25 Time 06:13 Rev Time 0.00
Received By tklarge Date 2016-08-25 Time 06:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-08-19 Cont ID  
Sent By tklarge Date 2016-08-19 Time 13:54 Rev Time 0.00
Received By tklarge Date 2016-08-19 Time 13:48 Sent To  
Notes
2016-08-19 13:55:47COMPLY WITH THE PLUMBING REVIEW COMMENTS FROM THE
 7/31/16 REVIEW.
 1) THE SHOWER SHALL BE NOT LESS THAN 30 INCHES WIDE IN
 THE LEAST DIMENSION AND SHALL BE A MINIMUM OF 900
 SQUARE INCHES.SHOWER COMPARTMENTS NOT LESS THAN 25
 INCHES IN MINIMUM DIMENSIONS SHALL BE A MINIMUM OF 1300
 SQUARE INCHES. 2014 FBC-PLUMBING SEC.417.4.THE PLANS
 SHOW THE MASTER BATH SHOWER WITH A DIMENSION OF 24
 INCHES AT ONE END.
 2) INDICATE ON THE PLAN IF ANY OF THE OTHER PLUMBING
 FIXTURES ARE BEING RELOCATED.WPB AMEND. TO FBC SEC.
 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-07-31 Cont ID  
Sent By tklarge Date 2016-07-31 Time 07:49 Rev Time 0.00
Received By tklarge Date 2016-07-31 Time 07:36 Sent To  
Notes
2016-07-31 07:48:231) THE SHOWER SHALL BE NOT LESS THAN 30 INCHES WIDE IN
 THE LEAST DIMENSION AND SHALL BE A MINIMUM OF 900
 SQUARE INCHES.SHOWER COMPARTMENTS NOT LESS THAN 25
 INCHES IN MINIMUM DIMENSIONS SHALL BE A MINIMUM OF 1300
 SQUARE INCHES. 2014 FBC-PLUMBING SEC.417.4.THE PLANS
 SHOW THE MASTER BATH SHOWER WITH A DIMENSION OF 24
 INCHES AT ONE END.
 2) INDICATE ON THE PLAN IF ANY OF THE OTHER PLUMBING
 FIXTURES ARE BEING RELOCATED.WPB AMEND. TO FBC SEC.
 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  