Plan Review Details - Permit 16070366
Plan Review Stops For Permit 16070366
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-07-28 Cont ID  
Sent By jwitmer Date 2016-07-28 Time 14:06 Rev Time  
Received By jwitmer Date 2016-07-28 Time 13:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-07 Cont ID  
Sent By albarran Date 2016-09-07 Time 11:55 Rev Time 0.00
Received By albarran Date 2016-09-07 Time 11:22 Sent To  
Notes
2016-09-07 11:57:22ALL PREVIOUSLY MENTIONED COMMENTS HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-14 Cont ID  
Sent By albarran Date 2016-07-14 Time 11:03 Rev Time 0.00
Received By albarran Date 2016-07-14 Time 09:10 Sent To  
Notes
2016-07-14 11:04:071ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. SHEET E101: PER FBC-EC405.7 A MINIMUM OF 50% OF ALL
 15 & 20 AMP RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED AS INDICATED IN ASHRAE 90.1 SECTION 8.4.2.
 THIS INCLUDES MODULAR PARTITIONS.
 2. SHEET E102: FBC-E C405.2.2. PROVIDE AUTOMATIC
 LIGHTING SHUTOFF.
 3. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & NCONDITIONED SPACES.
 4. FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS.
 A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING
 POWER DENSITY CHART TO SHOW COMPLIANCE.
 5. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL: DAYLIGHT
 ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN THE
 DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF GENERAL
 AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH
 EITHER SECTION C405.2.2.3.1 OR SECTION C405.2.2.3.2.
 6. SHEET E103: NEC 110.16 ARC-FLASH HAZARD WARNING:
 ELECTRICAL EQUIPMENT IN OTHER THAN DWELLING UNITS
 LIKELY TO REQUIRE SERVICED WHILE ENERGIZED SHALL BE
 FIELD MARKED TO WARN AGAINST POTENTIAL ARC-FAULT
 HAZARDS.
 7. NEC 110.24 THE MAXIMUM AVAILABLE FAULT CURRENT
 DURABLY MARKED AND DATED ON ALL NON-DWELLING ELECTRICAL
 APPARATUS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-07-18 Cont ID  
Sent By scaldero Date 2016-07-18 Time 12:12 Rev Time 0.00
Received By scaldero Date 2016-07-18 Time 11:03 Sent To  
Notes
2016-07-18 12:12:09PERMIT # 16070366
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO:
 1) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
 2) THERE IS AN OPEN FIRE SPRINKLER PERMIT (#16031374)
 FOR THIS SITE, THAT MAY CONFLICT WITH SPRINKLER WORK
 RELATING TO THIS PROJECT.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-08 Cont ID  
Sent By cpuell Date 2016-09-08 Time 15:07 Rev Time 0.00
Received By cpuell Date 2016-08-18 Time 08:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-01 Cont ID  
Sent By lmarchan Date 2016-08-01 Time 16:02 Rev Time 0.00
Received By lmarchan Date 2016-07-13 Time 08:13 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-07-28 Cont ID  
Sent By jwitmer Date 2016-07-28 Time 14:07 Rev Time 0.00
Received By jwitmer Date 2016-07-28 Time 14:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-07-18 Cont ID  
Sent By ccole Date 2016-07-18 Time 15:33 Rev Time 0.00
Received By ccole Date 2016-07-18 Time 15:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-09-08 Cont ID  
Sent By skennedy Date 2016-09-08 Time 17:09 Rev Time 0.00
Received By skennedy Date 2016-09-08 Time 17:09 Sent To  
Notes
2016-09-08 16:24:14MECHANICAL SHEETS CHECKED FOR SIGNATURES.
 9/8/16
2016-07-28 14:11:377/28/2016 ARCHITECTURAL SHEETS CHECKED FOR SIGNATURES.
 JW