| 2016-07-14 11:04:07 | 1ST ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | 1. SHEET E101: PER FBC-EC405.7 A MINIMUM OF 50% OF ALL |
| | 15 & 20 AMP RECEPTACLES SHALL BE AUTOMATICALLY |
| | CONTROLLED AS INDICATED IN ASHRAE 90.1 SECTION 8.4.2. |
| | THIS INCLUDES MODULAR PARTITIONS. |
| | 2. SHEET E102: FBC-E C405.2.2. PROVIDE AUTOMATIC |
| | LIGHTING SHUTOFF. |
| | 3. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & NCONDITIONED SPACES. |
| | 4. FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. |
| | A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL |
| | CONNECTED LIGHTING POWER CALCULATED UNDER SECTION |
| | C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER |
| | CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING |
| | POWER DENSITY CHART TO SHOW COMPLIANCE. |
| | 5. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL: DAYLIGHT |
| | ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN THE |
| | DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF GENERAL |
| | AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH |
| | EITHER SECTION C405.2.2.3.1 OR SECTION C405.2.2.3.2. |
| | 6. SHEET E103: NEC 110.16 ARC-FLASH HAZARD WARNING: |
| | ELECTRICAL EQUIPMENT IN OTHER THAN DWELLING UNITS |
| | LIKELY TO REQUIRE SERVICED WHILE ENERGIZED SHALL BE |
| | FIELD MARKED TO WARN AGAINST POTENTIAL ARC-FAULT |
| | HAZARDS. |
| | 7. NEC 110.24 THE MAXIMUM AVAILABLE FAULT CURRENT |
| | DURABLY MARKED AND DATED ON ALL NON-DWELLING ELECTRICAL |
| | APPARATUS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |