Plan Review Details - Permit 16070328
Plan Review Stops For Permit 16070328
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2016-07-27 Cont ID  
Sent By jwitmer Date 2016-07-27 Time 16:40 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-12 Cont ID  
Sent By jwitmer Date 2016-07-12 Time 06:29 Rev Time 0.00
Received By jwitmer Date 2016-07-12 Time 05:58 Sent To  
Notes
2016-07-12 06:19:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070328
 ADD: 2708 BROADWAY
 CONT: GULFSTREAM ROOFING/ REROOF FLAT ROOF
 TEL: 786-357-5327
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 12/2016
 ACTION: DENIED
  
 1) THE ROOFING PACKAGE SUBMITTED HAS A COVER LETTER
 STATING THIS PACKAGE IS IN DRAFT FORMAT. PLEASE
 RESUBMIT ONCE THE PACKAGE IS COMPLETE AND ALL PAPERWORK
 REQUIRED CAN BE OBTAINED, THEN SUBMIT TO THE BUILDING
 DEPARTMENT.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED
 BY THE CODE, THE CONSTRUCTION DOCUMENTS SHALL
 ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING
 SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE
 OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE
 SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.
  
 2) REROOF FLAT ROOF: THE PRODUCT APPROVAL SUBMITTED IS
 A MIAMI-DADE NOA 14-1030.02 GAF RUBEROID MODIFIED
 BITUMEN ROOF SYSTEM FOR WOOD DECKS. SHEETS 26 & 27
 SUBMITTED MEMBRANE TYPE SBS/SBS COLD APPLIED WOOD DECK
 NON-INSULATED. PLEASE BE AWARE THERE ARE 7 OPTIONS
 WITHIN THIS SYSTEM, EACH WITH VARYING PRESSURES DUE TO
 THE NAILING PATTERNS. ALL OF THE OPTIONS ARE LOW IN
 PRESSURES AND ALL OPTIONS ALLOW GENERAL LIMITATION # 7
 WHICH REQUIRES ENHANCED FASTENING CALCULATIONS (RAS
 117) BY EITHER A FLORIDA ENGINEER OR ARCHITECT. NOTE
 EXPOSURE C. 2014 FBC-B , 1609.6.4.4.1 COMPONENTS &
 CLADDING.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
  
  
  
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2016-07-27 Cont ID  
Sent By jwitmer Date 2016-07-27 Time 16:40 Rev Time 0.00
Received By jwitmer Date 2016-07-21 Time 10:58 Sent To  
Notes
2016-07-22 10:58:37RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-12 Cont ID  
Sent By jwitmer Date 2016-07-12 Time 06:29 Rev Time 0.00
Received By jwitmer Date 2016-07-11 Time 16:08 Sent To  
Notes