Plan Review Details - Permit 16070282
Plan Review Stops For Permit 16070282
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-12-15 Cont ID  
Sent By shill Date 2016-12-15 Time 17:17 Rev Time 0.00
Received By shill Date 2016-12-15 Time 17:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-07 Cont ID  
Sent By shill Date 2016-12-07 Time 09:13 Rev Time 0.00
Received By shill Date 2016-12-07 Time 09:13 Sent To  
Notes
2016-12-07 09:19:40REVISED SHEET 1.3 (ELECTRICAL CHANGES ONLY)
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-19 Cont ID  
Sent By shill Date 2016-07-19 Time 12:31 Rev Time 0.00
Received By shill Date 2016-07-19 Time 12:31 Sent To  
Notes
2016-07-19 12:39:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 107, PLAN IS TO BE CLEAR AS TO SCOPE. THIS
 PERMIT WAS ISSUED FOR USE AS A STORAGE AREA, AND THE
 PLAN WAS PREPARED BY A DESIGN PROFESSIONAL. ONLY THE
 DESIGN PROFESSIONAL CAN CHANGE THE DESIGN. IT APPEARS
 THAT THIS MAY BE A CHANGE OF OCCUPANCY, BUT LIFE
 SAFETY/CODE COMPLIANCE ISSUES WERE NOT A PART OF THE
 SKETCH PREPARED AND SUBMITTED BY STONY ELECTRIC.
  
 THE EOR IS TO REVISE THE PLAN. THE PLAN IS TO INCLUDE
 ALL INFORMATION REQUIRED TO DETERMINE CODE COMPLIANCE
 (INCLUDING INFORMATION REGARDING THE PROPOSED
 EQUIPMENT). INSUFFICIENT INFORMATION HAS BEEN PROVIDED;
 A COMPLETE LIST CANNOT BE GIVEN AT THIS TIME.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-12-15 Cont ID  
Sent By mvaldes Date 2016-12-15 Time 13:23 Rev Time 0.00
Received By mvaldes Date 2016-12-15 Time 13:16 Sent To B
Notes
2016-12-15 13:23:22ROUTED TO SH

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-12-05 Cont ID  
Sent By mvaldes Date 2016-12-05 Time 17:24 Rev Time 0.00
Received By mvaldes Date 2016-12-05 Time 16:22 Sent To B
Notes
2016-12-05 17:24:592ND REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] SERVICE CONDUCTORS UNDERSIZED 3/0 WIRE IS REQUIRED
 FOR 200 AMPS, PROVIDE COMPLETE LOAD CALCULATION ,
 INCLUDE NEW 100 AMP PANEL SCHEDULE. FBC-107.3.5.3
  
 2] THE METER BEING USED AS A J-BOX MUST NOT EXCEED 75%
 OF THE CROSS SECTIONAL AREA INCLUDING TAPS & SPLICES. A
 WARNING LABEL MUST BE APPLIED IDENTIFYING THE CLOSEST
 DISCONNECTING MEANS FOR THE FEED THROUGH CONDUCTORS.
 NEC 312.8 ADD A BLOCK NOTE.
  
 3] EMERGENCY/EXIT LIGHTING SHALL BE FED BY LIGHTING
 CIRCUIT OF SAME LOCAL AREA. NEC 700.12(F)(4)

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-11 Cont ID  
Sent By mvaldes Date 2016-07-11 Time 14:21 Rev Time 0.00
Received By mvaldes Date 2016-07-11 Time 13:11 Sent To  
Notes
2016-07-11 14:23:11JOB PERMIT NUMBER: MASTER 15071032, REVISION 16070282
 JOB ADDRESS: 2015 PARKER AVE
 WEST PALM BEACH FLORIDA
 DATE: JULY 11 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - PROVIDE LOAD CALCS AND A RISER DIAGRAM SHOWING PROPER
 SERVICE FEEDER CONDUCTOR SIZES REFERENCE NEC TABLE
 310.(B)(16)
 - WHEN MORE THAN 3 CURRENT CARRYING CONDUCTORS ARE
 INSTALLED IN A RACEWAY ADJUSTMENT FACTORS MUST BE TAKEN
 INTO CONSIDERATION, REFERENCE NEC TABLE 310.15(B)(3)(A)
 - THE EXISTING PANEL BEING USED AS A J-BOX MUST HAVE A
 WARNING LABEL THAT IDENTIFIES THE CLOSEST DISCONNECTING
 MEANS FOR ANY FEED THROUGH CONDUCTORS. NEC 312.8(3)
 - GFCI PROTECTION REQUIRED FOR ALL COMMERCIAL KITCHENS
 NEC 210.8(B)
 - INSTALL AN INTERSYSTEM BONDING TERMINAL AT THE
 SERVICE GROUNDING ELECTRODE SYSTEM. NEC 250.94
 - COMPLY WITH MANDATORY LIGHTING CONTROLS FOR NEW
 LIGHTING PER FBC-E C405
 - RECESSED LIGHTING MUST BE IC RATED AND SEALED TO
 LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND UN
 CONDITIONED SPACES. FBC-E C402.4.8
 - MEANS OF EGRESS ILLUMINATION REQUIRED, EMERGENCY &
 EXIT LIGHTS. FBC 1006.1, 1006.2, 1011.
 - REFLECT A NEW BUILDING PLAN AND FURTHER COMMENTS MAY
 BE ASKED FOR MINIMUM PLAN REVIEW. FBC 107
 - STEPHEN GAYDOSH, PE IS THE ELECTRICAL DESIGNER OF
 RECORD. ANY CHANGE TO HIS DESIGN MUST COME FROM HIM OR
 OTHERWISE DEMONSTRATE HIS APPROVAL NOT ACCEPTABLE PER
 FAC 61G15-23.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T
 HESITATE TO CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-12-15 Cont ID  
Sent By shill Date 2016-12-15 Time 17:17 Rev Time 0.00
Received By shill Date 2016-12-13 Time 14:57 Sent To  
Notes
2016-12-13 14:58:28MVALDES'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-07 Cont ID  
Sent By shill Date 2016-12-07 Time 09:33 Rev Time 0.00
Received By shill Date 2016-11-23 Time 13:41 Sent To  
Notes
2016-12-07 09:20:0712/7 TO FIRE BOX
  
  
2016-11-23 13:41:49RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-19 Cont ID  
Sent By shill Date 2016-07-19 Time 12:39 Rev Time 0.00
Received By shill Date 2016-07-08 Time 15:53 Sent To  
Notes
2016-07-08 15:53:48REVISION ROUTED TO MVALDES

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-12-07 Cont ID  
Sent By shill Date 2016-12-07 Time 09:25 Rev Time 0.00
Received By shill Date 2016-12-07 Time 09:25 Sent To  
Notes
***NONE***