| 2016-08-13 11:05:33 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16070269 |
| | ADD: 2427 PRESIDENTIAL WAY SUITE # 301 |
| | CONT: FINE LINE CONSTRUCTION |
| | TEL: 561-427-5664 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: SAT. AUGUST 13/2016 |
| | ACTION: DENIED |
| | |
| | 1) 3RD REQUEST. SEMI-COMPLIED.THE DEMOLITION PLAN |
| | INDICATES THE REMOVAL OF ALL FLOOR FINISHES THROUGH OUT |
| | THE UNIT. SHEET A.02 THIS REVIEW MAKES REFERENCE TO |
| | WHICH ROOMS WILL RECEIVE WOOD FLOOR FINISHES AND WHICH |
| | WILL RECEIVE MARBLE FINISHES. |
| | _______________________________________________________ |
| | _______________________________________________________ |
| | ___ |
| | E-MIAL SENT SAT. AUG. 13/16 11:24 AM |
| | |
| | GOOD MORNING MR. STEINBORG, |
| | I'VE BEEN REVIEWING THE PLANS FOR 2427 PRESIDENTIAL WAY |
| | THE PLANS INDICATE THE USE OF WOOD FLOORING THROUGH THE |
| | UNIT WITH THE EXCEPTION OF THE RESTROOMS AND LAUNDRY |
| | ROOM THE INSTALLATION OF MARBLE IN THESE ROOMS. WE ONLY |
| | HAVE TESTING FOR THE PROFLEX RCU-500 FOR MARBLE/ TILE. |
| | NO ONE TO DATE HAS BROUGHT IN THE TEST REPORTS TO USE |
| | THIS PRODUCT ON WOOD. WE WILL NEED THE ACTUAL TEST |
| | DOCUMENTS FOR THE FLOOR INSULATION TESTED WITH A WOOD |
| | FINISH FLOOR ABOVE. PLEASE ALSO NOTE THE SUBMITTED |
| | DOCUMENTS SUBMITTED ONCE OPENED ARE NOLONGER ATTACHED |
| | TO THIS E-MAIL. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | _______________________________________________________ |
| | _______________________________________________________ |
| | PLAN REVIEW NOTES |
| | |
| | THE PLANS REFER BACK TO THE REQUIRED TESTING REPORTS. I |
| | SPOKE LAST WEEK WITH A DESIGNER ON THIS PROJECT. DO NOT |
| | SEND IN SPEC SHEETS, WE NEED THE ACTUAL TEST. SUBMITTED |
| | IS PROFLEX MSC 90, THIS DOES NOT MEET THE REQUIREMENT |
| | WHEN YOU ACTUALLY SEE THE DOCUMENTED TEST. NEITHER DID |
| | THE DESIGNER NOR CONTRACTOR SUBMIT THE FLAME SPREAD |
| | TEST REPORT REQUESTED BELOW. |
| | CURRENTLY THE ONLY PRODUCT THAT HAS MET ALL OF THE |
| | REQUIREMENTS FOR TILE ON A 6 INCH SLAB IS THE PRODUCT |
| | PROFLEX RCU-500 WHICH IS 1/2 INCH THICK. STC 53 & IIC |
| | 50, |
| | FOR THE USE OF TILE/ MARBLE, 6 INCH CONCRETE SLAB/ NO |
| | DROPPED CEILING. |
| | |
| | |
| | PLEASE PROVIDE COMPLIANCE WITH THE 2014 FBC-B. |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 1A)2ND REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE |
| | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 1B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 1C) 2ND REQUEST. FLAME SPREAD- FBC-B 2014 603.1. |
| | EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |