Plan Review Details - Permit 16070268
Plan Review Stops For Permit 16070268
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-08-27 Cont ID  
Sent By tklarge Date 2016-08-27 Time 07:09 Rev Time 0.00
Received By tklarge Date 2016-08-27 Time 04:47 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-07-18 Cont ID  
Sent By tklarge Date 2016-07-18 Time 15:06 Rev Time 0.00
Received By tklarge Date 2016-07-18 Time 15:06 Sent To  
Notes
2016-07-18 15:06:341) SHT. K2.111.1 - ITEM #38 IS SHOWN WITH A 3/4 INCH
 GAS SIZE BUT THE SCHEDULE ON SHT. P5.403 SHOWS THE GAS
 SIZE AS 1 1/4 INCH. CLARIFY. 2ND REQUEST
 2) SHT. K2.112.1 - THE UTILITY SCHEDULE SHOWS ITEM 3146
 WITH A 3/4 INCH GAS SIZE BUT SHT. P5.403 SHOWS AN 1 1/4
 GAS SIZE. CLARIFY. 2ND REQUEST.
 3) SHT. K2.113.1 - THE UTILITY SCHEDULE SHOWS ITEM #
 246 WITH A 3/4 INCH GAS SIZE BUT SHT. P5.402 SCHEDULE
 SHOWS 1 1/4 INCHES.CLARIFY.2ND REQUEST.
 4) SHT.K2.114.1 - THE UTILITY SCHEDULE SHOWS ITEM # 354
 WITH A 3/4 INCH GAS SIZE BUT SHT. P5.402 SCHEDULE SHOWS
 1 1/4 INCHES. CLARIFY.2ND REQUEST.
 NOTE - ON COMMENTS # 1- #4, ALL THAT WAS DONE WAS THE
 PIPE SIZES HAVE BEEN REVERSED TO WHAT THEY WERE
 PREVIOUSLY. THEY ARE STILL SHOWING TWO DIFFERENT PIPE
 SIZES. NOTHING CORRELATES.
 5) PLEASE EXPLAIN HOW YOU ARRIVED AT THE REQUIRED CUBIC
 FEET PER MINUTE OF COMBUSTION AIR OF 0.00035 CFM PER
 1000 BTU'S WHEN THE 2014 FGC SEC. 304.9 REQUIRES 0.35
 CFM OF COMBUSTION AIR PER 1000 BTU'S.YOUR CALCULATIONS
 DO NOT MAKE ANY SENSE TO ME. PLEASE CLARIFY AND SUBMIT
 REVISED COMBUSTION AIR CALCULATIONS.
 6) SECTION 304.9.3 SPECIFICALLY REQUIRES THAT WHERE
 COMBUSTION AIR IS PROVIDED BY THE BUILDING'S MECHANICAL
 VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE
 SPECIFIED CCOMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION RATE. IF COMBUSTION AIR IS
 MECHANICALLY SUPPLIED THROUGH AN HVAC SYSTEM, THE
 SYSTEM MUST DELIVER THE REQUIRED COMBUSTION AIR RATE
 ABOVE AND BEYOND ANY OUTDOOR AIR RATE SUPPLIED FOR
 VENTILATION OF THE OCCUPIED SPACES. SUBMIT CALCULATIONS
 THAT SHOW COMPLIANCE WITH THIS CODE SECTION.
 7) THE NOA'S FOR THE LOUVERS FOR COMBUSTION AIR TO THE
 LAUNDRY ROOMS SHALL BE SUBMITTED FOR REVIEW PRIOR TO
 INSTALLATION.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-29 Cont ID  
Sent By lmarchan Date 2016-08-29 Time 11:36 Rev Time 0.00
Received By lmarchan Date 2016-08-11 Time 12:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-18 Cont ID  
Sent By lmarchan Date 2016-07-18 Time 15:26 Rev Time 0.00
Received By lmarchan Date 2016-07-12 Time 08:05 Sent To  
Notes
2016-07-13 08:06:06**PLANS UNDER 16070270**

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-08-27 Cont ID  
Sent By tklarge Date 2016-08-27 Time 07:09 Rev Time 0.00
Received By tklarge Date 2016-08-27 Time 07:09 Sent To  
Notes
***NONE***