Plan Review Details - Permit 16070262
Plan Review Stops For Permit 16070262
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-08-30 Cont ID  
Sent By jwitmer Date 2016-08-30 Time 11:51 Rev Time 0.00
Received By jwitmer Date 2016-08-30 Time 11;05 Sent To  
Notes
2016-08-30 11:54:318/30/2016 BLDG. PASSED, NO OLD PLANS NOR PERMIT
 APPLICATION, NO PLANS IN DENIED DRAWER UNDER SMALL C.
 JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-01 Cont ID  
Sent By jwitmer Date 2016-08-01 Time 16:51 Rev Time 0.00
Received By jwitmer Date 2016-08-01 Time 16:14 Sent To  
Notes
2016-08-01 16:51:20BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070262
 ADD: 6501 S. DIXIE HWY. SUITE # 103
 CONT: CONKLING & LEWIS CONSTRUCTION
 TEL: 561-833-4441
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUGUST 01/2016
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE WORK BEING
 COMPLETED IN UNIT # 103 WHERE AS PLANS WERE SUBMITTED
 FOR UNITS 101 AND 103. EITHER ADD THE SCOPE OF WORK FOR
 UNIT 101 TO THE APPLICATION OR PULL THE PLANS FOR UNIT
 101AND COME IN UNDER SEPARATE PERMIT FOR UNIT 101.
 ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.3.
  
 2) THE PLANS HAVE BEEN REDUCED IN SIZE, THE PLANS
 INDICATE THEY ARE ? INCH SCALE BUT ARE UNDER 1/8 INCH
 SCALE. 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE.
  
 3) THERE IS NO OWNERSHIP OF THE PLANS, WHO DREW THE
 PLANS. 105.3.1.2 NO PERMIT MAY BE ISSUED FOR ANY
 BUILDING CONSTRUCTION. THE DESIGNER OF RECORD(
 QUALIFIER OF COMPANY) FOR THE PLANS SUBMITTED SHALL
 TAKE OWNERSHIP BY PRINTING THEIR NAME, SIGNING THEIR
 NAME AND PRINT THEIR LICENSE NUMBER ON THE PLANS.
  
 4) PLEASE INDICATE TO WHAT CODES THE PLANS WERE
 DEVELOPED, UNDER THE 2014 EXISTING BUILDING CODE PLEASE
 PROVIDE HOW COMPLIANCE WITH 2014 EXISTING BUILDING CODE
 SECTION 301.1 GENERAL.
 THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION
 OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY
 WITH ONE OF THE METHODS LISTED IN SECTIONS 301.1.1
 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT.
 APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR
 ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A
 SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE
 OFFICIAL.
  
 5) PLEASE IDENTIFY WHERE THE AREA OF WORK IS TO OCCUR
 UNDER THE SCOPE OF THIS PERMIT. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-24 Cont ID  
Sent By vperez Date 2016-08-24 Time 07:37 Rev Time 0.00
Received By vperez Date 2016-08-24 Time 07:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-11 Cont ID  
Sent By vperez Date 2016-07-11 Time 12:27 Rev Time 0.00
Received By vperez Date 2016-07-11 Time 12:27 Sent To  
Notes
2016-07-11 12:27:57INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLANS PROVIDED ARE INSUFFICIENT. PLANS ARE TO
 REFLECT PER SCOPE LISTED ON APPLICATION ALL
 REQUIREMENTS PER FBC 107.3.5- MINIMUM PLAN REVIEW.
 2. PLANS ARE TO BE SIGNED AND SEALED BY AOR OR EOR, IF
 QUALIFIER IS DESIGNING DRAWINGS MUST SIGN AND NOTARIZED
 ELECTRICAL SHEETS. FBC 107.3.5- MINIMUM PLAN REVIEW
 3. PROVIDE A GENERAL NOTE TO INDICATE LOW VOLTAGE TO BE
 UNDER SEPARATE PERMIT.
 4. PROVIDE FIXTURE SPECS AND DETAILS OF INSTALLATIONS.
 5. PROVIDE CUT SHEET FOR ALL LIGHTING CONTROLS PANEL
 AND ACCESSORIES AND SHOW SEQUENCE OF OPERATION AS PER
 FBC ENERGY CONSERVATION C405.7
 6. LABEL ON DRAWING WHAT IS EXISTING TO REMAIN, NEW,
 RELOCATED ETC.
 7. LABEL CIRCUIT ID FOR ALL NEW POWER AND LIGHTING
 OUTLETS.
 8. PROVIDE A FIXTURE LEGEND.
 9. PROVIDE A REVISED PANEL SCHEDULE REFLECTING ALL
 CIRCUITS AND NEW LOADS BEING ADDED INCLUDING
 MECHANICAL.
 10. SHOW PANEL LOCATIONS FOR ALL SCOPE REFLECTING
 PROPER CLEARANCE PER NEC 110.26
 11. A COMPLETE REVIEW IN ACCORDANCE WITH FBC CANNOT BE
 COMPLETE DUE TO PENDING INFORMATION.
 12. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-26 Cont ID  
Sent By wjolin Date 2016-08-26 Time 13:53 Rev Time 0.00
Received By wjolin Date 2016-08-26 Time 13:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-28 Cont ID  
Sent By wjolin Date 2016-07-28 Time 09:54 Rev Time 0.00
Received By wjolin Date 2016-07-28 Time 09:46 Sent To  
Notes
2016-07-28 09:54:076501 SOUTH DIXIE HIGHWAY SUITE #103
 PERMIT #16070262
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SEVERAL OF THE PLAN SHEETS ARE NAMED "A1" OR "LS1."
  
 THE SCOPE OF WORK TO BE PERFORMED ON THE PLANS IS NOT
 CLEAR.
  
 PROVIDE A DETAILED LIFE SAFETY PLAN SHOWING ALL
 OCCUPANCY TYPES, OCCUPANT LOADS, FIRE RATED WALLS,
 EXITS, EXIT SIGNS, EMERGENCY LIGHTING, TRAVEL
 DISTANCES, COMMON PATH OF TRAVEL ETC.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-12 Cont ID  
Sent By gjohnson Date 2016-09-12 Time 16:01 Rev Time 0.00
Received By gjohnson Date 2016-08-17 Time 13:50 Sent To  
Notes
2016-08-19 13:51:15B03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-02 Cont ID  
Sent By ccole Date 2016-08-02 Time 13:39 Rev Time 0.00
Received By ccole Date 2016-07-08 Time 09:04 Sent To  
Notes
2016-07-27 09:05:50B01

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-08-24 Cont ID  
Sent By ccole Date 2016-08-24 Time 10:17 Rev Time 0.00
Received By ccole Date 2016-08-24 Time 10:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-02 Cont ID  
Sent By ccole Date 2016-08-02 Time 13:32 Rev Time 0.00
Received By ccole Date 2016-08-02 Time 13:32 Sent To  
Notes
2016-08-02 13:33:371ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #16070262
 8/2/16
  
 1) PROVIDE CLEAR, LEGIBLE PLANS AT A MINIMUM 1/8"
 SCALE- SECTION 107.2.1.4 WPB AMENDMENTS TO THE FBC.
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 3) PROVIDE MECHANICAL PLANS THAT CLEARLY INDICATE ATHE
 SCOPE OF WORK WITH CORRESPONDING DRAWINGS AND DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-09-12 Cont ID  
Sent By gjohnson Date 2016-09-12 Time 16:00 Rev Time 0.00
Received By gjohnson Date 2016-09-12 Time 16:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-02 Cont ID  
Sent By tklarge Date 2016-08-02 Time 14:08 Rev Time 0.00
Received By tklarge Date 2016-08-02 Time 13:48 Sent To  
Notes
2016-08-02 14:08:311) PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE PER
 WPB AMEND. TO FBC SEC.107.2.1.4. THE SUBMITTED PLANS
 ARE ILLEGIBLE.
 2) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. WPB AMEND. TO FBC
 SEC.107.2.1.
 3) CLEARLY INDICATE ON THE PLAN THE ENTIRE SCOPE OF
 PLUMBING WORK (IF ANY) THAT WILL BE DONE IN THIS UNIT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  