Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-07-20 Cont ID  
Sent By wjolin Date 2016-07-20 Time 15:06 Rev Time 0.00
Received By wjolin Date 2016-07-20 Time 14:54 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-08 Cont ID  
Sent By wjolin Date 2016-07-08 Time 13:39 Rev Time 0.00
Received By wjolin Date 2016-07-08 Time 13:31 Sent To  
Notes
2016-07-08 13:39:481721 PALM BEACH LAKES BOULEVARD - E419
 PERMIT #16070187
 MASTER #15110510
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 PLANS INDICATE THE INSTALLATION OF 4 HOODS; HOWEVER,
 THE PERMIT INDICATES ONLY 3 HOODS ARE BEING INSTALLED.
  
 PROVIDE A FLOOR PLAN SHOWING LOCATION OF THE HOODS.
  
 PROVIDE A ROOF PLAN SHOWING EXHAUST TERMINATION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-22 Cont ID  
Sent By ccole Date 2016-07-22 Time 12:28 Rev Time 0.00
Received By ccole Date 2016-07-19 Time 12:52 Sent To  
Notes
2016-07-20 12:53:08RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-08 Cont ID  
Sent By wjolin Date 2016-07-08 Time 13:39 Rev Time 0.00
Received By wjolin Date 2016-07-08 Time 13:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-07-22 Cont ID  
Sent By ccole Date 2016-07-22 Time 12:28 Rev Time 0.00
Received By ccole Date 2016-07-22 Time 12:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-07 Cont ID  
Sent By ccole Date 2016-07-07 Time 14:33 Rev Time 0.00
Received By ccole Date 2016-07-07 Time 14:32 Sent To FIRE
Notes
2016-07-07 15:28:521ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16070187
 7/6/16
  
 1) PLEASE NOTE THAT MANY OF THE REQUIRED DETAILS AND
 NOTES FOR THE PROPOSED KITCHEN HOODS PROJECT ARE FOUND
 IN THE MAIN PERMIT SET OF PLANS- #15110510 THAT WERE
 PREPARED BY THE EOR FROM INTERPLAN. THE EOR FOR THIS
 PROJECT- BUCHANAN P.E. MUST PROVIDE THESE NOTES AND
 DETAILS ON THIS SEPARATELY PERMITTED SETS OF PLANS-
 REFER TO MAIN PERMIT SHEETS M2.0, M4.0, & M4.1 AS THEY
 PERTAIN TO THE FOLLOWING COMMENTS:
  
 A) PROVIDE AIR VELOCITY CALCULATIONS FOR THE GREASE
 DUCTS- SECTION 506.3.4
  
 B) PROVIDE A DETAIL SHOWING REQUIRED CLEARANCES TO
 COMBUSTIBLES FOR THE HOODS- SECTION 507.9.
  
 C) PROVIDE A DETAIL SHOWING REQUIRED CLEARANCES TO
 COMBUSTIBLES FOR THE GREASE DUCTS- SEE SECTION 506.3.6
 & 506.3.11. IF DUCT WRAP IS TO BE USED, PROVIDE A
 SUBMITTAL FOR THE PRODUCT WITH SHOP DRAWING APPROVAL
 SIGNATURE BY THE EOR- SEE SECTION 506.3.11.2
  
 D) PROVIDE A DETAIL SHOWING THE CLEARANCE DISTANCES FOR
 THE EXHAUST FAN DISCHARGES ABOVE THE ROOF SURFACES-
 506.3.13.
  
 E) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE REQUIRED
 CLEARANCE DISTANCES FOR THE FOUR EXHAUST TERMINATIONS
 TO MECHANICAL AND GRAVITY AIR INTAKES INTO THE
 BUILDING.
  
 F) PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE ROOF TOP FANS AND SUBMIT THE NOA'S
 SHOWN ON SHEET NO. 3 WITH SHOP DRAWING APPROVAL
 SIGNATURES BY THE EOR.
  
 G) REFER TO SECTION 508.1.1 AND SHOW COMPLIANCE FOR
 MAKEUP AIR TEMPERATURE.
  
 H) SHEET 3: PROVIDE THE TAG INFORMATION FOR FAN UNIT #4
 SHOWN IN THE EXHAUST FAN INFORMATION SCHEDULE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  