| 2016-07-07 06:56:26 | THE SUBMITTED PLANS ARE SEVERELY DEFICIENT WITH THE |
| | REQUIRED INFORMATION IN ORDER TO PERFORM A THOROUGH AND |
| | COMPREHENSIVE REVIEW, COMPLY WITH ALL OF THE FOLLOWING |
| | REQUIREMENTS. |
| | |
| | 1.) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING |
| | |
| | (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO |
| | FBC SEC.107.2.1. |
| | |
| | 2.) TYPE OF GAS (LP OR NATURAL). |
| | |
| | 3.) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. |
| | SEC. G2413.2. . |
| | |
| | 4.) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE |
| | AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS |
| | SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426. |
| | |
| | 5.) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | |
| | 6) SUBMIT A PLAN SHOWING THE LOCATION OF THE TANKLESS |
| | WATER HEATER AND THE GENERATOR. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | |
| | 7) THE GENERATOR INSTALLATION SHALL COMPLY WITH NFPA 37 |
| | AND SHALL MEET THE REQUIREMENTS OF UL2200 PER 2014 FGC |
| | SEC.616.1. |
| | |
| | 8) SHOW THE DISTANCE OF THE GENERATOR FROM THE EXTERIOR |
| | WALL OF THE STRUCTURE. THE GENERATOR SHALL BE A MINIMUM |
| | OF 5 FT. FROM AN EXTERIOR WALL UNLESS THE WALL IS ONE |
| | HOUR FIRE RATED CONSTRUCTION PER NFPA 37. |
| | |
| | 9) SHOW THE LOCATION OF ALL DOORS AND WINDOWS ON THE |
| | PLAN AND THE DISTANCE FROM THE GENERATOR EXHAUST. THE |
| | GENERATOR EXHAUST SHALL BE A MINIMUM OF 10 FEET FROM |
| | DOORS AND WINDOWS. FGC SEC. |
| | |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |