Plan Review Details - Permit 16070073
Plan Review Stops For Permit 16070073
Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2016-12-16 Time 11:08 Sent To  
Notes
2016-12-16 11:08:36RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-14 Cont ID  
Sent By cpuell Date 2016-12-14 Time 15:31 Rev Time 0.00
Received By cpuell Date 2016-12-13 Time 13:22 Sent To  
Notes
2016-12-13 13:22:27RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-19 Cont ID  
Sent By lmarchan Date 2016-07-19 Time 08:18 Rev Time 0.00
Received By lmarchan Date 2016-07-05 Time 10:18 Sent To  
Notes
2016-11-21 17:28:54SPOKE TO HOMEOWNER ON 11/21/2016. I EXPLAINED AS PER
 THE SUBMITTED HEAT LOAD CALCULATION, THE TOTAL BTUH FOR
 LEVEL 1 IS 27415 AND AS PER ENERGY CALCULATIONS 36,000
 BTU -16 SEER. THE SUBMITTED HEAT LOAD CALCULATION TOTAL
 BTUH FOR LEVEL 2 IS 27461 AND AS PER ENERGY
 CALCULATIONS 36,000 BTU -16 SEER. HEAT LOADS AND ENERGY
 CALCULATIONS NEED TO BE REVISED TO MEET INSTALLATION OR
 INSTALLATION HAS TO CONFORM TO SUBMITTED DOCUMENT.
 JORGE V. 11/21/2016.
2016-07-06 10:19:42TLARGE'S DESK

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-12-19 Cont ID  
Sent By jvalido Date 2016-12-19 Time 17:08 Rev Time 0.00
Received By jvalido Date 2016-12-19 Time 16:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-12-13 Cont ID  
Sent By jvalido Date 2016-12-13 Time 17:20 Rev Time 0.00
Received By jvalido Date 2016-12-13 Time 16:09 Sent To  
Notes
2016-12-13 17:14:47CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE TWO SETS OF PLANS. ONLY ONE SUBMITTED.
  
 FLORIDA ENERGY CODE FBC 2014
  
 (2) PROVIDE APPROVED HEAT LOADS TO MATCH REVISED FORM
 R405-2014 ENERGY CALCULATIONS.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-18 Cont ID  
Sent By skennedy Date 2016-07-18 Time 17:23 Rev Time 0.00
Received By jvalido Date 2016-07-18 Time 16:39 Sent To  
Notes
2016-07-18 17:05:59CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 MAKE CORRECTIONS TO DUCT SIZES AND CFM QUANTITIES AS
 PER THE HEAT LOAD CALCULATIONS SUBMITTED.
  
 FLORIDA ENERGY CODE FBC 2014
  
 R403.6.1.1 COOLING EQUIPMENT CAPACITY. COOLING ONLY
 EQUIPMENT SHALL BE SELECTED SO THAT ITS TOTAL CAPACITY
 IS NOT LESS THAN THE CALCULATED TOTAL LOAD, BUT NOT
 MORE THAN 1.15 TIMES GREATER THAN THE TOTAL LOAD
 CALCULATED ACCORDING TO THE PROCEDURE SELECTED IN
 SECTION 403.6, OR THE CLOSEST AVAILABLE SIZE PROVIDED
 BY THE MANUFACTURER?S PRODUCT LINES. THE CORRESPONDING
 LATENT CAPACITY OF THE EQUIPMENT SHALL NOT BE LESS THAN
 THE CALCULATED LATENT LOAD.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-07-07 Cont ID  
Sent By tklarge Date 2016-07-07 Time 14:40 Rev Time 0.00
Received By tklarge Date 2016-07-07 Time 14:40 Sent To  
Notes
***NONE***