Plan Review Details - Permit 16070062
Plan Review Stops For Permit 16070062
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-07-08 Cont ID  
Sent By cthroop Date 2016-07-08 Time 08:46 Rev Time 0.00
Received By cthroop Date 2016-07-08 Time 08:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-10 Cont ID  
Sent By mvaldes Date 2016-08-10 Time 09:02 Rev Time 0.00
Received By mvaldes Date 2016-08-10 Time 08:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-07 Cont ID  
Sent By mvaldes Date 2016-07-07 Time 14:58 Rev Time 0.00
Received By mvaldes Date 2016-07-07 Time 14:04 Sent To B
Notes
2016-07-07 15:03:05REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - CLARIFY HOW A 60 AMP SUB PANEL IS BEING FED FROM THE
 EXISTING SERVICE WITH # 10 AWG IS GONA BE SUFFICIENT
 FOR A 3000 VA POOL PUMP AND A 10000 VA POOL HEATER ?
 REFLECT EXISTING SERVICE RISER DIAGRAM TO VERIFY LOAD
 DISTRUBUTION NEC 215.5
  
 - CORRECT LOAD CALCULATION IN ACCORDANCE WITH NEC
 220.82/83 OPTIONAL METHOD IF THAT IS THE INTENT AND
 TAKE A LOOK AT THE AC DEMANDS.
  
 - PROVIDE A # 8 AWG EQUIPMENT GROUNDING CONDUCTOR
 INSIDE THE RACEWAY FOR THE LIGHT NICHE BONDING.
 ENCAPSULATE THE FORMING SHELL LUG TERMINAL WITH A
 LISTED COMPOUND FOR DETERIORATION OF CONNECTION. NEC
 680.23(B)(1)(2)
  
 - SHOW BONDING DETAIL FOR SHED IF REQUIRED PER NEC
 680.26(7) FIXED METAL PARTS WITHIN 5'

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-07-07 Cont ID  
Sent By tklarge Date 2016-07-07 Time 06:30 Rev Time 0.00
Received By tklarge Date 2016-07-07 Time 06:30 Sent To  
Notes
2016-07-07 06:31:36THERE IS NO GAS ON THIS POOL. A HEAT PUMP IS BEING
 INSTALLED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-10 Cont ID  
Sent By mvaldes Date 2016-08-10 Time 09:03 Rev Time 0.00
Received By mvaldes Date 2016-07-29 Time 09:52 Sent To  
Notes
2016-08-01 09:53:15RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-08 Cont ID  
Sent By cthroop Date 2016-07-08 Time 08:46 Rev Time 0.00
Received By cthroop Date 2016-07-08 Time 08:46 Sent To  
Notes
2016-07-05 11:21:55ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-07-07 Cont ID  
Sent By tklarge Date 2016-07-07 Time 06:30 Rev Time 0.00
Received By tklarge Date 2016-07-07 Time 06:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-08-02 Cont ID  
Sent By njwira Date 2016-08-02 Time 14:42 Rev Time 0.00
Received By njwira Date 2016-08-01 Time 15:07 Sent To E
Notes
2016-08-02 14:44:048/2/16-PASSED
  
 LANDSCAPE PERMIT REQUIRED PRIOR TO FINAL APPROVAL.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-07-06 Cont ID  
Sent By njwira Date 2016-07-06 Time 11:24 Rev Time 0.00
Received By njwira Date 2016-07-06 Time 11:24 Sent To E
Notes
2016-08-02 10:22:15NO TREES BEING REMOVED
2016-07-06 11:26:157/6/16- FAILED
  
 1. TREE ALTERATION PERMIT REQUIRED TO REMOVE A TREE.
 2. SF-14 HISTORIC NOT A PLANNED DEVELOPMENT
 3. POOL HAS A 5FT. SIDE SETBACK MEETING THE 5FT. SIDE
 SETBACK REQUIREMENT.
 4. POOL HAS A 12FT. REAR SETBACK MEETING THE 5FT. REAR
 SETBACK REQUIREMENT.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  