| Plan Review Stops For Permit 16070033 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2016-08-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-08-20 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-08-20 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2016-08-20 09:29:06 | BUILDING PROVISO: | | | IF A BREAK ROOM SUNK IS PROVIDED, THEN COMPLIANCE WITH | | | THE 2014 FBC-ACCESSIBILITY CODE 606. 1-5 IS REQUIRED. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-07-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-07-07 |
Time |
07:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-07-07 |
Time |
07:00 |
Sent To |
|
|
| Notes |
| 2016-07-07 07:23:15 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 16070033 | | | ADD: 1558 PALM BEACH LAKES BLVD SUITE: B-4 | | | CONT: PALM BEACH REMODELING LLC | | | TEL: 561-432-8147 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: THURS. JULY 07/ 2016 | | | ACTION: DENIED | | | | | | 1) THE PLANS APPEAR TO BE DRAWN BY THE CONTRACTOR OF | | | RECORD. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND | | | LICENSE NUMBER TO ALL DRAWINGS UNDER YOUR | | | RESPONSIBILITY. | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | | | | 2) THE PLANS DO NOT INDICATE TO WHICH CODES THE PLANS | | | WERE DEVELOPED, | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | 107.3.5.1.1 COMMERCIAL BUILDINGS:(BUILDING) | | | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS | | | SHALL BE DETERMINED. | | | OCCUPANCY GROUP | | | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE | | | TABLE 503). | | | FIRE SPRINKLERS YES OR NO | | | LIFE SAFETY PLAN | | | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: | | | OCCUPANCY LOAD | | | GROSS | | | NET | | | MEANS OF EGRESS | | | EXIT | | | EXIT DISCHARGE | | | DOORS | | | EMERGENCY LIGHTING AND EXIT SIGNS | | | | | | 2) SHEET A-200 SHOWS A DOOR BETWEEN THE RECEPTION AREA | | | AND COORIDOR. THIS DOOR AS IT CURRENTLY IS DETICTED AS | | | SWINGING INTO THE CORRIDOR, DOES NOT HAVE MANEUVERING | | | CLEARANCES. SEE THE 2014 FBC-ACCESSIBILITY CODE 404.2.4 | | | MANEUVERING CLEARANCES. MINIMUM MANEUVERING CLEARANCES | | | AT DOORS AND GATES SHALL COMPLY WITH 404.2.4. | | | MANEUVERING CLEARANCES SHALL EXTEND THE FULL WIDTH OF | | | THE DOORWAY AND THE REQUIRED LATCH SIDE OR HINGE SIDE | | | CLEARANCE. SEE FIGURE | | | 404.2.4.1(A). | | | | | | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2016-09-06 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-09-06 |
Time |
19:33 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-09-06 |
Time |
18:05 |
Sent To |
I |
|
| Notes |
| 2016-09-06 19:34:30 | ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN | | | SATISFACTORILY ADDRESSED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2016-08-29 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-08-29 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-08-29 |
Time |
13:44 |
Sent To |
I |
|
| Notes |
| 2016-08-29 14:12:51 | 2ND ELECTRICAL REVIEW NOTES | | | REVIEWED FOR COMPLIANCE WITH: | | | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) | | | | | | PROJECT NAME: TENANT BUILD OUT | | | JOB ADDRESS: 1558 PALM BEACH LAKES BLVD. | | | DESCRIPTION: TENANT BUILD OUT FOR RETAIL IN EXISTING | | | SHELL. | | | MASTER PERMIT: 16070033 | | | | | | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. | | | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF | | | SUBMITTED CORRECTIONS. | | | | | | 1. FBC-E C405.2.2. PROVIDE AUTOMATIC LIGHTING SHUTOFF | | | FOR THE WATER CLOSET. | | | 2. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL: DAYLIGHT | | | ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN THE | | | DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF GENERAL | | | AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH | | | EITHER SECTION C405.2.2.3.1 OR SECTION C405.2.2.3.2. | | | THIS APPLIES TO THE RECEPTION AREA. | | | 3. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15- | | | AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY | | | CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN | | | OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE | | | INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD | | | 90.1) | | | 4. THE ELECTRICAL SCOPE REQUIRED FOR THE JOB EXCEEDS | | | THAT WHICH IS DEFINED ON THE PERMIT. REVISE THE PERMIT | | | DESCRIPTION ACCORDINGLY. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-07-12 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-07-12 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-07-12 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2016-07-12 10:22:17 | 1ST ELECTRICAL REVIEW NOTES | | | REVIEWED FOR COMPLIANCE WITH: | | | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) | | | | | | 1. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL | | | BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO | | | PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP | | | DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH | | | ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE | | | LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE | | | CONSIDERED ACCESSIBLE TO PEDESTRIANS. THIS OUTLET IS | | | MISSING AT THE FRONT DOOR. | | | 2. FBC-EC405.2.1.2 REQUIRES LIGHTING REDUCTION | | | 3. FBC-EC405.2.2 REQUIRES THAT YOU HAVE AUTOMATIC | | | LIGHTING CONTROL. | | | 4. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL MEANS THAT | | | DAYLIGHT ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN | | | THE DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF | | | GENERAL AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE | | | WITH EITHER SECTION C405.2.2.3.1 OR SECTION | | | C405.2.2.3.2. | | | 5. NEC 215.5 DIAGRAMS OF FEEDERS. A RISER DIAGRAM | | | SHOWING FEEDER DETAILS ALONG WITH RESPECTIVE LOAD CALCS | | | SHALL BE PROVIDED. THIS DIAGRAM SHALL INCLUDE CONDUCTOR | | | SIZING AND INSULATION TYPE. FURTHERMORE, IT SHALL BE | | | SITE SPECIFIC. | | | 6. NEC 408.4(A) REQUIRES THAT YOU PROVIDE A PANEL | | | SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY INDICATING THE | | | SPECIFIC PURPOSE OF EVERY CIRCUIT. | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-08-22 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2016-08-22 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2016-08-22 |
Time |
13:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-07-07 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2016-07-07 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2016-07-07 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2016-07-07 08:48:12 | PERMIT # 16070033 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SEE BUILDING DEPT. COMMENTS | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-09-06 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-09-06 |
Time |
19:35 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-09-01 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2016-09-06 19:36:47 | 9/6/16 PASSED ALL TRADE REVIEWS. CONTRACTOR NOTIFIED | | | VIA EMAIL. FILE SENT TO SMALL READY BIN P. MA | | 2016-09-02 10:47:24 | RESUB ROUTED TO MALBARRAN |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-08-29 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-08-29 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-08-16 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2016-08-29 14:18:02 | 8/29/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR | | | NOTIFIED VIA EMAIL. FILE SENT TO SMALL DENIED BIN "P". | | | MA | | 2016-08-16 15:21:59 | B26 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-07-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-07-23 |
Time |
04:14 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-07-01 |
Time |
08:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2016-08-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-08-23 |
Time |
07:11 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-08-22 |
Time |
17:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-07-12 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-07-12 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-07-11 |
Time |
12:31 |
Sent To |
|
|
| Notes |
| 2016-07-11 12:34:25 | 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING | | | PERMIT #16070033 | | | 7/11/16 | | | | | | 1) SHEET A-301: PLEASE IDENTIFY ALL ROOMS AND SPACES ON | | | THE PLANS. | | | | | | 2) A-301: REFER TO SECTION 809.2 FBC-14 EXISTING | | | BUILDING CODE AND PROVIDE MINIMUM VENTILATION | | | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3 | | | FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES | | | THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 3) A-301: PROVIDE AN EQUIPMENT SCHEDULE FOR THE | | | EXISTING AC SYSTEM THAT INCLUDES THE COOLING, HEATING, | | | AND CFM CAPACITIES. | | | | | | 4) A-301: PROVIDE A RETURN AIR PLAN PER SECTION 601.5, | | | AND NOTE THAT THE CORRIDOR SHALL NOT BE USED TO CONVEY | | | RETURN AIR PER SECTION 601.2: PROVIDE A DUCTED RETURN | | | SYSTEM. | | | | | | 5) A-200: IDENTIFY THE NAME OF THE PROPOSED BUSINESS | | | AND OCCUPANCY CLASSIFICATION PER THE FBC-14. THE PLAN | | | INDICATES AN "OPERATION ROOM". PLEASE CLARIFY WHAT TYPE | | | OF "OPERATIONS"ARE TO BE PERFORMED THERE. PLEASE NOTE | | | THAT ADDITIONAL COMMENTS MAY FOLLOW AFTER CORRECTED | | | PLANS ARE RESUBMITTED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2016-08-22 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-08-22 |
Time |
04:49 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-08-22 |
Time |
04:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2016-07-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-07-23 |
Time |
04:13 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-07-23 |
Time |
04:08 |
Sent To |
|
|
| Notes |
| 2016-07-23 04:14:11 | NO NEW PLUMBING SHOWN. TKL. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2016-07-07 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2016-07-07 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2016-07-07 |
Time |
12:15 |
Sent To |
|
|
| Notes |
|
|