Plan Review Details - Permit 16070033
Plan Review Stops For Permit 16070033
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-08-20 Cont ID  
Sent By jwitmer Date 2016-08-20 Time 09:29 Rev Time 0.00
Received By jwitmer Date 2016-08-20 Time 09:00 Sent To  
Notes
2016-08-20 09:29:06BUILDING PROVISO:
 IF A BREAK ROOM SUNK IS PROVIDED, THEN COMPLIANCE WITH
 THE 2014 FBC-ACCESSIBILITY CODE 606. 1-5 IS REQUIRED.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-07 Cont ID  
Sent By jwitmer Date 2016-07-07 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2016-07-07 Time 07:00 Sent To  
Notes
2016-07-07 07:23:15BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070033
 ADD: 1558 PALM BEACH LAKES BLVD SUITE: B-4
 CONT: PALM BEACH REMODELING LLC
 TEL: 561-432-8147
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 07/ 2016
 ACTION: DENIED
  
 1) THE PLANS APPEAR TO BE DRAWN BY THE CONTRACTOR OF
 RECORD. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER TO ALL DRAWINGS UNDER YOUR
 RESPONSIBILITY.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 2) THE PLANS DO NOT INDICATE TO WHICH CODES THE PLANS
 WERE DEVELOPED,
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS:(BUILDING)
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 OCCUPANCY GROUP
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
 FIRE SPRINKLERS YES OR NO
 LIFE SAFETY PLAN
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 2) SHEET A-200 SHOWS A DOOR BETWEEN THE RECEPTION AREA
 AND COORIDOR. THIS DOOR AS IT CURRENTLY IS DETICTED AS
 SWINGING INTO THE CORRIDOR, DOES NOT HAVE MANEUVERING
 CLEARANCES. SEE THE 2014 FBC-ACCESSIBILITY CODE 404.2.4
 MANEUVERING CLEARANCES. MINIMUM MANEUVERING CLEARANCES
 AT DOORS AND GATES SHALL COMPLY WITH 404.2.4.
 MANEUVERING CLEARANCES SHALL EXTEND THE FULL WIDTH OF
 THE DOORWAY AND THE REQUIRED LATCH SIDE OR HINGE SIDE
 CLEARANCE. SEE FIGURE
 404.2.4.1(A).
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-09-06 Cont ID  
Sent By albarran Date 2016-09-06 Time 19:33 Rev Time 0.00
Received By albarran Date 2016-09-06 Time 18:05 Sent To I
Notes
2016-09-06 19:34:30ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-08-29 Cont ID  
Sent By albarran Date 2016-08-29 Time 14:10 Rev Time 0.00
Received By albarran Date 2016-08-29 Time 13:44 Sent To I
Notes
2016-08-29 14:12:512ND ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: TENANT BUILD OUT
 JOB ADDRESS: 1558 PALM BEACH LAKES BLVD.
 DESCRIPTION: TENANT BUILD OUT FOR RETAIL IN EXISTING
 SHELL.
 MASTER PERMIT: 16070033
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. FBC-E C405.2.2. PROVIDE AUTOMATIC LIGHTING SHUTOFF
 FOR THE WATER CLOSET.
 2. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL: DAYLIGHT
 ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN THE
 DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF GENERAL
 AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH
 EITHER SECTION C405.2.2.3.1 OR SECTION C405.2.2.3.2.
 THIS APPLIES TO THE RECEPTION AREA.
 3. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD
 90.1)
 4. THE ELECTRICAL SCOPE REQUIRED FOR THE JOB EXCEEDS
 THAT WHICH IS DEFINED ON THE PERMIT. REVISE THE PERMIT
 DESCRIPTION ACCORDINGLY.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-12 Cont ID  
Sent By albarran Date 2016-07-12 Time 10:21 Rev Time 0.00
Received By albarran Date 2016-07-12 Time 09:47 Sent To  
Notes
2016-07-12 10:22:171ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS. THIS OUTLET IS
 MISSING AT THE FRONT DOOR.
 2. FBC-EC405.2.1.2 REQUIRES LIGHTING REDUCTION
 3. FBC-EC405.2.2 REQUIRES THAT YOU HAVE AUTOMATIC
 LIGHTING CONTROL.
 4. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL MEANS THAT
 DAYLIGHT ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN
 THE DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF
 GENERAL AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE
 WITH EITHER SECTION C405.2.2.3.1 OR SECTION
 C405.2.2.3.2.
 5. NEC 215.5 DIAGRAMS OF FEEDERS. A RISER DIAGRAM
 SHOWING FEEDER DETAILS ALONG WITH RESPECTIVE LOAD CALCS
 SHALL BE PROVIDED. THIS DIAGRAM SHALL INCLUDE CONDUCTOR
 SIZING AND INSULATION TYPE. FURTHERMORE, IT SHALL BE
 SITE SPECIFIC.
 6. NEC 408.4(A) REQUIRES THAT YOU PROVIDE A PANEL
 SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY INDICATING THE
 SPECIFIC PURPOSE OF EVERY CIRCUIT.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-22 Cont ID  
Sent By scaldero Date 2016-08-22 Time 13:35 Rev Time 0.00
Received By scaldero Date 2016-08-22 Time 13:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-07 Cont ID  
Sent By scaldero Date 2016-07-07 Time 08:48 Rev Time 0.00
Received By scaldero Date 2016-07-07 Time 08:47 Sent To  
Notes
2016-07-07 08:48:12PERMIT # 16070033
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SEE BUILDING DEPT. COMMENTS
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-09-06 Cont ID  
Sent By albarran Date 2016-09-06 Time 19:35 Rev Time 0.00
Received By albarran Date 2016-09-01 Time 10:47 Sent To  
Notes
2016-09-06 19:36:479/6/16 PASSED ALL TRADE REVIEWS. CONTRACTOR NOTIFIED
 VIA EMAIL. FILE SENT TO SMALL READY BIN P. MA
2016-09-02 10:47:24RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-29 Cont ID  
Sent By albarran Date 2016-08-29 Time 14:14 Rev Time 0.00
Received By albarran Date 2016-08-16 Time 15:21 Sent To  
Notes
2016-08-29 14:18:028/29/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. FILE SENT TO SMALL DENIED BIN "P".
 MA
2016-08-16 15:21:59B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-23 Cont ID  
Sent By tklarge Date 2016-07-23 Time 04:14 Rev Time 0.00
Received By tklarge Date 2016-07-01 Time 08:47 Sent To  
Notes
2016-07-05 08:47:41B15

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-08-23 Cont ID  
Sent By ccole Date 2016-08-23 Time 07:11 Rev Time 0.00
Received By ccole Date 2016-08-22 Time 17:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-12 Cont ID  
Sent By ccole Date 2016-07-12 Time 11:00 Rev Time 0.00
Received By ccole Date 2016-07-11 Time 12:31 Sent To  
Notes
2016-07-11 12:34:251ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16070033
 7/11/16
  
 1) SHEET A-301: PLEASE IDENTIFY ALL ROOMS AND SPACES ON
 THE PLANS.
  
 2) A-301: REFER TO SECTION 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 3) A-301: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 EXISTING AC SYSTEM THAT INCLUDES THE COOLING, HEATING,
 AND CFM CAPACITIES.
  
 4) A-301: PROVIDE A RETURN AIR PLAN PER SECTION 601.5,
 AND NOTE THAT THE CORRIDOR SHALL NOT BE USED TO CONVEY
 RETURN AIR PER SECTION 601.2: PROVIDE A DUCTED RETURN
 SYSTEM.
  
 5) A-200: IDENTIFY THE NAME OF THE PROPOSED BUSINESS
 AND OCCUPANCY CLASSIFICATION PER THE FBC-14. THE PLAN
 INDICATES AN "OPERATION ROOM". PLEASE CLARIFY WHAT TYPE
 OF "OPERATIONS"ARE TO BE PERFORMED THERE. PLEASE NOTE
 THAT ADDITIONAL COMMENTS MAY FOLLOW AFTER CORRECTED
 PLANS ARE RESUBMITTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2016-08-22 Cont ID  
Sent By tklarge Date 2016-08-22 Time 04:49 Rev Time 0.00
Received By tklarge Date 2016-08-22 Time 04:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2016-07-23 Cont ID  
Sent By tklarge Date 2016-07-23 Time 04:13 Rev Time 0.00
Received By tklarge Date 2016-07-23 Time 04:08 Sent To  
Notes
2016-07-23 04:14:11NO NEW PLUMBING SHOWN. TKL.

Review Stop Z ZONING
Rev No 1 Status P Date 2016-07-07 Cont ID  
Sent By ajones Date 2016-07-07 Time 12:15 Rev Time 0.00
Received By ajones Date 2016-07-07 Time 12:15 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved