Plan Review Details - Permit 16070025
Plan Review Stops For Permit 16070025
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-09-12 Cont ID  
Sent By jwitmer Date 2016-09-12 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2016-09-10 Time 10:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-11 Cont ID  
Sent By jwitmer Date 2016-08-11 Time 07:54 Rev Time 0.00
Received By jwitmer Date 2016-08-11 Time 07:01 Sent To  
Notes
2016-08-11 07:54:23BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070025
 ADD: 2450 METRO CENTRE BLVD.
 CONT: MEDICAL CONSULTANTS PLUS
 TEL: 954-444-3325
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUGUST 11/ 2016
 ACTION: DENIED
  
 1) SHEET A-1 & LIFE SAFETY WILL REQUIRE RATED
 CORRIDORS. THE CORRIDOR IS A LOOPED SYSTEM. TAKING THE
 DIAGONAL OPPOSITE WHAT IS LAID OUT IN THE LIFE SAFETY
 SHEET WILL MAKE THE LONGEST TRAVEL DISTANCE TO AN EXIT,
 IN EACH CASE THE OCCUPANT LOAD WOULD BE OVER 30
 OCCUPANTS SEE FBC-B TABLE 1018.1, BUSINESS OCCUPANCY
 WHEN THE CORRIDOR SERVES AN OCCUPANT LOAD GREATER THAN
 30 IN A NON-SPRINKLERED BUILDING.
  
 1A) FBC-B 1018.6 CORRIDOR CONTINUITY.
 FIRE-RESISTANCE-RATED CORRIDORS SHALL BE CONTINUOUS
 FROM THE POINT OF ENTRY TO AN EXIT, AND SHALL NOT BE
 INTERRUPTED BY INTERVENING ROOMS. WHERE THE PATH OF
 EGRESS TRAVEL WITHIN A FIRE-RESISTANCE-RATED CORRIDOR
 TO THE EXIT INCLUDES TRAVEL ALONG UNENCLOSED EXIT
 ACCESS STAIRWAYS OR RAMPS, THE FIRE RESISTANCE-RATING
 SHALL BE CONTINUOUS FOR THE LENGTH OF THE STAIRWAY OR
 RAMP AND FOR THE LENGTH OF THE CONNECTING CORRIDOR ON
 THE ADJACENT FLOOR LEADING TO THE EXIT.
  
 1B) FBC-B 1018.1 CONSTRUCTION. CORRIDORS SHALL BE
 FIRE-RESISTANCE RATED IN ACCORDANCE WITH TABLE 1018.1.
 THE CORRIDOR WALLS REQUIRED TO BE FIRE-RESISTANCE RATED
 SHALL COMPLY WITH SECTION 708 FOR FIRE PARTITIONS.
 708.3 FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL
 HAVE A FIRE RESISTANCE RATING OF NOT LESS THAN 1 HOUR.
  
 1C) FBC-B 708.4 CONTINUITY. FIRE PARTITIONS SHALL
 EXTEND FROM THE TOP OF THE FOUNDATION OR FLOOR/CEILING
 ASSEMBLY BELOW TO THE UNDERSIDE OF THE FLOOR OR ROOF
 SHEATHING, SLAB OR DECK ABOVE OR TO THE
 FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING
 ASSEMBLY ABOVE, AND SHALL BE SECURELY ATTACHED THERETO.
  
 1D) FBC-B 717.5.4 FIRE PARTITIONS. DUCTS AND AIR
 TRANSFER OPENINGS THAT PENETRATE FIRE PARTITIONS SHALL
 BE PROTECTED WITH LISTED FIRE DAMPERS INSTALLED IN
 ACCORDANCE WITH THEIR LISTING.
  
 1E) FBC-B 717.4 ACCESS AND IDENTIFICATION.
 FIRE AND SMOKE DAMPERS SHALL BE PROVIDED WITH AN
 APPROVED MEANS OF ACCESS, WHICH IS LARGE ENOUGH TO
 PERMIT INSPECTION AND MAINTENANCE OF THE DAMPER AND ITS
 OPERATING PARTS. THE ACCESS SHALL NOT AFFECT THE
 INTEGRITY OF FIRE-RESISTANCE-RATED ASSEMBLIES. THE
 ACCESS OPENINGS SHALL NOT REDUCE THE FIRE-RESISTANCE
 RATING OF THE ASSEMBLY. ACCESS POINTS SHALL BE
 PERMANENTLY IDENTIFIED ON THE EXTERIOR BY A LABEL
 HAVING LETTERS NOT LESS THAN 1/2 INCH (12.7 MM) IN
 HEIGHT READING: FIRE/SMOKE DAMPER, SMOKE DAMPER OR FIRE
 DAMPER. ACCESS DOORS IN DUCTS SHALL BE TIGHT FITTING
 AND SUITABLE FOR THE REQUIRED DUCT CONSTRUCTION.
  
 1F) FBC-B 703.7 MARKING AND IDENTIFICATION.
 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS OR PENETRATIONS
 SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING. SUCH IDENTIFICATION SHALL:
 1F) 1. BE LOCATED IN ACCESSIBLE CONCEALED FLOOR,
 FLOOR-CEILING OR ATTIC SPACES;
 1F) 2. BE LOCATED WITHIN 15 FEET (4572 MM ) OF THE END
 OF EACH WALL AND AT INTERVALS NOT EXCEEDING 30 FEET
 MEASURED HORIZONTALLY ALONG THE WALL OR PARTITION; AND
 1F) 3. INCLUDE LETTERING NOT LESS THAN 3 INCHES (76 MM
 ) IN HEIGHT WITH A MINIMUM 3/8 INCH (9.5 MM) STROKE IN
 A CONTRASTING COLOR INCORPORATING THE SUGGESTED
 WORDING. ?FIRE AND/OR SMOKE BARRIER?PROTECT ALL
 OPENINGS? OR OTHER WORDING.
  
 2 COMPLIED.
  
 3) 2ND REQUEST, PLANS STILL SHOW A MICROWAVE OUT OF THE
 REACH RANGES AND OPERATING PARTS RANGE!!!!!SHEET A.5
 DETAIL 1 SHOWS A MICROWAVE ON THE BOTTOM SHELF OF THE
 UPPER CABINETS. PLEASE REVIEW 2014 FBC-ACCESS. CODE
 REACH RANGES IN 308 AND OPERABLE PARTS UNDER 309.3
 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR
 MORE OF THE REACH RANGES SPECIFIED IN 308.
  
 4)2ND REQUEST, CONTRACTOR HAS NOT SUBMITTED SHEET M2
 INDICATES THE USE OF NEW ROOF TOP A/C STANDS. PLEASE
 PROVIDE COMPLIANCE WITH 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS / WALL LOUVERS FOR
 OUTSIDE AIR.
  
 5-8) COMPLIED.
  
 9A) NEW COMMENT OUTSIDE AIR LOUVER A SALES BROCHURE WAS
 SUBMITTED NOT A MIAMI DADE NOA. 2014 FBC-B 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(C) PANEL WALLS:, WALL LOUVERS,
 9B) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 AMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-19 Cont ID  
Sent By jwitmer Date 2016-07-19 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2016-07-19 Time 14:11 Sent To  
Notes
2016-07-19 14:59:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070025
 ADD: 2450 METRO CENTRE BLVD.
 CONT: MEDICAL CONSULTANTS PLUS
 TEL: 954-444-3325
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 19/ 2016
 ACTION: DENIED
  
 1) SHEET A-1 & LIFE SAFETY SHEET, PLEASE SHOW HOW MANY
 OCCUPANTS WILL BE IN THE SUB-WAITING AREA # 112?
 DEPENDING ON THE OCCUPANT LOAD IN THE CORRIDORS LEADING
 AWAY SOME OF THE CORRIDORS MAY REQUIRE A 1 HOUR FIRE
 RATING. SEE FBC-B TABLE 1018.1, BUSINESS OCCUPANCY WHEN
 THE CORRIDOR SERVES AN OCCUPANT LOAD GREATER THAN 30 IN
 A NON-SPRINKLERED BUILDING.
  
 2) SHEET A.3 THE TOLIET GRAB BARS ARE SHOWN BEING
 MEASURED FROM THE CENTERLINE TO THE FINISH FLOOR. UNDER
 THE 2014 FBC-ACCESSIBILTY CODE SECTION 609.4 THEY ARE
 TO BE MEASURED FROM THE TOP OF THE GRIPPING SURFACE TO
 THE FINISH FLOOR.
  
 3) SHEET A.5 DETAIL 1 SHOWS A MICROWAVE ON THE BOTTOM
 SHELF OF THE UPPER CABINETS. PLEASE REVIEW 2014
 FBC-ACCESS. CODE REACH RANGES IN 308 AND OPERABLE PARTS
 UNDER 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED
 WITHIN ONE OR MORE OF THE REACH RANGES SPECIFIED IN
 308.
  
 4) SHEET M2 INDICATES THE USE OF NEW ROOF TOP A/C
 STANDS. PLEASE PROVIDE COMPLIANCE WITH 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS / WALL LOUVERS FOR
 OUTSIDE AIR.
  
 5) ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN PROFESSIONAL
 IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE FOR
 REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS PREPARED
 BY OTHERS, INCLUDING PHASED AND DEFERRED SUBMITTAL
 ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF THE
 BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
  
 6) DEPENDING ON THE PLACEMENT OF THE A/C STAND
 ADDITIONAL ROOF FRAMING RE-INFORCEMENT MAY BE NEEDED TO
 ANCHOR INTO THE MAIN WIND FORCE RESISTING SYSTEM
 (MWFRS). 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON
 STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE
 DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE
 INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC
 COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL
 PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST
 THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. 22014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
  
 7) PLEASE PROVIDE THE WIND DESIGN CRITERIA INCLUDING
 THE MEAN ROOF HEIGHT, EXPOSURE AND PRESSURES FOR THE
 NEW ROOFTOP A/C STAND AND ROOF TOP CONDENSING UNITS.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 8) PLEASE ALSO PROVIDE THE ANCHORING OF THE ROOF TOP
 UNITS TO THE NEW ROOF TOP STAND. 2014 FBC-M- 301.15
 WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-25 Cont ID  
Sent By albarran Date 2016-08-25 Time 17:17 Rev Time 0.00
Received By albarran Date 2016-08-25 Time 16:46 Sent To I
Notes
2016-08-25 17:18:17ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-11 Cont ID  
Sent By albarran Date 2016-07-11 Time 15:32 Rev Time 0.00
Received By albarran Date 2016-07-11 Time 13:56 Sent To  
Notes
2016-07-11 15:32:391ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. PAGE. E1: PER FBC-EC405.7 A MINIMUM OF 50% OF ALL
 125V, 15 & 20 AMP RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OR PEN OFFICES
 AND COMPUTER CLASSROOMS. THIS INCLUDES MODULAR
 PARTITIONS TOO. SHOW COMPLIANCE ACCORDINGLY.
 2. PER NEC 408.4(A), A CIRCUIT DIRECTORY FOR EVERY
 PANEL IS REQUIRED.
 3. PER NEC 408.4(B), ALL PANELS SHALL BE MARKED WITH
 THE LOCATION OF THE SOURCE OF POWER. WHILE OBN THIS
 TOPIC, THERE ARE MORE PANEL INDICATED ON THE FLOOR
 PLANS THAT APPEAR ON THE RISER DIAGRAM ON PAGE E3.
 4. PAGE E2: PER FBC-EC405.2.2.3 ADDITIONAL LIGHTING
 CONTROL IS REQUIRED FOR DAYLIGHT ZONES. RECONFIGURE
 YOUR LIGHTING PLAN ACCORDINGLY.
 5. PAGE E3: NEC 215.5 REQUIRES THAT YOU PROVIDE LOAD
 CALCS. INCLUDE ALL APPLICABLE PANELS.
 6. NEC 230.2 RESTRICTS YOUR SERVICES TO ONE UNLESS
 SPECIFIC CONDITIONS ARE MET. EXPLAIN WHAT YOU MEAN BY
 SERVICE 4 OF 4 AND THEN STILL ANOTHER SERVICE AS
 EXISTING..
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-09-07 Cont ID  
Sent By pleduc Date 2016-09-07 Time   Rev Time 0.00
Received By pleduc Date 2016-09-07 Time 13:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-08 Cont ID  
Sent By pleduc Date 2016-08-08 Time   Rev Time 0.00
Received By pleduc Date 2016-08-08 Time 16:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-07 Cont ID  
Sent By pleduc Date 2016-07-07 Time   Rev Time 0.00
Received By pleduc Date 2016-07-07 Time 14:22 Sent To  
Notes
2016-07-07 15:20:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A.1 - DOOR 114 IS INDICATED WITHIN A FIRE
 RATED WALL; HOWEVER, SHEET A..3, DOOR AND FRAME
 SCHEDULE INDICATES DOOR 114 AND HARDWARE AS HAVING NO
 RATING.
  
 PLEASE CORRECT OR CLARIFY.
  
 2) SHEET A.1 - KEYNOTE # 10 INDICATES A WINDOW WITHIN A
 FIRE RATED WALL; HOWEVER, THERE IS FIRE RATING
 INDICATED FOR THE WINDOW.
  
 PLEASE CORRECT OR JUSTIFY.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-09-12 Cont ID  
Sent By jwitmer Date 2016-09-12 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2016-09-02 Time 15:38 Sent To  
Notes
2016-09-02 15:38:32C18

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2016-08-25 Cont ID  
Sent By albarran Date 2016-08-25 Time 17:36 Rev Time 0.00
Received By albarran Date 2016-08-03 Time 09:27 Sent To  
Notes
2016-08-25 17:37:448/25/16 FAILED BLDG & MECH REVIEWS. CONTRACTOR NOTIFIED
 VIA EMAIL. FILE SENT TO LARGE DENIED DRAWER "M". MA
2016-08-04 09:28:35C18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-23 Cont ID  
Sent By tklarge Date 2016-07-23 Time 11:23 Rev Time 0.00
Received By tklarge Date 2016-07-01 Time 08:59 Sent To  
Notes
2016-07-05 08:59:46C08

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-09-08 Cont ID  
Sent By ccole Date 2016-09-08 Time 12:42 Rev Time 0.00
Received By ccole Date 2016-09-08 Time 12:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-08-08 Cont ID  
Sent By ccole Date 2016-08-08 Time 10:37 Rev Time 0.00
Received By ccole Date 2016-08-08 Time 10:37 Sent To  
Notes
2016-08-08 10:40:532ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16070025
 8/8/16
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS. I AM
 REPRINTING IT BELOW. PLEASE NOTE THAT THE ARCHITECT HAS
 SIGNED THE ENERGY CALCULATIONS BUT NOT THE AC
 CALCULATIONS.
 1) IN REGARD TO THE SUBMITTED AC CALCULATIONS PREPARED
 FOR THE PROJECT BY TOM PLATANIA- PRO CALCS LLC., PLEASE
 REFER TO SECTION 105.3.1.2(3) FBC-14 BUILDING:
 AN AIR-CONDITIONING SYSTEM MAY BE DESIGNED BY AN
 INSTALLING AIR-CONDITIONING CONTRACTOR CERTIFIED UNDER
 CHAPTER 489, FLORIDA STATUTES, TO SERVE ANY BUILDING OR
 ADDITION WHICH IS DESIGNED TO ACCOMMODATE FEWER THAN
 100 PERSONS AND REQUIRES AN AIR-CONDITIONING SYSTEM
 WITH A VALUE OF $125,000 OR LESS; AND WHEN A 15-TON-PER
 SYSTEM OR LESS IS DESIGNED FOR A SINGULAR SPACE OF A
 BUILDING AND EACH 15-TON SYSTEM OR LESS HAS AN
 INDEPENDENT DUCT SYSTEM. SYSTEMS NOT COMPLYING WITH THE
 ABOVE REQUIRE DESIGN DOCUMENTS THAT ARE TO BE SEALED BY
 A PROFESSIONAL ENGINEER.
 PLEASE CLARIFY IF MR. PLATANIA IS EITHER THE ENGINEER
 OF RECORD OR THE INSTALLING AC CONTRACTOR.
  
 2) THE AC LOAD CALCULATIONS AND THE EQUIPMENT SCHEDULE
 ON M.1 IDENTIFY THE NEW SYSTEMS AS AC-6 & AC-7, HOWEVER
 THEY ARE INCORRECTLY IDENTIFIED AS AHU-1 & AHU-2 IN THE
 ENERGY CALCULATIONS.
  
 3) M.1: PLEASE SHOW THE DUCT LAYOUTS FOR AHU-3 AND
 AHU-4. INDICATE DUCT SIZES AND WHICH DUCTS ARE NEW,
 EXISTING, OR RELOCATED.
  
 4) M.1: SHOW THE DISCHARGE LOCATION FOR THE CONDENSATE
 PIPE SERVING AHU-7.
  
 5) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW (COMMENT
 #12), PROVIDE A PRODUCT APPROVAL OR NOA FOR THE
 LOUVERS. WHAT HAS BEEN SUBMITTED IS A MANUFACTURER'S
 DATA SHEET.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-11 Cont ID  
Sent By ccole Date 2016-07-11 Time 07:28 Rev Time 0.00
Received By ccole Date 2016-07-11 Time 07:28 Sent To  
Notes
2016-07-11 09:12:091ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16070025
 7/11/16
  
 1) IN REGARD TO THE SUBMITTED AC CALCULATIONS PREPARED
 FOR THE PROJECT BY TOM PLATANIA- PRO CALCS LLC., PLEASE
 REFER TO SECTION 105.3.1.2(3) FBC-14 BUILDING:
 AN AIR-CONDITIONING SYSTEM MAY BE DESIGNED BY AN
 INSTALLING AIR-CONDITIONING CONTRACTOR CERTIFIED UNDER
 CHAPTER 489, FLORIDA STATUTES, TO SERVE ANY BUILDING OR
 ADDITION WHICH IS DESIGNED TO ACCOMMODATE FEWER THAN
 100 PERSONS AND REQUIRES AN AIR-CONDITIONING SYSTEM
 WITH A VALUE OF $125,000 OR LESS; AND WHEN A 15-TON-PER
 SYSTEM OR LESS IS DESIGNED FOR A SINGULAR SPACE OF A
 BUILDING AND EACH 15-TON SYSTEM OR LESS HAS AN
 INDEPENDENT DUCT SYSTEM. SYSTEMS NOT COMPLYING WITH THE
 ABOVE REQUIRE DESIGN DOCUMENTS THAT ARE TO BE SEALED BY
 A PROFESSIONAL ENGINEER.
 PLEASE CLARIFY IF MR. PLATANIA IS EITHER THE ENGINEER
 OF RECORD OR THE INSTALLING AC CONTRACTOR.
  
 2) INDICATE WHICH AC SYSTEM SHOWN ON THE PLANS IS BEING
 SIZED IN ACCORDANCE WITH THE AC CALCULATIONS.
  
 3) REFER TO PAGE 3 OF THE SUBMITTED ENERGY GAUGE
 CALCULATION SUBMITTAL: THE OWNER/AGENT AND ARCHITECT
 MUST SIGN THE DOCUMENT.
  
 4) PROVIDE A DUPLICATE COPY OF THE ENERGY GAUGE INPUT
 DATA REPORT- ONLY ONE COPY WAS SUBMITTED.
  
 5) IT APPEARS THAT AC SYSTEMS #7 & # 8 ARE NOT LISTED
 IN THE ENERGY CALCULATIONS, AND THE DESIGNER OR
 ENGINEER HAS NOT FILLED OUT THE CHECKLIST ON PAGE 7.
  
 6) DUCT SMOKE DETECTORS SHALL BE PLACED IN THE RETURN
 AIR SYSTEMS OF AC SYSTEMS #5 & #8- SEE SECTION 606.2.1.
  
 7) SHEETS A.1 & M.1: AC-8 HAS BEEN SIZED PER THE HEAT
 LOAD FROM EQUIPMENT. PLEASE IDENTIFY THE EQUIPMENT
 SHOWN IN EQPT 115, AND IF IT IS COMPUTER EQUIPMENT,
 PLEASE PROVIDE THE SCOP RATING OF THE SYSTEM PER TABLE
 C403.2.3 FBC-14 ENERGY CONSERVATION.
  
 8) A.1 & M.1: PLEASE IDENTIFY ALL ROOMS AND SPACES
 SHOWN ON THE HVAC PLAN.
  
 9) M.1: PROVIDE A CONDENSATE DISPOSAL PLAN- SHOW PIPING
 RUNS AND DISCHARGE LOCATIONS, AND INDICATE THE TYPES
 AND SIZES OF PIPINGS.
  
 10) M.1: THE RESTROOM EF-1'S SHALL EACH HAVE MINIMUM 70
 CFM CAPACITY PER TABLE 403.3.
  
 11) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE
 LOCATIONS OF ALL NEW EQUIPMENT AND CLEARANCE DISTRANCES
 TO ROOF EDGES, AIR INTAKES ETC.
  
 12) PROVIDE MIAMI-DADE NOA'S OR FLORIDA PRODUCT
 APPROVALS FOR THE AC STAND AND O/A INTAKE LOUVERS WITH
 SHOP DRAWING APPROVAL SIGNATURES OF THE DOCUMENTS BY
 THE DESIGN PROFESSIONAL OF RECORD- FLORIDA DEPT. OF
 COMMUNITY AFFAIRS RULE 9N-3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-08-24 Cont ID  
Sent By gjohnson Date 2016-08-24 Time 15:04 Rev Time 0.00
Received By gjohnson Date 2016-08-24 Time 14:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-07-23 Cont ID  
Sent By tklarge Date 2016-07-23 Time 11:23 Rev Time 0.00
Received By tklarge Date 2016-07-23 Time 10:45 Sent To  
Notes
2016-07-23 11:21:571) THE SINK IN THE HALL BY THE DRESSING ROOMS SHALL
 COMPLY WITH FBC-ACCESIBILITY SEC. 212.3.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 RECTORSEAL WATERLESS TRAP.THIS INFORMATION WILL BE
 REVIEWED FOR COMPLIANCE WITH THE PLUMBING CODE.
 3) THE BRANCH VENT FROM SK-1 APPEARS TO BE OVER 40 FEET
 IN DEVELOPED LENGTH. THE VENT SHALL BE INCREASED TO 3
 INCHES FOR THE ENTIRE DEVELOPED LENGTH PER 2014 FBC -
 PLUMBING SEC.906.2.
 4) GRAB BARS SHALL BE MEASUREDD TO THE TOP OF THE
 GRIPPING SURFACE. FAC SEC.609.4.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  