Plan Review Details - Permit 16061686
Plan Review Stops For Permit 16061686
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-08-24 Cont ID  
Sent By jwitmer Date 2016-08-24 Time 14:15 Rev Time 0.00
Received By jwitmer Date   Time 13:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-11 Cont ID  
Sent By jwitmer Date 2016-08-11 Time 15:31 Rev Time 0.00
Received By jwitmer Date   Time 13:31 Sent To  
Notes
2016-08-11 15:31:50BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16061686
 ADD: 415 NORTHWOOD RD.
 CONT: INGECO CONTRACTORS LLC
 TEL: 561-601-2379
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. AUGUST 22/ 2016
 ACTION: BUILDING PROVISO
  
 AREA OF REFUGE DOCUMENTS AND LULA LIFT DOCUMENTS WILL
 BE REQUIRED TO BE REVIEWED AND APPROVED BY PLAN REVIEW
 BEFORE THE FRAMING INSPECTION CAN OCCUR!!!
  
 1) AREA OF REFUGE SHALL COMPLY WITH THESE REQUIREMENTS.
 AREA OF REFUGE. 2003 IBC-B 1007.6 .3 TWO-WAY
 COMMUNICATION. AREAS OF REFUGE SHALL BE PROVIDED WITH
 TWO-WAY COMMUNICATION SYSTEM BETWEEN THE AREA OF REFUGE
 AND A CONTROL POINT. IF THE CENTRAL CONTROL POINT IS
 NOT CONSTANTLY ATTENDED, THE AREA OF REFUGE SHALL ALSO
 HAVE CONTROLLED ACCESS TO A PUBLIC TELEPHONE SYSTEM.
 LOCATION OF THE CENTRAL CONTROL POINT SHALL BE APPROVED
 BY THE FIRE DEPARTMENT. TWO-WAY COMMUNICATION SYSTEM
 SHALL INCLUDE BOTH AUDIBLE AND VISIBLE SIGNALS.
  
 1007.6.4 INSTRUCTIONS. IN AREAS OF REFUGE THAT HAVE A
 TWO-WAY EMERGENCY COMMUNICATIONS SYSTEM, INSTRUCTIONS
 ON THE USE OF THE AREA UNDER EMERGENCY CONDITIONS SHALL
 BE POSTED ADJOINING THE COMMUNICATIONS SYSTEM. THE
 INSTRUCTIONS SHALL INCLUDE ALL OF THE FOLLOWING;
 1) DIRECTIONS TO FIND OTHER MEANS OF EGRESS.
 2) PERSONS ABLE TO USE THE EXIT STAIRWAY DO SO AS SOON
 AS POSSIBLE, UNLESS THEY ARE ASSISTING OTHERS.
 3) INFORMATION ON THE PLANNED AVAILABILITY OF
 ASSISTANCE IN THE USE OF STAIRS OR SUPERVISED OPERATION
 OF ELEVATORS AND HOW TO SUMMON SUCH ASSISTANCE. 4)
 DIRECTIONS FOR THE USE OF THE EMERGENCY COMMUNICATIONS
 SYSTEM.
  
 1007.6.5 IDENTIFICATION. EACH DOOR PROVIDING ACCESS TO
 AN AREA OF REFUGE FROM AN ADJACENT FLOOR AREA SHALL BE
 IDENTIFIED BY A SIGN COMPLYING WITH ICC A117., STATING
 AREA OF REFUGE, AND INCLUDING THE INTERNATIONAL SYMBOL
 OF ACCESSIBILITY. WHERE EXIT SIGN ILLUMINATION IS
 REQUIRED BY SECTION 1011.2, THE AREA OF REFUGE SIGN
 SHALL BE ILLUMINATED. ADDITIONALLY, TACTILE SIGNAGE
 COMPLYING WITH ICC A117.1 SHALL BE LOCATED AT EACH DOOR
 TO AN AREA OF REFUGE.
  
 1007.7. SIGNAGE. AT EXITS AND ELEVATORS SERVING A
 REQUIRED ACCESSIBLE SPACE BUT NOT PROVIDING AN APPROVED
 ACCESSIBLE MEANS OF EGRESS, SIGNAGE SHALL BE INSTALLED
 INDICATING THE LOCATION OF ACCESSIBLE MEANS OF EGRESS.
  
 2) SHOP DRAWINGS WILL BE REQUIRED FOR THE LULA LIFT
 (LIMITED-USE / LIMITED-APPLICATION ELEVATORS) THAT WILL
 SHOW COMPLIANCE WITH 2014 FBC-ACCESS
 408.1L. LIMITED-USE/LIMITED-APPLICATION ELEVATORS SHALL
 COMPLY WITH 408 AND WITH ASME A17.1.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
 CODE 408.1- 408.4.8 & ASME A17.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-08 Cont ID  
Sent By jwitmer Date 2016-07-08 Time 14:06 Rev Time 0.00
Received By jwitmer Date 2016-07-08 Time 07:29 Sent To  
Notes
2016-07-08 14:06:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16061686
 ADD: 415 NORTHWOOD RD.
 CONT: INGECO CONTRACTORS LLC
 TEL: 561-601-2379
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 08/2016
 ACTION: DENIED
  
 1) SHEET A-1 SHOWS (2) INFILL WALLS WITHIN EITHER A
 PARTY WALL OR A ZERO LOT LINE BEARING WALL. THE PLANS
 ARE NOT CLEAR AS TO WHICH TYPE OF EXTERIOR WALL THIS
 IS?
 IF THE WALL IN QUESTION IS A PARTY WALL THEN THE WALL
 MUST MEET THE REQUIREMENTS FOR A FIRE WALL, SEE FBC-B
 706.1.1 PARTY WALLS. ANY WALL LOCATED ON A LOT LINE
 BETWEEN ADJACENT BUILDINGS, WHICH IS USED OR ADAPTED
 FOR JOINT SERVICE BETWEEN THE TWO BUILDINGS, SHALL BE
 CONSTRUCTED AS A FIRE WALL IN ACCORDANCE WITH SECTION
 706. PARTY WALLS SHALL BE CONSTRUCTED WITHOUT OPENINGS
 AND SHALL CREATE SEPARATE BUILDINGS. F1, M & B
 OCCUPANCIES ALL REQUIRE A 3 HOUR FIRE WALL.
 IF THERE ARE 2 BEARING WALLS, ONE FOR EACH BUILDING
 THEN TABLE 601 EXTERIOR BEARING WALLS FOR CONSTRUCTION
 TYPE III-B WOULD ALSO REQUIRE 2 HOUR WALLS. PLEASE
 UPDATE PLANS ACCORDINGLY.
 2A) THE LAST KNOWN USE UNDER PERMIT NUMBER 00061010
 THERE WAS A DOOR FROM THE RETAIL AREA DIRECTLY INTO
 STAIRWELL 109, THIS DOOR OPENING WAS CLOSED UP WITHOUT
 THE BENEFIT OF A PERMIT. PLEASE IDENTIFY THE TYPE OF
 MATERIALS AND RATING OF THE INFILL.
 FBC-B 1009.3.1.2 FIRE-RESISTANCE RATING. EXIT ACCESS
 STAIRWAY ENCLOSURES SHALL HAVE A FIRE-RESISTANCE RATING
 OF NOT LESS THAN 2 HOURS WHERE CONNECTING FOUR STORIES
 OR MORE, AND NOT LESS THAN 1 HOUR WHERE CONNECTING LESS
 THAN FOUR STORIES.
 2B) THE SAME STAIRWELL ON THE SUBMITTED PLANS INDICATES
 AN EXISTING DOOR BUT UNDER THE LAST PERMIT FOR THIS
 SUITE THERE IS NO DOOR NOR IS THERE PLANS SHOWING A
 PORTION OF THE EXTERIOR OPENING BEING ENCLOSED.
 2C) THE 1ST FLOOR IN THE PRODUCTION ROOM 101 THERE
 SHOWS AN EXISTING EXTERIOR DOOR ON THE EAST SIDE OF THE
 BUILDING. PLEASE NOTE UNDER THE LAST KNOWN PERMIT
 00061010 THERE WAS NO DOOR. PLEASE PROVIDE DETAILS OF
 REINFORCEMENT COLUMNS, LINTEL OR BEAM TYING BACK INTO
 THE MWFRS MAIN WIND FORCE RESISTING SYSTEM.
 2D) PLEASE PROVIDE WHERE THE ACCESSIBLE EGRESS IS
 LOCATED ON THE PLANS. 2014 FBC-ACCESSIBILITY CODE
 SECTION 207.1 MEANS OF EGRESS SHALL COMPLY WITH SECTION
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE (2000
 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF THE
 INTERNATIONAL BUILDING CODE (2003 EDITION).
  
 3) NO ACTION REQUIRED, BACK OPEN STAIRWAY IS CONSIDERED
 AN EXIT ACCESS STAIR INCOMPLIANCE WITH 1009.3 , 1014.3
 COMMON PATH OF TRAVEL 100 FT. < 30 OCCUPANTS/ WITHOUT
 SPRINKLERS & 1016.3 EXIT ACCESS STAIRS.
 4A) SHEET LS.1 THE 2ND FLOOR SHOWS THE SQUARE FOOTAGE
 OF 1598 SQ. FT./ 300= 5.33 OCCUPANT LOADS ALWAYS ROUND
 UP, THE OCCUPANT LOAD WOULD BE 6 OCCUPANTS. THE
 DESIGNER OF RECORD WILL EITHER NEED TO PROVIDE A LETTER
 EXPLAINING WHY THERE WOULD BE A REDUCED OCCUPANT LOAD
 FOR STORAGE OR PROVIDE VERTICAL ACCESSIBILITY TO THE
 2ND FLOOR. 201.1.1 VERTICAL ACCESSIBILITY. THE
 EXCEPTION (3) IS LIMITED TO 5 PERSONS. THE ALTERNATIVE
 IS TO PROVIDE A LULA LIFT IN ACCORDANCE WITH 2014
 FBC-ACCESSIBILITY 408 LIMITED USE/ LIMITED APPLICATION
 ELEVATOR.
 4B) PLEASE NOTE THAT IF THE DESIGNER OF RECORD DOES
 PROVIDE A LULA LIFT THEN PROVISIONS FOR AN AREA OF
 RESCUE ASSISTANCE WILL ALSO BE REQUIRED IN ACCORDANCE
 WITH 2014 FBC-ACCESS. CODE SECTION 207.1. AND THE
 SECTION 1007.6 OF THE 2003 IBC-BUILDING CODE.
 5) PLEASE NOTE THE 2ND FLOOR IS GOING TO BE STORAGE
 OCCUPANCY AND WILL NEED TO SHOW COMPLIANCE WITH:
 5A) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 106.1 LIVE LOADS POSTED. WHERE THE LIVE
 LOADS FOR WHICH EACH FLOOR OR PORTION THEREOF OF A
 COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN
 DESIGNED TO EXCEED 50 PSF, SUCH DESIGN LIVE LOADS SHALL
 BE CONSPICUOUSLY POSTED BY THE OWNER IN THAT PART OF
 EACH STORY IN WHICH THEY APPLY, USING DURABLE SIGNS. IT
 SHALL BE UNLAWFUL TO REMOVE OR DEFACE SUCH NOTICES.
 5B) 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A
 CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111
 SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS,
 REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED.
  
 5C) 106.3 RESTRICTIONS ON LOADING. IT SHALL BE UNLAWFUL
 TO PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON
 ANY FLOOR OR ROOF OF A BUILDING, STRUCTURE OR PORTION
 THEREOF, A LOAD GREATER THAN IS PERMITTED BY THIS
 CODE. PLEASE VERIFY THE ALLOWABLE FLOOR LIVE LOADS 125
 PSF LIGHT OR 250 PSF HEAVY, FBC-B TABLE 1016.1.
  
 6) SHEET S-1 SHOWS A EXISTING 8X12 COLUMN BUT THERE NO
 REFERENCE TO WHERE THIS COLUMN IS LOCATED TO THE REST
 OF THE BUILDING. THIS COLUMN DOES NOT EVEN SHOW ON THE
 LS SHEET OR THE A1 FLOOR PLAN. ADDITIONAL INFORMATION
 IS REQUIRED. 107.2.1.3. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 7) THE PLANS FAIL TO PROVIDE HOW COMPLIANCE WITH 2014
 FBC-ACCESSIBILITY CODE 904.4 SALES AND SERVICE
 COUNTERS. SALES COUNTERS AND SERVICE COUNTERS SHALL
 COMPLY WITH 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION
 OF THE COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE
 SALES OR SERVICE COUNTER TOP.
  
 8) SHEET A-3 DETAIL 14 RESTROOM DETAILS PLEASE REVIEW
 THE GRAB BAR DIMENSION IN HOW THEY ARE MEASURED, NO
 LONGER DO YOU USE THE CENTER LINE BUT THE TOP OF THE
 GRASPING SURFACE. ACCESS. CODE 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE GRIPPING SURFACE.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-11 Cont ID  
Sent By vperez Date 2016-08-11 Time 05:43 Rev Time 0.00
Received By vperez Date 2016-08-11 Time 05:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-15 Cont ID  
Sent By vperez Date 2016-07-15 Time 07:24 Rev Time 0.00
Received By vperez Date 2016-07-15 Time 07:24 Sent To  
Notes
2016-07-15 07:34:14INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4-
 COMPLETION DOCUMENTS PER CODE SECTION.
 3. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION
 PROVIDED BY UTILITY FOR APPROVAL. NEC 110.24 FBC 107
 4. CHANGES ARE SHOWN TO THE EXISTING SERVICE
 ARRANGEMENTS. LABEL MAINS TO INDICATE MAIN 1 OF 3 AND 2
 OF 3 ETC, ALSO COMPLY WITH THE REQUIRED SIGNAGE TO
 ASSIST FIRST RESPONDERS. NEC 230.70B
 5. LABEL ALL MAINS TO RATED FOR SERVICE ENTRANCE. SHOW
 METER AMP RATINGS.
 6. PROVIDE A NOTE PER PLAN TO USE EXISTING BOX AS A
 JUNCTION BOX, THAT EQUIPMENT IS TO BE LISTED AND
 LABELED PER NEC 110.3B
 7. SHEET E1.1 SHOW ROOFTOP RECEPTACLES TO WP/ GFCI
 PROTECTED NEC 210.8B
 8. LABEL FOUNTAIN RECEPTACLES TO BE GFCI PROTECTED PER
 NEC 422.52
 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-17 Cont ID  
Sent By pleduc Date 2016-08-17 Time   Rev Time 0.00
Received By pleduc Date 2016-08-17 Time 09:03 Sent To P
Notes
2016-08-17 13:01:14THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET E 1.1 - ONLY ONE (1) PHONE HEADSET IS
 INDICATED ON THE PLAN SHEET. THE AREA OF REFUGE
 COMMUINCATION SYSTEM SHALL BE PROVIDED AS REQUIRED BY
 NFPA 101, CHAPTER 7.
  
 7.2.12 AREAS OF REFUGE.
 7.2.12.1 GENERAL.
 7.2.12.1.1 AN AREA OF REFUGE USED AS PART OF A REQUIRED
 ACCESSIBLE MEANS OF EGRESS IN ACCORDANCE WITH 7.5.4;
 CONSISTING OF A STORY IN A BUILDING THAT IS PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 9.7; AND
 HAVING AN ACCESSIBLE STORY THAT IS ONE OR MORE STORIES
 ABOVE OR BELOW A STORY OF EXIT DISCHARGE SHALL MEET THE
 FOLLOWING CRITERIA:
 (1) EACH ELEVATOR LANDING SHALL BE PROVIDED WITH A
 TWO-WAY COMMUNICATION SYSTEM FOR COMMUNICATION BETWEEN
 THE ELEVATOR LANDING AND THE FIRE COMMAND CENTER OR A
 CENTRAL CONTROL POINT APPROVED BY THE AUTHORITY HAVING
 JURISDICTION.
 (2) DIRECTIONS FOR THE USE OF THE TWO-WAY COMMUNICATION
 SYSTEM, INSTRUCTIONS FOR SUMMONING ASSISTANCE VIA THE
 TWO-WAY COMMUNICATION SYSTEM, AND WRITTEN
 IDENTIFICATION OF THE LOCATION SHALL BE POSTED ADJACENT
 TO THE TWO-WAY COMMUNICATION SYSTEM.
 (3) THE TWO-WAY COMMUNICATION SYSTEM SHALL INCLUDE BOTH
 AUDIBLEAND VISIBLE SIGNALS
  
  
 7.2.12.2.5 THE AREA OF REFUGE SHALL BE PROVIDED WITH A
 TWO-WAY COMMUNICATION SYSTEM FOR COMMUNICATION BETWEEN
 THE AREA OF REFUGE AND A CENTRAL CONTROL POINT. THE
 DOOR OPENING TO THE STAIR ENCLOSURE OR THE ELEVATOR
 DOOR AND THE ASSOCIATED PORTION OF THE AREA OF REFUGE
 THAT THE STAIR ENCLOSURE DOOR OPENING OR ELEVATOR DOOR
 SERVES SHALL BE IDENTIFIED BY SIGNAGE. (SEE
 7.2.12.3.5.)
  
  
 7.2.12.2.6* INSTRUCTIONS FOR SUMMONING ASSISTANCE, VIA
 THE TWOWAY COMMUNICATION SYSTEM, AND WRITTEN
 IDENTIFICATION OF THE AREA OF REFUGE LOCATION SHALL BE
 POSTED ADJACENT TO THE TWO-WAY COMMUNICATION SYSTEM.
  
  
 AS PER DISCUSSION WITH GLENN PATE, ARCHITECT, PROVIDE A
 2ND PHONE HEADSET IN THE FRONT OF THE BUILDING LOCATED
 IN AN AREA COORDINATED WITH THE FIRE MARSHAL'S OFFICE
 AND PROVIDE A REVISION.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-06 Cont ID  
Sent By pleduc Date 2016-07-07 Time 16:59 Rev Time 0.00
Received By pleduc Date 2016-07-06 Time 11:52 Sent To  
Notes
2016-07-06 16:59:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET LS 1 - AN F 1 OCCUPANCY IS INDICATED; HOWEVER,
 THERE IS NO F 1 IN THE REFERENCED FLORIDA LIFE SAFETY
 CODE.
  
 THIS PROPOSED PROJECT FALLS UNDER NFPA 101, CHAPTER 40
 INDUSTRIAL OCCUPANCIES AND SHALL COMPLY WITH THOSE
 REQUIREMENTS.
  
 PLEASE IDENTIFY THE CLASSIFICATION OF CONTENTS PER
 SECTION 40.1.2 CLASSIFICATION OF OCCUPANCY.
 CLASSIFICATION OF OCCUPANCY SHALL BE IN ACCORDANCE WITH
 6.1.12.
 40.1.2.1 SUBCLASSIFICATION OF OCCUPANCY. EACH
 INDUSTRIAL OCCUPANCY SHALL BE SUBCLASSIFIED ACCORDING
 TO ITS USE AS DESCRIBED IN 40.1.2.1.1, 40.1.2.1.2, AND
 40.1.2.1.3. 40.1.2.1.1 GENERAL INDUSTRIAL OCCUPANCY.
 GENERAL INDUSTRIAL OCCUPANCIES SHALL INCLUDE ALL OF THE
 FOLLOWING:
 (1) INDUSTRIAL OCCUPANCIES THAT CONDUCT ORDINARY AND
 LOW HAZARD INDUSTRIAL OPERATIONS IN BUILDINGS OF
 CONVENTIONAL DESIGN THAT ARE USABLE FOR VARIOUS TYPES
 OF INDUSTRIAL PROCESSES
 (2) INDUSTRIAL OCCUPANCIES THAT INCLUDE MULTISTORY
 BUILDINGS WHERE FLOORS ARE OCCUPIED BY DIFFERENT
 TENANTS, OR BUILDINGS THAT ARE USABLE FOR SUCH
 OCCUPANCY AND, THEREFORE, ARE SUBJECT TO POSSIBLE USE
 FOR TYPES OF INDUSTRIAL PROCESSES WITH A HIGH DENSITY
 OF EMPLOYEE POPULATION
 40.1.2.1.2 SPECIAL-PURPOSE INDUSTRIAL OCCUPANCY.
 SPECIALPURPOSE INDUSTRIAL OCCUPANCIES SHALL INCLUDE ALL
 OF THE FOLLOWING:
 (1) INDUSTRIAL OCCUPANCIES THAT CONDUCT ORDINARY AND
 LOW HAZARD INDUSTRIAL OPERATIONS IN BUILDINGS DESIGNED
 FOR, AND THAT ARE USABLE ONLY FOR, PARTICULAR TYPES OF
 OPERATIONS
 (2) INDUSTRIAL OCCUPANCIES THAT ARE CHARACTERIZED BY A
 RELATIVELY LOW DENSITY OF EMPLOYEE POPULATION, WITH
 MUCH OF THE AREA OCCUPIED BY MACHINERY OR EQUIPMENT
 40.1.2.1.3* HIGH HAZARD INDUSTRIAL OCCUPANCY. HIGH
 HAZARD INDUSTRIAL OCCUPANCIES SHALL INCLUDE ALL OF THE
 FOLLOWING:
 (1) INDUSTRIAL OCCUPANCIES THAT CONDUCT INDUSTRIAL
 OPERATIONS THAT USE HIGH HAZARD MATERIALS OR PROCESSES
 OR HOUSE HIGH HAZARD CONTENTS
 (2) INDUSTRIAL OCCUPANCIES IN WHICH INCIDENTAL HIGH
 HAZARD OPERATIONS IN LOW OR ORDINARY HAZARD OCCUPANCIES
 THAT ARE PROTECTED IN ACCORDANCE WITH SECTION 8.7 AND
 40.3.2 ARE NOT REQUIRED TO BE THE BASIS FOR OVERALL
 OCCUPANCY CLASSIFICATION
  
 PLEASE PROVIDE A DETAILED DESCRIPTION OF THE WORK OR
 PRODUCT AND WHAT SUBCLASSIFICATION IS PROPOSED TO
 COMPLY WITH.
  
  
 2) SHEET LS 1 - UNDER THE BUILDING CODE REQUIREMENTS
 IT'S INDCATING A 75' MAXIMUN COMMON PATH OF TRAVEL.
  
 PER NFPA 101, CHAPTER 40, TABLE 40.2.5 THE MAXIMUM
 COMMON PATH OF TRAVEL IS INDCATED AS 50'
  
 PLEASE CORRECT OR CLARIFY.
  
  
  
 3) SHEET LS 1 - TRAVEL DISTANCE TO AN EXIT ON THE 1ST
 FLOOR IS INDICATED AS 52'.9". PER NFPA 101, CHAPTER 40,
 TABLE 40.2.5 INDICATES IT CAN NOT EXCEED 50"
  
 PLEASE CORRECT OR CLARIFY.
  
  
  
 4) SHEET LS 1 - A VERTICAL OPENING STAIRWAY IS
 INDICATED ON THE PLAN. PER NFPA 101, CHAPTER 40, 40.3.1
 PROTECTION OF VERTICAL OPENINGS. ANY VERTICAL OPENING
 SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 8.6,
 UNLESS OTHERWISE
 PERMITTED BY ONE OF THE FOLLOWING:
 (1) IN SPECIAL-PURPOSE INDUSTRIAL AND HIGH HAZARD
 INDUSTRIAL OCCUPANCIES WHERE UNPROTECTED VERTICAL
 OPENINGS EXIST AND ARE NECESSARY TO MANUFACTURING
 OPERATIONS, SUCH OPENINGS SHALL BE PERMITTED BEYOND THE
 SPECIFIED LIMITS, PROVIDED THAT EVERY FLOOR LEVEL HAS
 DIRECT ACCESS TO ONE OR MORE ENCLOSED STAIRS OR OTHER
 EXITS PROTECTED AGAINST OBSTRUCTION BY ANY FIRE OR
 SMOKE IN THE OPEN AREAS CONNECTED BY THE UNPROTECTED
 VERTICAL OPENINGS.
 (2) APPROVED EXISTING OPEN STAIRS, EXISTING OPEN RAMPS,
 AND EXISTING ESCALATORS SHALL BE PERMITTED WHERE
 CONNECTING ONLY TWO FLOOR LEVELS.
 (3) APPROVED, EXISTING, UNPROTECTED VERTICAL OPENINGS
 IN BUILDINGS WITH LOW OR ORDINARY HAZARD CONTENTS THAT
 ARE PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.1(1) SHALL BE
 PERMITTED, PROVIDED THAT THE FOLLOWING CONDITIONS
 EXIST:
 (A) THE VERTICAL OPENING DOES NOT SERVE AS A REQUIRED
 EXIT.
 (B) ALL REQUIRED EXITS CONSIST OF OUTSIDE STAIRS IN
 ACCORDANCE WITH 7.2.2, SMOKEPROOF ENCLOSURES IN
 ACCORDANCE WITH 7.2.3, OR HORIZONTAL EXITS IN
 ACCORDANCE WITH 7.2.4.
 (4) VERTICAL OPENINGS IN ACCORDANCE WITH 8.6.9.1 SHALL
 BE PERMITTED
  
 THIS IS NOT AN APPROVED EXISTING STAIR. THE PROPOSED IS
 A CHANGE OF OCCUPANCY.
  
 PLEASE CORRECT OR PROVIDE CLARIFICATION OR
 JUSTIFICATION.
  
  
  
 5) SHEET LS 1 - THERE ARE TWO (2) STAIRWAYS INDICATED.
  
 THERE IS NO STAIR DETAIL OR INDICATIONS THAT THEY
 COMPLY WITH THE CODE PER 40.2.2.3 STAIRS.
 40.2.2.3.1 STAIRS SHALL COMPLY WITH 7.2.2 AND SHALL BE
 PERMITTED TO BE MODIFIED BY ANY OF THE FOLLOWING:
 (1) NONCOMBUSTIBLE GRATED STAIR TREADS AND
 NONCOMBUSTIBLE GRATED LANDING FLOORS SHALL BE
 PERMITTED.
 (2) INDUSTRIAL EQUIPMENT ACCESS STAIRS IN ACCORDANCE
 WITH 40.2.5.2 SHALL BE PERMITTED.
  
 PLEASE CLEARLY INDICATE HEADROOM.
  
 PLEASE CORRECT AND PROVIDE STAIR DETAIL.
  
  
 6) SHEET LS 1 - THE DOOR SWINGS FROM THE THE PRODUCTION
 AREA SHOW THEM SWINGING AGAINST THE DIECTION OF EGRESS.
  
 PER SECTION 40.2.2.2 DOORS.
 40.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE OF THE SIDE-HINGED OR PIVOTED-SWINGING
 TYPE SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL
 UNDER ANY OF THE FOLLOWING CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR MORE, EXCEPT UNDER ANY OF THE FOLLOWING
 CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO SWING IN THE DIRECTION OF EGRESS TRAVEL
 WHERE PERMITTED BY 7.2.4.3.8.1 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING
 HEALTH CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS THE DOOR OPENING SERVES AN INDIVIDUAL
 LIVING UNIT THAT OPENS DIRECTLY INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD
 CONTENTS AREA
  
 PLEASE CORRECT OR CLARIFY IN RELATION TO (3) AND
 COMMENT # 1 ABOVE.
  
  
  
 7) SHEET LS 1 - A KITCHENETTE IS INDICATED; HOWEVER, AN
 EQUIPMENT PLAN IS NOT.
  
 PLEASE PROVIDE A KITCHETTE EQUIPMENT PLAN.
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-19 Cont ID  
Sent By tklarge Date 2016-08-19 Time 14:41 Rev Time 0.00
Received By tklarge Date 2016-08-04 Time 11:26 Sent To  
Notes
2016-08-05 11:26:59B30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By tklarge Date 2016-06-30 Time 11:25 Sent To  
Notes
2016-07-01 11:25:56B29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-07-08 Cont ID  
Sent By jwitmer Date 2016-07-08 Time 13:47 Rev Time 0.00
Received By jwitmer Date 2016-07-08 Time 07:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-08-24 Cont ID  
Sent By ccole Date 2016-08-24 Time 11:14 Rev Time 0.00
Received By ccole Date 2016-08-24 Time 11:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-08-15 Cont ID  
Sent By ccole Date 2016-08-15 Time 13:07 Rev Time 0.00
Received By ccole Date 2016-08-15 Time 12:19 Sent To  
Notes
2016-08-15 13:12:212ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16061686
 8/15/16
  
 1) THE REQUESTED AC CALCULATIONS WERE NOT SUBMITTED.
  
 2) THE CONTRACTOR OR HIS/HER PERMIT AGENT MUST INSERT
 THE NEW MECHANICAL PLAN SHEETS INTO THE MAIN SETS, AND
 VOID OUT THE OLD SHEETS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-11 Cont ID  
Sent By ccole Date 2016-07-11 Time 11:31 Rev Time 0.00
Received By ccole Date 2016-07-11 Time 11:31 Sent To  
Notes
2016-07-11 12:05:441ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16061686
 7/11/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 COMPLIANCE WITH SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) M4.1: AC 2-1 IS MISLABELED AS A 5-TON SYSTEM.
  
 3) M4.1: THE VENTILATION CALCULATIONS DO NOT INCLUDE A
 BREAKDOWN FOR THE PRODUCTION 101 AREA OF THE PROPOSED
 OCCUPANCY. PLEASE CLARIFY WHAT TYPE OF WORK WILL BE
 PERFORMED THERE AND WHAT TYPE OF EQUIPMENT WILL BE
 USED.
  
 3) EF-1-1 AND 2-1 SHALL EACH HAVE MINIMUM 70 CFM
 CAPACITIES- TABLE 403.3.
  
 4) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE NEW AIR
 HANDLERS- SECTION 307. NOTE: NO DETAILS ARE SHOWN ON
 THE PLUMBING PLANS.
  
 4) SUBMIT COPIES OF THE FL. PRODUCT APPROVAL FOR THE AC
 STAND, AND THE MIAMI-DADE NOA FOR THE O/A LOUVER WITH
 SHOP DRAWING SIGNATURES BY THE EOR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-08-19 Cont ID  
Sent By tklarge Date 2016-08-19 Time 14:41 Rev Time 0.00
Received By tklarge Date 2016-08-19 Time 14:40 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-07-28 Cont ID  
Sent By tklarge Date 2016-07-28 Time 11:32 Rev Time 0.00
Received By tklarge Date 2016-07-28 Time 05:40 Sent To  
Notes
2016-07-28 06:56:141) SHT. LS-1 - THE BUILDING CODE DATA LISTS A BUSINESS
 OCCUPANCY BUT A BUSINESS AREA IS NOT SHOWN ON THE
 PLANS. CLARIFY.
 2) SEPARATE FACILITIES SHALL BE PROVIDED FOR THE MALES
 AND FEMALES. 2014 FBC-PLUMBING SEC. 403.1.1, 403.2.
 BOTH TOILET ROOMS SHALL BE HANDICAPPED ACCESSIBLE PER
 THE 2014 FBC-ACCESS. SEC.213.2.
 3) VERTICAL ACCESSIBILITY SHALL BE PROVIDED FOR THE
 TOILET ROOM ON THE SECOND FLOOR.FBC-ACCESSIBILITY SEC.
 201.1.1.
 4) THE DRINKING FOUNTAINS SHALL COMPLY WITH FBC-ACCESS.
 SECS.204.1 7 307 FOR PROTRUDING OBJECTS.
 5) THE FINISH SCHEDULE ON SHT. A-1 SHOWS THE WALLS IN
 THE TOILET ROOMS AND JANITORS CLOSET TO BE PAINT.WALLS
 AND PARTITIONS WITHIN TWO FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBANT SURFACE TO A HEIGHT OF NO LESS THAN FOUR
 FEET ABOVE THE FLOOR PER 2014 FBC SEC.1210.2.2.
 6) THE PLAN SHOWS PRODUCTION AREAS. SUBMIT INFORMATION
 AS TO WHAT TYPE OF PROCESSES WILL BE PERFORMED IN THESE
 AREAS. WPB AMEND. TO 2014 FBC SEC.107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy