Plan Review Details - Permit 16061677
Plan Review Stops For Permit 16061677
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-04 Cont ID  
Sent By hmoser Date 2016-08-15 Time 14:29 Rev Time 0.00
Received By wjolin Date 2016-08-04 Time 09:12 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-07 Cont ID  
Sent By wjolin Date 2016-07-07 Time 13:53 Rev Time 0.00
Received By wjolin Date 2016-07-07 Time 13:38 Sent To M
Notes
2016-07-07 13:51:171851 DIVISION AVENUE
 PERMIT #16061677
 MASTER #15050261
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION AND THE ADDRESS OF THE BUILDING
 BEING SERVED.
  
 SHEET FP-203: PROVIDE A DWELLING UNIT HYDRAULIC
 CALCULATION SUPPORTING THE USE OF 4 SPRINKLERS ON
 1-1/2" BRANCH LINE.
  
 SHEET FP-305: SECTION BB DETAIL STATES THE SIDEWALL
 MODEL VK460 K-5.8 IS TO BE LOCATED 6" BELOW THE
 CEILING; HOWEVER, THE ACTUAL PIPE DROP DETAIL APPEARS
 TO SHOW A 12" DROP. WHICH VALUE IS THE CORRECT VALUE?
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-15 Cont ID  
Sent By hmoser Date 2016-08-15 Time 14:29 Rev Time 0.00
Received By hmoser Date 2016-07-26 Time 16:14 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-18 Cont ID  
Sent By hmoser Date 2016-07-18 Time 09:29 Rev Time 0.00
Received By hmoser Date 2016-06-30 Time 09:59 Sent To  
Notes
2016-07-01 10:00:07ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-08-15 Cont ID  
Sent By hmoser Date 2016-08-15 Time 14:29 Rev Time 0.00
Received By hmoser Date 2016-08-15 Time 14:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-18 Cont ID  
Sent By hmoser Date 2016-07-18 Time 09:16 Rev Time 0.00
Received By hmoser Date 2016-07-18 Time 09:16 Sent To  
Notes
2016-07-18 09:28:58PLAN DENIED
 PROVIDE THE ORIGINAL STAMPED SHEETS FROM THE ENGINEER
 FOR SHOP DRAWING REVIEW. CAN NOT EXCEPT COPY'S
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-66766


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved