Plan Review Details - Permit 16061675
Plan Review Stops For Permit 16061675
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-04 Cont ID  
Sent By hmoser Date 2016-08-15 Time 15:05 Rev Time 0.00
Received By wjolin Date 2016-08-04 Time 09:19 Sent To M
Notes
2016-08-04 11:07:27838 ADAMS STREET
 PERMIT #16061675
 MASTER #15050261
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 SHEET FP-101: PROVIDE A HYDRAULIC CALCULATION FOR AN
 AREA ENCOMPASSING THE EXERCISE ROOM.
  
 GENERAL: PLANS INDICATE MIAMI THREADS ON THE STANDPIPE
 FIRE DEPARTMENT VALVES. ENSURE THREADS ARE NST -
 NATIONAL STANDARD THREAD.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-07 Cont ID  
Sent By wjolin Date 2016-07-07 Time 13:36 Rev Time 0.00
Received By wjolin Date 2016-07-07 Time 09:26 Sent To M
Notes
2016-07-07 09:46:24838 ADAMS STREET
 PERMIT #16061675
 MASTER #15050261
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION AND THE ADDRESS OF THE BUILDING
 BEING SERVED.
  
 SHEET FP-101: NO SPRINKLER PROTECTION PROVIDED IN
 SOUTHWEST MAINTENANCE ROOM.
  
 SHEET FP-101: PLANS SHOW THE 4" & 6" STANDPIPE MAIN
 ROUTED THROUGH THE ELECTRICAL ROOM BETWEEN COLUMN LINES
 8 & 9. THIS IS PROHIBITED BY NFPA 70 ARTICLE 110. THIS
 PIPING IS ALSO ROUTED THROUGH ANOTHER ELECTRICAL ROOM
 ON SHEET FP-102.
  
 SHEET FP-101: PLANS SHOWS THE CLUB ROOM AND EXCERCISE
 ROOM PROTECTED WITH EXTENDED COVERAGE SPRINKLERS
 LOCATED IN THE HIGH CEILING (14'-8"). THE ENTIRE FLOOR
 AREA IS NOT BEING PROTECTED DUE TO THE OBSTRUCTIONS OF
 THE LOWER CEILING ELEVATION (12'-8"). DESIGN CHANGES TO
 THIS AREA WILL EFFECT THE HYDRAULIC CALCULATIONS.
  
 SHEET FP-101: "LEVEL 1 LOBBY AREA" HYDRAULIC
 CALCULATION IS INCORRECTLY CALCULATED. THE HYDRAULIC
 CALCULATION HAS THE LONG SIDE (1.2 X THE SQUARE ROOT OF
 THE AREA OF SPRINKLER OPERATION) OF THE HYDRAULIC AREA
 DRAWN PERPENDICULAR TO THE BRANCH LINES WHEN THE LONG
 SIDE OF THE HYDRAULIC AREA SHOULD BE RUN PARALLEL TO
 THE BRANCH LINES PER NFPA 13 (2010 EDITION) SECTION
 22.4.4.1.1.1.
  
 SHEET FP-101: PROVIDE A HYDRAULIC CALCULATION FOR AN
 AREA ENCOMPASSING THE EXERCISE ROOM.
  
 SHEET FP-102: SPRINKLER RISER IS SHOWN ENTERING THE
 TRASH ROOM (SEMI-CORROSIVE). PLEASE RELOCATE. STAIR #4
 MAY BE A BETTER LOCATION.
  
 SHEET FP-102: THE SPRINKLER PROTECTING THE STORAGE ROOM
 (COLUMN LINE 14/15) HAS AN SXL COVERAGE EXCEEDING 130
 SQUARE FEET.
  
 SHEET FP-105, 106, 107 & 108: NO SPRINKLER PROTECTION
 PROVIDED IN PORTION OF ENCLOSED EXTERIOR EXIT CORRIDOR.
  
 SHEET FP-106: PROVIDE HYDRAULIC CALCULATIONS SUPPORTING
 THE DESIGN FOR UNIT C.
  
 SHEET FP-110: PROVIDE A DWELLING UNIT HYDRAULIC
 CALCULATION SUPPORTING THE USE OF 4 SPRINKLERS ON
 1-1/4" BRANCH LINE.
  
 SHEET FP-113: SECTION BB DETAIL STATES THE SIDEWALL
 MODEL VK460 K-5.8 IS TO BE LOCATED 6" BELOW THE
 CEILING; HOWEVER, THE ACTUAL PIPE DROP DETAIL APPEARS
 TO SHOW A 12" DROP. WHICH VALUE IS THE CORRECT VALUE?
  
 HYDRAULIC CALCULATIONS: CALCULATION INDICATES "5TH
 FLOOR UNIT A, REMOTE AREA C." THIS CALCULATION AREA WAS
 NOT FOUND ON THE 5TH FLOOR PLANS. THE SAME HOLDS TRUE
 FOR "3RD FLOO UNIT A, REMOTE AREA A." THE INFORMATION
 BOX IS NOT FOUND ON THE PLAN.
  
 GENERAL: WHY ARE SPRINKLERS ON DIFFERENT FLOOR SUPPLIED
 FROM DIFFERENT STAIRS? THIS IS CONFUSING. FOR EXAMPLE
 THE GROUND FLOOR SUPPLIES THE SPRINKLER SYSTEM FROM THE
 CONTROL VALVES LOCATED IN STAIR #1 AND #3; WHILE 2ND
 FLOOR SPRINKLERS ARE SUPPLIED FROM STAIRS #2 AND #4.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-15 Cont ID  
Sent By hmoser Date 2016-08-15 Time 15:05 Rev Time 0.00
Received By hmoser Date 2016-07-26 Time 16:06 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-11 Cont ID  
Sent By hmoser Date 2016-07-11 Time 14:25 Rev Time 0.00
Received By hmoser Date 2016-06-30 Time 10:02 Sent To  
Notes
2016-07-01 10:03:07ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-08-15 Cont ID  
Sent By hmoser Date 2016-08-15 Time 15:05 Rev Time 0.00
Received By hmoser Date 2016-08-15 Time 14:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-11 Cont ID  
Sent By hmoser Date 2016-07-11 Time 14:21 Rev Time 0.00
Received By hmoser Date 2016-07-11 Time 14:02 Sent To  
Notes
2016-07-11 14:24:39PLAN DENIED
 REFER TO FIRE COMMENTS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676