Plan Review Details - Permit 16061663
Plan Review Stops For Permit 16061663
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-08-15 Cont ID  
Sent By shill Date 2016-08-15 Time 19:13 Rev Time 0.00
Received By shill Date 2016-08-15 Time 19:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-09 Cont ID  
Sent By shill Date 2016-08-09 Time 07:19 Rev Time 0.00
Received By shill Date 2016-08-09 Time 07:05 Sent To  
Notes
2016-08-09 07:20:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. I WAS UNABLE TO LOCATE WIND DESIGN CRITERIA ON THIS
 PLAN, FBC 1609. THE MASTER FOR THIS REVISION
 (16010527), SHEET S213, HAS A NOTE REGARDING COMPONENTS
 & CLADDING WIND PRESSURE 169MPH ULTIMATE. AS THE SCOPE
 OF THIS PERMIT INCLUDES THE TRELLIS, GATES, AND WALL,
 PLEASE CLARIFY WIND DESIGN CRITERIA (WIND SPEED,
 EXPOSURE).
  
 2. PEDERSTRIAN GATES ARE DEPICTED ON THE ARCH SHEETS.
 ALL GATES IN THE MEANS OF EGRESS (EXIT DISCHARGE) FOR
 THE ASSEMBLY OCCUPANCY ARE TO INCLUDE PANIC DEVICES OR
 FIRE EXIT HARDWARE, FBC 1008.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-12 Cont ID  
Sent By shill Date 2016-09-12 Time 06:47 Rev Time 0.00
Received By shill Date 2016-08-10 Time 08:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-09 Cont ID  
Sent By shill Date 2016-08-09 Time 07:31 Rev Time 0.00
Received By shill Date 2016-07-18 Time 08:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-09-12 Cont ID  
Sent By shill Date 2016-09-12 Time 06:47 Rev Time 0.00
Received By shill Date 2016-09-12 Time 06:47 Sent To  
Notes
2016-09-12 06:47:069/12 C SHEETS OK
  
2016-08-15 19:13:528/15/16 ARCH & STRUCT SHEETS OK, SH

Review Stop Z ZONING
Rev No 2 Status P Date 2016-09-01 Cont ID  
Sent By eschneid Date 2016-09-01 Time 18:03 Rev Time 0.50
Received By eschneid Date 2016-09-01 Time 17:42 Sent To  
Notes
2016-09-01 18:04:26PASSED
  
 STAFF HAS NOTED THAT TRUCKS (LARGE DELIVERY AND
 GARBAGE) MAY REQUIRE GATE ARMS TO RECESS PARALLEL TO
 THE COLUMN EDGES AT THE DRIVEWAYS SO AS NOT TO BE HIT
 WHEN REVIEWED VS. THE PROVIDED GARBAGE TRUCK TURNING
 DETAIL.

Review Stop Z ZONING
Rev No 1 Status F Date 2016-08-04 Cont ID  
Sent By eschneid Date 2016-08-04 Time 14:39 Rev Time 0.75
Received By eschneid Date 2016-08-04 Time 14:39 Sent To  
Notes
2016-08-04 14:40:24FAILED - UNTIL CC APPROVAL
  
 1) THE PROPOSED SITE LAYOUT IS SCHEDULED TO BE HEARD BY
 THE CITY COMMISSION ON AUGUST 29, 2016. ZONING CANNOT
 GIVE FINAL APPROVAL OF THE PERMIT UNTIL AFTER THE
 COMMISSION APPROVAL AND EFFECTIVE DATE OF THE
 RESOLUTION.
  
 2) SHEETS THAT WILL BE APPROVED UPON PASSAGE OF
 RESOLUTION NO. 260-16 - A-050, A-101, A-106, A-107,
 A-201A, 202A, A-426, A-440, A-441, S-4.02
  
 3) STAFF HAS NOTED THAT TRUCKS (LARGE DELIVERY AND
 GARBAGE) MAY REQUIRE GATE ARMS TO RECESS PARALLEL TO
 THE COLUMN EDGES AT THE DRIVEWAYS SO AS NOT TO BE HIT
 WHEN REVIEWED VS. THE PROVIDED GARBAGE TRUCK TURNING
 DETAIL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  