Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-07-08 Cont ID  
Sent By ccole Date 2016-07-08 Time 11:34 Rev Time 0.00
Received By ccole Date 2016-07-08 Time 11:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-01 Cont ID  
Sent By ccole Date 2016-07-01 Time 14:32 Rev Time 0.00
Received By ccole Date 2016-07-01 Time 14:32 Sent To  
Notes
2016-07-01 14:39:221ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16061662
 7/1/16
  
 1) PLEASE PLACE REVISION CLOUDS AND A DELTA TRIANGLE ON
 THE PLAN INDICATING THE LOCATIONS OF REVISION 2.
  
 2) PROVIDE RETURN AIR FROM THE OFFICES- SECTION 601.5
  
 3) INDICATE THE CFM CAPACITIES OF THE DIFFUSERS IN THE
 OFFICES THAT ARE SHOWN AT THE TOP LEFT CORNER OF THE
 PLAN SHEET.
  
 4) INCLUDE THE LINEAR DIFFUSERS IN THE DEVICE SHCEDULE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  