| 2016-07-06 13:26:10 | BUILDING PLAN REVIEW |
| | REVISION: 16061589 |
| | PERMIT:14071105 |
| | ADD: 1517 CAMERON SAMUEL LN. |
| | CONT: KAST |
| | TEL: (561)346-4994 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JULY 2016 |
| | ACTION: DENIED |
| | |
| | 1) THE DESIGNER OF RECORD (ARCHITECT) HAS NOT REVIEWED |
| | THE INTERIOR DESIGNERS DRAWING FOR THE OVERALL CONCEPT |
| | IS IN COMPLIANCE WITH THE ARCHITECTS DESIGN. |
| | |
| | 1A) IN THE LAST REVISION 15031217 THE ARCHITECTURAL |
| | PLAN A-1.0 SHOWS THE RISER GOING ACROSS THE THEATER IN |
| | A STRAIGHT LINE 90 DEGREES TO THE SIDE WALLS. WHILE THE |
| | INTERIOR DESIGNER HAS A STRAIGHT LINE DOTTED AND A |
| | CURVED SOLID LINE, SHEET ID-11 DOES NOT HAVE A LEGEND |
| | INDICATING WHAT THESE LINES REPRESENT. DOES THE DOTTED |
| | LINE REPRESENT THE RISERS AND THE CURVED SOLID LINE |
| | INDICATE A DROPPED CEILING? THERE ARE NO CUT SECTIONS |
| | THROUGH THE CEILING SHOWING A DROPPED CEILING OR |
| | CONSTRUCTION OTHER THAN A FLAT CEILING. 107.2.1.3. NOT |
| | ENOUGH DETAIL IN THE PLANS TO INDICATE CODE COMPLIANCE. |
| | |
| | 1B) BOTH SHEETS ID-03 AND ID-11 SHOW THE STAGE GOING |
| | ALL THE WAY ACROSS THE FRONT OF THE THEATER. WHERE AS |
| | THE ARCHITECTURAL SHEET A-1.0 REVISION 15031217 SHOWS |
| | ON THE ONE SIDE OF THE STAGE AN AREA WHERE A PLATFORM |
| | LIFT IS TO BE INSTALLED AND ON THE OPPOSITE SIDE OF THE |
| | STAGE A DOOR THAT LEADS INTO THE CONCESSION AREA. AGAIN |
| | THE PLANS DO NOT CONFORM TO THE DESIGNER OF RECORDS |
| | PLANS ON FILE WITH THE CITY. THESE SHEETS NEED TO BE |
| | REVISED. |
| | |
| | 1C) SHEET ID-11 DOES NOT INDICATE THE LAYOUT OF THE |
| | SEATING NOR THE AISLES FOR EGRESS. THE OTHER ISSUE THE |
| | PLANS DO NOT PROVIDE A HANDRAILS ON EITHER SIDE OF THE |
| | EGRESS AISLES. PLEASE PROVIDE CODE COMPLIANCE WITH: |
| | 2010 FBC-B 1028.9.1 MINIMUM AISLE WIDTH. |
| | THE MINIMUM CLEAR WIDTH FOR AISLES SHALL BE AS SHOWN: |
| | 1. FORTY-EIGHT INCHES (1219 MM) FOR AISLE STAIRS HAVING |
| | SEATING ON EACH SIDE. |
| | EXCEPTION: THIRTY-SIX INCHES (914 MM) WHERE THE AISLE |
| | SERVES LESS |
| | THAN 50 SEATS. |
| | 2. THIRTY-SIX INCHES (914 MM) FOR AISLE STAIRS HAVING |
| | SEATING ON ONLY ONE SIDE. |
| | EXCEPTION: TWENTY-THREE INCHES (584 MM) BETWEEN AN |
| | AISLE STAIR HANDRAIL AND SEATING WHERE AN AISLE DOES |
| | NOT SERVE MORE THAN FIVE ROWS ON ONE SIDE. |
| | 3. TWENTY-THREE INCHES (584 MM) BETWEEN AN AISLE STAIR |
| | HANDRAIL OR GUARD AND SEATING WHERE THE AISLE IS |
| | SUBDIVIDED BY A HANDRAIL. |
| | 4. FORTY-TWO INCHES (1067 MM) FOR LEVEL OR RAMPED |
| | AISLES HAVING SEATING ON BOTH SIDES. |
| | |
| | 1D) SHEET ID-11, THE WALLS & CEILING APPEAR TO BE SET |
| | OUT TYPE OF CONSTRUCTION WITH FOAM AND FABRIC FINISHES |
| | PLEASE PROVIDE WHAT TYPE OF FRAME WORK AND BACKING |
| | MATERIAL CREATES THE BACKING FOR THE WALL PANELS, THIS |
| | HOLDS TRUE FOR THE FORMICA PANEL ASSEMBLY AS WELL. SHOW |
| | COMPLIANCE WITH: 2010 FBC-B 803.11.2 SET-OUT |
| | CONSTRUCTION. WHERE WALLS AND CEILINGS ARE REQUIRED TO |
| | BE OF FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE |
| | CONSTRUCTION AND WALLS ARE SET OUT OR CEILINGS ARE |
| | DROPPED DISTANCES GREATER THAN SPECIFIED IN SECTION |
| | 803.11.1, CLASS A FINISH MATERIALS( FLAME SPREAD INDEX |
| | 0-25; SMOKE DEVELOPMENT INDEX 0-450, ASTM E 84 OR UL |
| | 723), IN ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2, |
| | SHALL BE USED. |
| | EXCEPTIONS: |
| | 1. WHERE INTERIOR FINISH MATERIALS ARE PROTECTED ON |
| | BOTH SIDES BY AN AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2. |
| | 2. WHERE INTERIOR FINISH MATERIALS ARE ATTACHED TO |
| | NONCOMBUSTIBLE BACKING OR FURRING STRIPS INSTALLED AS |
| | SPECIFIED IN SECTION 803.11.1.1. |
| | |
| | THE POLYURETHANE FOAM SUBMITTED WAS NOT TESTED TO THE |
| | CORRECT STANDARD. |
| | |
| | 1E) 803.5 TEXTILE WALL COVERINGS. WHERE USED AS |
| | INTERIOR WALL FINISH MATERIALS, TEXTILE WALL COVERINGS, |
| | INCLUDING MATERIALS HAVING WOVEN OR NONWOVEN, NAPPED, |
| | TUFTED, LOOPED OR SIMILAR SURFACE AND CARPET AND |
| | SIMILAR TEXTILE MATERIALS, SHALL BE TESTED IN THE |
| | MANNER INTENDED FOR USE, USING THE PRODUCT MOUNTING |
| | SYSTEM, INCLUDING ADHESIVE, AND SHALL COMPLY WITH THE |
| | REQUIREMENTS OF SECTION 803.1.2, 803.1.3 OR 803.1.4. |
| | 803.1.2 ROOM CORNER TEST FOR INTERIOR WALL OR CEILING |
| | FINISH MATERIALS. |
| | INTERIOR WALL OR CEILING FINISH MATERIALS SHALL BE |
| | PERMITTED TO BE TESTED IN ACCORDANCE WITH NFPA 286. |
| | INTERIOR WALL OR CEILING FINISH MATERIALS TESTED IN |
| | ACCORDANCE WITH NFPA 286 SHALL COMPLY WITH SECTION |
| | 803.1.2.1. |
| | 803.1.3 ROOM CORNER TEST FOR TEXTILE WALL COVERINGS AND |
| | EXPANDED VINYL WALL COVERINGS. |
| | TEXTILE WALL COVERINGS AND EXPANDED VINYL WALL |
| | COVERINGS SHALL MEET THE CRITERIA OF SECTION 803.1.3.1 |
| | WHEN TESTED IN THE MANNER INTENDED FOR USE IN |
| | ACCORDANCE WITH THE METHOD B PROTOCOL OF NFPA 265 USING |
| | THE PRODUCT-MOUNTING SYSTEM, INCLUDING ADHESIVE. |
| | 803.1.4 ACCEPTANCE CRITERIA FOR TEXTILE AND EXPANDED |
| | VINYL WALL OR CEILING COVERINGS TESTED TO ASTM E 84 OR |
| | UL 723. |
| | TEXTILE WALL AND CEILING COVERINGS AND EXPANDED VINYL |
| | WALL AND CEILING COVERINGS SHALL HAVE A CLASS A FLAME |
| | SPREAD INDEX IN ACCORDANCE WITH ASTM E 84 OR UL 723 AND |
| | BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM INSTALLED |
| | IN ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2. TEST |
| | SPECIMEN PREPARATION AND MOUNTING SHALL BE IN |
| | ACCORDANCE WITH ASTM E 2404. |
| | |
| | 1F) 803.6 TEXTILE CEILING COVERINGS. WHERE USED AS |
| | INTERIOR CEILING FINISH MATERIALS, TEXTILE CEILING |
| | COVERINGS, INCLUDING MATERIALS HAVING WOVEN OR |
| | NONWOVEN, NAPPED, TUFTED, LOOPED OR SIMILAR SURFACE AND |
| | CARPET AND SIMILAR TEXTILE MATERIALS, SHALL BE TESTED |
| | IN THE MANNER INTENDED FOR USE, USING THE PRODUCT |
| | MOUNTING SYSTEM, INCLUDING ADHESIVE, AND SHALL COMPLY |
| | WITH THE REQUIREMENTS OF SECTION 803.1.2 OR 803.1.4. |
| | |
| | 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |