Plan Review Details - Permit 16061576
Plan Review Stops For Permit 16061576
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-25 Cont ID  
Sent By mvaldes Date 2016-07-25 Time 14:17 Rev Time 0.00
Received By mvaldes Date 2016-07-25 Time 13:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-30 Cont ID  
Sent By mvaldes Date 2016-06-30 Time 17:40 Rev Time 0.00
Received By mvaldes Date 2016-06-30 Time 17:10 Sent To  
Notes
2016-06-30 17:48:03REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - SINCE THE SERVICE IS BEING CHANGED SHOW AMPERE RATING
 OF METER ENCLOSURE, GROUNDING DETAIL TO INCLUDE
 ELECTRODE SIZING, CONDUIT AND SERVICE ENTRANCE
 CONDUCTOR SIZES. FBC 107 MINIMUM PLAN CRITEREA.
  
 - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED
  
 - THE GENERATOR SHALL HAVE A DISSCONNECT WITHIN SIGHT
 OR INTERGRATED. IF NOT THE GENERATOR DISCONNECTING
 MEANS SHALL BE LOCKABLE IN THE OPEN POSITION. NEC
 445.18

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2016-07-07 Cont ID  
Sent By tklarge Date 2016-07-07 Time 05:19 Rev Time 0.00
Received By tklarge Date 2016-07-07 Time 04:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-25 Cont ID  
Sent By mvaldes Date 2016-07-25 Time 14:17 Rev Time 0.00
Received By mvaldes Date 2016-07-22 Time 09:35 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-07 Cont ID  
Sent By tklarge Date 2016-07-07 Time 05:24 Rev Time 0.00
Received By tklarge Date 2016-06-29 Time 10:48 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-06-30 Cont ID  
Sent By tklarge Date 2016-07-07 Time 05:24 Rev Time 0.00
Received By njwira Date 2016-06-30 Time 13:54 Sent To E
Notes
***NONE***