Plan Review Details - Permit 16061557
Plan Review Stops For Permit 16061557
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-12 Cont ID  
Sent By ccole Date 2016-09-12 Time 07:25 Rev Time 0.00
Received By ccole Date 2016-09-08 Time 09:46 Sent To  
Notes
2016-09-09 09:47:01RESUB OF REVISION ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-30 Cont ID  
Sent By ccole Date 2016-06-30 Time 11:44 Rev Time 0.00
Received By ccole Date 2016-06-28 Time 10:18 Sent To  
Notes
2016-06-29 10:19:16CCOLE'S DESK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-09-12 Cont ID  
Sent By ccole Date 2016-09-12 Time 07:25 Rev Time 0.00
Received By ccole Date 2016-09-12 Time 07:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-30 Cont ID  
Sent By ccole Date 2016-06-30 Time 11:45 Rev Time 0.00
Received By ccole Date 2016-06-30 Time 11:45 Sent To  
Notes
2016-06-30 11:57:011ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16061557
 6/20/16
  
 1) PLEASE IDENTIFY ALL ROOMS ON THE PLANS.
  
 2) THERE APPEARS TO BE DUCT DROPS MISSING IN SOME OF
 THE FIRST FLOOR ROOMS.
  
 3) THE TRANSFER GRILLS ON THE SECOND FLOOR PLAN ARE
 UNDERSIZED PER SECTION M1602.4 FBC-14 RESIDENTIAL
 EXCEPTION (2): TRANSFER GRILLES SHALL USE 50 SQUARE
 INCHES (32 258 MM2) (OF GRILLE AREA) TO 100 CFM (OF
 SUPPLY AIR) FOR SIZING THROUGH-THE-WALL TRANSFER
 GRILLES AND USING AN UNRESTRICTED 1-INCH (25 MM)
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER RETURN AIR
 BALANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  