Plan Review Details - Permit 16061550
Plan Review Stops For Permit 16061550
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-08-10 Cont ID  
Sent By cthroop Date 2016-08-10 Time 09:07 Rev Time 0.00
Received By cthroop Date 2016-08-10 Time 08:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-05 Cont ID  
Sent By cthroop Date 2016-07-05 Time 08:33 Rev Time 0.00
Received By cthroop Date 2016-07-05 Time 08:33 Sent To  
Notes
2016-07-05 08:37:13BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 7/5/16
  
 1. PLANS DO NOT REFERENCE GOVERNING CODES.
 2. MECHANICAL, ELECTRICAL & FIRE PLAN REVIEW REQUIRED.
 3. VALUE APPEARS LOW.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY
 DELAY THE APPLICATION PROCESS.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-04 Cont ID  
Sent By mvaldes Date 2016-08-04 Time 11:23 Rev Time 0.00
Received By mvaldes Date 2016-08-04 Time 10:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-06 Cont ID  
Sent By mvaldes Date 2016-07-06 Time 16:06 Rev Time 0.00
Received By mvaldes Date 2016-07-06 Time 15:25 Sent To M
Notes
2016-07-06 16:15:45REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - NEC 406.12 TAMPER-RESISTANT RECEPTACLES IN DWELLING
 UNITS. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT,
 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER
 RESISTANT RECEPTACLES.
  
 - NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL.
  
 - NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
  
 - NEC 210.70(1) A LIGHTING OUTLET IS REQUIRED IN EVERY
 HABITABLE ROOM TO BE CONTROLLED BY AT LEAST 1 WALL
 SWITCH.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-08 Cont ID  
Sent By pleduc Date 2016-08-08 Time   Rev Time 0.00
Received By pleduc Date 2016-08-08 Time 16:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-07 Cont ID  
Sent By pleduc Date 2016-07-07 Time   Rev Time 0.00
Received By pleduc Date 2016-07-07 Time 13:45 Sent To PC
Notes
2016-07-07 13:58:27THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A1 - THERE ARE NOT CODE COMPLIANCE REFERNCES.
 PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE INDICATING:
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
  
  
 2) THE ENCLOSING OF THE DEN APPEARS TO BE CREATING
 ANOTHER BEDROOOM THAT SHALL MEET THE REQUIREMENTS OF
 THE FLORIDA FIRE PREVENTION CODE NFPA 1 & 101, 5TH
 EDITION. INCUDING THE REQUIREMENTS FOR FIRE ALARM
 AUDIBLILITY AND SMOKE DETECTION.
  
 PLEASE CORRECT OR PROVIDE JUSTIFICATION.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-12 Cont ID  
Sent By cpuell Date 2016-08-12 Time 09:11 Rev Time 0.00
Received By cpuell Date 2016-08-03 Time 15:23 Sent To  
Notes
2016-08-03 15:23:53B07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-07 Cont ID  
Sent By pleduc Date 2016-07-07 Time   Rev Time 0.00
Received By pleduc Date 2016-06-28 Time 16:01 Sent To  
Notes
2016-06-28 16:02:09BLDG - $5000

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-08-11 Cont ID  
Sent By jvalido Date 2016-08-11 Time 17:40 Rev Time 0.00
Received By jvalido Date 2016-08-11 Time 17:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-07-06 Cont ID  
Sent By jvalido Date 2016-07-06 Time 18:19 Rev Time 0.00
Received By jvalido Date 2016-07-06 Time 18:11 Sent To FIRE
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2016-07-05 Cont ID  
Sent By cthroop Date 2016-07-05 Time 15:25 Rev Time 0.00
Received By cthroop Date 2016-07-05 Time 15:25 Sent To  
Notes
2016-07-05 15:25:35PLUMBING REVIEW NOT REQUIRED.