Plan Review Details - Permit 16061484
Plan Review Stops For Permit 16061484
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-22 Cont ID  
Sent By albarran Date 2016-07-22 Time 08:24 Rev Time 0.00
Received By albarran Date 2016-07-22 Time 07:40 Sent To I
Notes
2016-07-22 08:29:19I SPOKE TO MIKE OF KASPER ELECTRIC TO DISCUSS THE FIRST
 LINE ITEM ON HIS PROPOSAL, THE GENERATOR WHICH WAS A
 QUESTION ON THE INITIAL REVIEW. THE GENERATOR HAS BEEN
 DELETED FROM THE PERMIT APPLICATION AND THEREFORE
 NOLONGER BEING CONSIDERED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-29 Cont ID  
Sent By albarran Date 2016-06-29 Time 13:11 Rev Time 0.00
Received By albarran Date 2016-06-29 Time 10:19 Sent To I
Notes
2016-06-29 13:13:441ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC
 SECTION 107.2.1 REQUIRES THAT ALL DRAWINGS SUBMITTED
 FOR PERMITTING INCLUDE THE PROPOSED SCOPE OF WORK,
 INCLUDE THE APPLICABLE CODE AND BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DRAWING.
 2. THESE SAME AMENDMENTS AS WELL AS THE NEC ON SECTION
 215.5 REQUIRE THAT YOU PROVIDE IN ADDITION TO THE RISER
 DIAGRAM LOAD CALCS.
 3. THE SUBMITTED PROPOSAL MENTIONS THE INSTALLATION OF
 A GENERATOR OUTLET TO POWER THE HOUSE. YOU SHALL
 PROVIDE MANUFACTURER SPEC SHEETS ON THE PROPOSED
 GENERATOR. IF THE GENERATOR IS NOT OF SUFFICIENT SIZE
 TO RUN THE WHOLE HOUSE, AN AUTOMATIC TRANSFER SWITCH IS
 NOT PERMITTED. ON A MANUALLY OPERATED SYSTEM SAFETY
 PRECAUTIONS HAVE TO BE MADE SO AS NOT TO INADVERTENTLY
 HAVE TO LINE SIDE OF THE SERVICE CONNECTED TO THE
 GENERATOR LOAD.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-22 Cont ID  
Sent By albarran Date 2016-07-22 Time 08:29 Rev Time 0.00
Received By albarran Date 2016-07-20 Time 10:51 Sent To  
Notes
2016-07-22 08:32:08ELECTRICAL REVIEW APPROVED AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. FILE SENT TO SMALL READY BIN "K".
 MA
2016-07-21 10:51:27RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-29 Cont ID  
Sent By albarran Date 2016-06-29 Time 13:13 Rev Time 0.00
Received By albarran Date 2016-06-27 Time 12:50 Sent To  
Notes
2016-06-29 13:14:566/29/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. FILE SENT TO SMALL DENIED BIN ''K".
 MA
2016-06-28 12:50:29ELEC <5K