| 2016-06-29 13:13:44 | 1ST ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | 1. CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC |
| | SECTION 107.2.1 REQUIRES THAT ALL DRAWINGS SUBMITTED |
| | FOR PERMITTING INCLUDE THE PROPOSED SCOPE OF WORK, |
| | INCLUDE THE APPLICABLE CODE AND BEAR THE NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DRAWING. |
| | 2. THESE SAME AMENDMENTS AS WELL AS THE NEC ON SECTION |
| | 215.5 REQUIRE THAT YOU PROVIDE IN ADDITION TO THE RISER |
| | DIAGRAM LOAD CALCS. |
| | 3. THE SUBMITTED PROPOSAL MENTIONS THE INSTALLATION OF |
| | A GENERATOR OUTLET TO POWER THE HOUSE. YOU SHALL |
| | PROVIDE MANUFACTURER SPEC SHEETS ON THE PROPOSED |
| | GENERATOR. IF THE GENERATOR IS NOT OF SUFFICIENT SIZE |
| | TO RUN THE WHOLE HOUSE, AN AUTOMATIC TRANSFER SWITCH IS |
| | NOT PERMITTED. ON A MANUALLY OPERATED SYSTEM SAFETY |
| | PRECAUTIONS HAVE TO BE MADE SO AS NOT TO INADVERTENTLY |
| | HAVE TO LINE SIDE OF THE SERVICE CONNECTED TO THE |
| | GENERATOR LOAD. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |