Plan Review Details - Permit 16061459
Plan Review Stops For Permit 16061459
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-06 Cont ID  
Sent By mvaldes Date 2016-07-06 Time 11:21 Rev Time 0.00
Received By mvaldes Date 2016-07-06 Time 11:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-29 Cont ID  
Sent By mvaldes Date 2016-06-29 Time 09:47 Rev Time 0.00
Received By mvaldes Date 2016-06-29 Time 09:32 Sent To  
Notes
2016-06-29 09:53:32REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - PROVIDE A NUETRAL LOAD CALCULATION IN ACCORDANCE TO
 NEC 220.61(A)(B)(C) TO VERIFY REDUCTION IN FEEDER WIRE
 SIZE.
  
 - KEEP IN MIND ELECTRICAL CONNECTION WITH DISSIMILIAR
 METALS SUCH AS ALUMINUM AND COPPER SHALL BE IDENTIFIED
 AND SUITABLE FOR THE USE PER NEC 110.14

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-06 Cont ID  
Sent By mvaldes Date 2016-07-06 Time 11:21 Rev Time 0.00
Received By mvaldes Date 2016-07-05 Time 11:22 Sent To  
Notes
2016-07-05 11:23:16RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-29 Cont ID  
Sent By mvaldes Date 2016-06-29 Time 09:53 Rev Time 0.00
Received By mvaldes Date 2016-06-27 Time 15:32 Sent To  
Notes
2016-06-27 15:32:25ELEC -$5000