Plan Review Details - Permit 16061412
Plan Review Stops For Permit 16061412
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-07-12 Cont ID  
Sent By tklarge Date 2016-07-12 Time 10:38 Rev Time 0.00
Received By tklarge Date 2016-07-12 Time 10:13 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-06-29 Cont ID  
Sent By tklarge Date 2016-06-29 Time 06:48 Rev Time 0.00
Received By tklarge Date 2016-06-29 Time 06:31 Sent To  
Notes
2016-06-29 06:48:511) SIZE THE RISER TO THE GRILL ON THE PLANS.
 2) SUBMIT TWO COPIES OF THE SIZING TABLE FOR THE COPPER
 PIPE OR REFERENCE THE TABLE ON BOTH SETS OF PLANS. IF
 YOU ARE USING TABLE 402.4 (9), A 1/2 INCH LINE CARRIES
 47,000 BTU'S. THE LINES ARE UNDERSIZED.
 3) THE APPLIANCE SPEC SHEETS DO NOT SHOW THAT THE
 APPLIANCES ARE LISTED AND LABELED PER FGC SEC.301.3.
 SUBMIT SPECIFICATIONS THAT SHOW THE APPLIANCES ARE
 LISTED AND LABELED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-12 Cont ID  
Sent By tklarge Date 2016-07-12 Time 10:38 Rev Time 0.00
Received By tklarge Date 2016-07-12 Time 10:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-29 Cont ID  
Sent By tklarge Date 2016-06-29 Time 06:49 Rev Time 0.00
Received By tklarge Date 2016-06-24 Time 14:59 Sent To  
Notes
2016-06-24 14:59:49ROUTED TO PLUMB <5K