Plan Review Details - Permit 16061407
Plan Review Stops For Permit 16061407
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-11 Cont ID  
Sent By albarran Date 2016-07-11 Time 16:22 Rev Time 0.00
Received By albarran Date 2016-07-11 Time 15:35 Sent To I
Notes
2016-07-11 16:23:56ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-27 Cont ID  
Sent By albarran Date 2016-06-27 Time 17:07 Rev Time 0.00
Received By albarran Date 2016-06-27 Time 16:37 Sent To I
Notes
2016-06-27 17:09:151ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. SCOPE OF WORK NOT CLEARLY DEFINED ON PLANS.
 2. CITY OF WEST PALM BEACH AMENDMENTS SECTION 107.2.1
 REQUIRES THAT IN ADDITION TO THE SCOPE OF WORK, ALL
 PLANS SHALL HAVE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 3. YOU SHALL INCLUDE ON THE PLANS THE TYPE OF
 CONDUCTORS PROPOSED
 4. YOU SHALL INDICATE HOW AND FROM WHERE WILL THE
 REMOTE POWER SUPPLY WILL BE POWERED AND MAKE NOTE OF
 COMPLIANCE TO SECTION 760 OF THE 2011 EDITION OF THE
 NEC.
 5. YOU SHALL INDICATE OR MAKE NOTE THAT THIS IS BEING
 DESIGNED TO COMPLY WITH THE 2010 EDITION OF NFPA 72
 6. HOW WILL THE REMOTE POWER SUPPLY BE CONNECTED TO THE
 EXISTING SYSTEM AND INCLUDE THAT INTO THE RISER
 DIAGRAM. THE RISER DIAGRAM AS SUBMITTED ONLY INDICATES
 THE NEW STROBES BUT FAILED TO INCLUDE THE FULL SCOPE OF
 WORK.
 7. YOU SHALL INCLUDE VOLTAGE DROP CALCULATIONS ON THE
 DRAWINGS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-07-11 Cont ID  
Sent By scaldero Date 2016-07-11 Time 10:23 Rev Time 0.00
Received By scaldero Date 2016-07-11 Time 10:23 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-06-27 Cont ID  
Sent By scaldero Date 2016-06-27 Time 11:00 Rev Time 0.00
Received By scaldero Date 2016-06-27 Time 10:59 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-11 Cont ID  
Sent By albarran Date 2016-07-11 Time 16:24 Rev Time 0.00
Received By albarran Date 2016-06-30 Time 14:47 Sent To  
Notes
2016-07-11 16:28:167/11/16 PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. FILE SENT TO SMALL READY BIN "A". MA
2016-06-30 14:47:53RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-27 Cont ID  
Sent By albarran Date 2016-06-27 Time 17:14 Rev Time 0.00
Received By albarran Date 2016-06-24 Time 09:37 Sent To  
Notes
2016-06-27 17:16:136/27/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. FILE SENT TO SMALL DENIED BIN "A".
 MA
2016-06-27 09:37:26ROUTED TO FIRE