| 2016-07-01 14:42:59 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE APPROVED PLANS WERE SIGNED AND SEALED BY A |
| | FLORIDA LICENSED ARCHITECT (MIGUEL F. SANCHEZ), WHO IS |
| | THE DESIGNER OF RECORD. THE REVISED PLANS NEED TO BE |
| | SIGNED AND SEALED BY THE ARCHITECT THAT IS THE DESIGNER |
| | OF RECORD. FS 481 THE OTHER OPTION IS TO HAVE THE NEW |
| | PLANS REVIEWED AND APPROVED BY THE ARCHITECT AND |
| | STAMPED WITH HIS SHOP DRAWING REVIEW STAMP. |
| | |
| | 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 3) THE PLANS THAT WERE SUBMITTED ARE MISSING |
| | INFORMATION, SUCH AS THE CONDENSER PAD AND ANCHORING |
| | INFORMATION. THE INFORMATION ON THE BATHROOM EXHAUST |
| | FANS MODEL AND CFMS IS MISSING. FBC 107.2.1, |
| | FBCR-M1301.1, FBCR-M1305.1.4.1 |
| | |
| | 4) THE TRANSFER DUCT AT THE MASTER BEDROOM SUITE IS |
| | REQUIRED TO BE 10" AND THE PLANS HAVE 9". ALL SUPPLY |
| | AIR INTO THE MASTER SUITE INCLUDING THE MASTER BATHROOM |
| | IS REQUIRED TO BE CONSIDERED FOR BALANCED RETURN AIR. |
| | FBCR-M1602.04 |
| | |
| | 5) SOME OF THE SUPPLY DROPS DO NOT HAVE THE CFMS |
| | SPECIFIED. FBC 107.2.1 |
| | |
| | 6) IT IS NOT CLEAR ON THE DRAWINGS HOW THE SUPPLY AIR |
| | TO THE FIRST FLOOR IS BEING ROUTED. THERE APPEARS TO BE |
| | A 16" X 10 " DISTRIBUTION BOX OFF THE AIR HANDLER WITH |
| | A 14" DIAMETER FLEX DUCT DOWN TO THE FIRST FLOOR. THE |
| | FIRST FLOOR PLANS DO NOT SHOW THE 14" DIA. SUPPLY FROM |
| | THE SECOND FLOOR AND THERE ARE TWO DISTRIBUTION BOXES |
| | THAT ARE NOT CONNECTED TO EACH OTHER SHOWN. THE |
| | DUCTWORK HAS A DARK SHADING ON THEM THAT MAKES IT |
| | ILLEGIBLE. FBC 107.2.1 |