Plan Review Details - Permit 16061369
Plan Review Stops For Permit 16061369
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-14 Cont ID  
Sent By shill Date 2016-07-14 Time 08:33 Rev Time 0.00
Received By shill Date 2016-07-14 Time 08:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-24 Cont ID  
Sent By shill Date 2016-06-24 Time 17:13 Rev Time 0.00
Received By shill Date 2016-06-24 Time 17:13 Sent To  
Notes
2016-06-24 17:20:37****CORRECTIONS****
 ***REVISED ON 7/13/16 TO INCLUDE SPECIFIC FBC107
 PROVISIONS, TEXT OF THE FBC107 CODE REFERENCES***
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THREE COMPLETE ORIGINAL SETS OF PLANS (PERMIT
 DOCUMENTS) REQUIRED, FBC 107.
  
 2. THE PRODUCT APPROVAL IS INCOMPLETE. PROVIDE THE
 PAGES OF THE PRODUCT APPROVAL APPLICABLE TO ALL
 SYSTEMS, FBC 1609. PAGES SPECIFIC TO ASSEMBLIES NOT
 APPLICABLE TO THE ONE SELECTED ARE NOT REQUIRED.
  
 3. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL, FBC 107.
  
 SEE FBC 107.1, 107.2.1.2, 107.2.1.4, 107.3.1, 107.3.4,
 107.3.4.2.
  
 107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH
 PERMIT APPLICATION.
  
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL
 ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING
 SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT
 BY AN ARCHITECT OR ENGINEER FOR THE
 SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.
  
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN
 ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM.
  
 107.3.1 APPROVAL OF CONSTRUCTION DOCUMENTS. WHEN THE
 BUILDING OFFICIAL ISSUES A PERMIT, THE
 CONSTRUCTION DOCUMENTS SHALL BE NOTED, IN WRITING OR BY
 STAMP, AS ?REVIEWED FOR CODE
 COMPLIANCE.? ONE SET OF CONSTRUCTION DOCUMENTS SO
 REVIEWED SHALL BE RETAINED BY THE BUILDING
 OFFICIAL. THE OTHER SET SHALL BE RETURNED TO THE
 APPLICANT, SHALL BE KEPT AT THE SITE OF WORK AND
 SHALL BE OPEN TO INSPECTION BY THE BUILDING OFFICIAL OR
 A DULY AUTHORIZED REPRESENTATIVE.
  
 107.3.4 . . . THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE
 SHALL BE RESPONSIBLE FOR REVIEWING AND COORDINATING
 SUBMITTAL DOCUMENTS PREPARED BY OTHERS, INCLUDING
 PHASED AND DEFERRED SUBMITTAL ITEMS,
 FOR COMPATIBILITY WITH THE DESIGN OF THE BUILDING.
 THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING
 BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE
 BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE
 DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL
 THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN APPROVED BY THE BUILDING OFFICIAL.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-14 Cont ID  
Sent By shill Date 2016-07-14 Time 08:33 Rev Time 0.00
Received By shill Date 2016-07-12 Time 09:22 Sent To  
Notes
2016-07-13 09:23:10RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-24 Cont ID  
Sent By shill Date 2016-06-24 Time 17:23 Rev Time 0.00
Received By shill Date 2016-06-23 Time 13:33 Sent To  
Notes
2016-06-24 13:33:09ROUTED TO SHILL