Plan Review Details - Permit 16061357
Plan Review Stops For Permit 16061357
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-08-08 Cont ID  
Sent By jwitmer Date 2016-08-08 Time 11:37 Rev Time 0.00
Received By jwitmer Date 2016-08-08 Time 09:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-07-22 Cont ID  
Sent By jwitmer Date 2016-07-22 Time 11:53 Rev Time 0.00
Received By jwitmer Date 2016-07-22 Time 09:56 Sent To  
Notes
2016-07-22 11:53:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16061357
 ADD: 400 N FLAGLER DR. SUITE # 706
 CONT: MARYJULE CONSTRUCTION INC.
 TEL: 561-386-6032
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JULY 22/2016
 ACTION: DENIED
  
 1-2) COMPLIED.WINDOWS AND DOORS TO BE COMPLETED UNDER A
 SEPARATE PERMIT.
  
 3) 2ND REQUEST. SHEET 1 NOTES INDICATE THE DEMO OF ALL
 FLOOR TILE AND REPLACEMENT WITH WOOD FLOORING AND SOUND
 UNDERLAYMENT OF WHISPERMAT CS. WHISPER MAT CS IS FOR
 TILE AND OR MARBLE FINISH FLOORS NOT WOOD FLOORS.
  
 PLEASE NOTE IN THE SALES BROCHURES FOR WHISPER MAT HW
 THEY SHOW A IIC RATING OF IIC RATING OF 55 WHEN TESTED
 ON A 8 INCH CONCRETE SLAB. NO TEST RESULT ARE SHOWN FOR
 A 6 INCH SLAB.
  
 SUBMITTED PRODUCT TESTING IS FOR WHISPER MAT CS FOR
 TILE FLOORING. PLEASE PROVIDE CODE COMPLIANCE WITH:
  
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 3A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-06 Cont ID  
Sent By jwitmer Date 2016-07-06 Time 06:28 Rev Time 0.00
Received By jwitmer Date 2016-07-06 Time 05:57 Sent To  
Notes
2016-07-06 06:13:34 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16061357
 ADD: 400 N FLAGLER DR. SUITE # 706
 CONT: MARYJULE CONSTRUCTION INC.
 TEL: 561-386-6032
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 06/2016
 ACTION: DENIED
  
 1) SHEET 1 INDICATES THE REPLACEMENT OF WINDOWS AND
 DOORS. THERE IS A NOTE THAT THE REPLACEMENT OF DOORS BY
 OTHERS. IN THIS SUBMITTAL THERE WAS NO PRODUCT
 APPROVALS FOR THE REPLACEMENT OF WINDOWS.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS/ MULLIONS
  
 2) MISSING THE WIND DESIGN CRITERIA. 2014 FBC-B
 1603.1.4 WIND DESIGN DATA. THE FOLLOWING INFORMATION
 RELATED TO WIND LOADS SHALL BE SHOWN, REGARDLESS OF
 WHETHER WIND LOADS GOVERN THE DESIGN OF THE LATERAL
 FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3) SHEET 1 NOTES INDICATE THE DEMO OF ALL FLOOR TILE
 AND REPLACEMENT WITH WOOD FLOORING AND SOUND
 UNDERLAYMENT OF WHISPERMAT HC-71. SUBMITTED PRODUCT
 TESTING IS FOR WHISPER MAT CS FOR TILE FLOORING. PLEASE
 PROVIDE CODE COMPLIANCE WITH:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 3A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-08-05 Cont ID  
Sent By albarran Date 2016-08-05 Time 09:32 Rev Time 0.00
Received By albarran Date 2016-08-05 Time 08:04 Sent To  
Notes
2016-08-05 09:34:10ELECTRICAL REVIEW APPROVED WITH NOTES ENTERED ON PLANS
 AS TO THE ELECTRICAL CODE TO FOLLOW, AS WELL AS THE
 FBC-R REQUIREMENT FOR HIGH EFFICIENCY LAMPS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-25 Cont ID  
Sent By albarran Date 2016-07-25 Time 14:02 Rev Time 0.00
Received By albarran Date 2016-07-25 Time 12:17 Sent To P
Notes
2016-07-25 14:03:22ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB NAME: CONDO RENOVATION
 JOB ADDRESS: 400 N. FLAGLER DR.
 DESCRIPTION: RENO OF CONDO AS INDICATED ON THE PERMIT
 APPLICATION
 MAST. PERMIT: 16061357
 REVISION:
  
 CONDITIONAL APPROVAL AS FOLLOWS:
  
 1. THE SCOPE OF THE ELECTRICAL UPGRADE IS NOT DEFINED
 ON THE SUBMITTED PLANS, THEREFORE THE CONDITIONAL
 APPROVAL HEREIN IS SUBJECTED TO THE APPROVAL OF THE
 FIELD INSPECTOR.
 2. THE OUTLET SPACING AS INDICATED ON THE SUBMITTED
 DRAWINGS DO NOT COMPLY WITH MINIMUM CODE REQUIREMENTS,
 THEREFORE ELECTRICAL CONTRACTOR SHALL PLACE OUTLETS AS
 REQUIRED BY CODE AND NOT LIMIT ITSELF TO THE MARKINGS
 ON THE PLANS.
 3. THE FBC-RE CODE REQUIRES THAT A MINIMUM OF 75% OF
 THE LAMPS IN PERMANENTLY INSTALLED FIXTURES BE OF THE
 HIGH-EFFICIENCY TYPE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-29 Cont ID  
Sent By albarran Date 2016-06-29 Time 17:03 Rev Time 0.00
Received By albarran Date 2016-06-29 Time 16:35 Sent To  
Notes
2016-06-29 17:05:191ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. CONTRARY TO THE MARKINGS ON THE SUBMITTED PLANS, ALL
 WORK SHALL BE MADE COMPLIANT TO THE 2011 EDITION OF THE
 NEC & THE 5TH EDITION OF THE FBC 2014 EDITION. NOT THE
 2010 FBC & 2008 NEC AS INDICATED.
 2. IN ADDITION TO THE LIGHTING PLAN YOU SHALL SUBMIT A
 POWER PLAN SHOWING THE PLACEMENT OF ALL RECEPTACLES
 EXISTING OR OTHERWISE. OUTLETS SHALL BE MARKED AS
 EXISTING, NEW OR EXISTING TO BE RELOCATED ETC.
 3. IN ADDITION TO THE PANEL SCHEDULE, YOU ARE TO SUBMIT
 LOAD CALCS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-07-21 Cont ID  
Sent By pleduc Date 2016-07-21 Time   Rev Time 0.00
Received By pleduc Date 2016-07-21 Time 15:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pleduc Date 2016-06-27 Time 15:06 Sent To  
Notes
2016-06-27 15:19:10THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO: COLLATED
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) SHEET 1 & 2 OF 2 -
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-08 Cont ID  
Sent By   Date 2016-08-08 Time   Rev Time 0.00
Received By lmarchan Date 2016-08-03 Time 09:17 Sent To  
Notes
2016-08-04 09:17:50B17

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-01 Cont ID  
Sent By tklarge Date 2016-08-01 Time 06:52 Rev Time 0.00
Received By tklarge Date 2016-07-20 Time 13:02 Sent To  
Notes
2016-07-20 13:02:54B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-06 Cont ID  
Sent By   Date 2016-07-06 Time 06:08 Rev Time 0.00
Received By lmarchan Date 2016-06-23 Time 12:39 Sent To  
Notes
2016-06-24 12:39:28B01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-08-08 Cont ID  
Sent By jwitmer Date 2016-07-06 Time 06:27 Rev Time  
Received By jwitmer Date 2016-07-06 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-08-05 Cont ID  
Sent By ccole Date 2016-08-05 Time 16:34 Rev Time 0.00
Received By ccole Date 2016-08-05 Time 16:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-07-26 Cont ID  
Sent By ccole Date 2016-07-26 Time 12:35 Rev Time 0.00
Received By ccole Date 2016-07-26 Time 12:32 Sent To  
Notes
2016-07-26 12:43:252ND REVIEW MECHANICAL
 PERMIT #16061357
 7/26/16
  
 1) SHEET 2: THE PLAN IS INDICATING 1850 CFMS OF SUPPLY
 AIR FOR THE EXISTING 4-TON SYSTEM. PLEASE SUBMIT A
 MANUFACTURER'S DATA SHEET FOR THE SYSTEM INDICATING
 MAXIMUM CFMS OF SUPPLY AIR.
  
 2) SHEET 2: THE PLAN DOES NOT CLEARLY INDICATE A MEANS
 OF RETURN AIR TO THE AIR HANDLER- NEITHER A DOOR OR
 RETURN AIR GRILL ARE SHOWN AT THE MECHANICAL CLOSET.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-28 Cont ID  
Sent By ccole Date 2016-06-28 Time 10:46 Rev Time 0.00
Received By ccole Date 2016-06-28 Time 10:46 Sent To  
Notes
2016-06-28 11:05:321ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16061357
 6/28/16
  
 1) REFER TO SECTION 107.2.1 WPB AMENDMENTS TO THE FBC
 AND PROVIDE PLANS WITH CLEARER PRINT- SOME OF THE
 MEASUREMENTS AND NOTES ARE BARELY LEGIBLE.
  
 2) PROVIDE A SCOPE OF WORK OUTLINE ON THE PLAN FOR
 MECHANICAL ALTERATIONS- THE PLAN DOES NOT INDICATE
 WHICH DUCTS ARE EXISTING, REPLACED, OR RELOCATED.
 SIMPLE SYMBOLS SUCH AS (E) EXISTING, (N) NEW, OR (RE)
 RELOCATED WOULD BE HELPFUL.
  
 3) PROVIDE AN AIR DEVICE SCHEDULE LISTING THE MAKES AND
 MODELS OF THE DIFFUSERS AND GRILLS. PLEASE NOTE THAT
 THE 48-2 DIFFUSER SUPPLING 260 CFM'S TO THE BEDROOM IS
 UNDERSIZED.
  
 4) INDICATE THE MAKE AND MODEL OF THE EXISTING AC
 SYSTEM AND IT'S HEATING AND COOLING CAPACITY.
  
 5) THE AIR HANDLER CLOSET DOOR WHICH IS SPECIFIED AS A
 WOOD LOUVERED DOOR SHALL BE NON-COMBUSTIBLE PER SECTION
 C403.2.7.2 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-08-05 Cont ID  
Sent By tklarge Date 2016-08-05 Time 05:45 Rev Time 0.00
Received By tklarge Date 2016-08-05 Time 05:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-08-01 Cont ID  
Sent By tklarge Date 2016-08-01 Time 06:52 Rev Time 0.00
Received By tklarge Date 2016-08-01 Time 06:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-28 Cont ID  
Sent By gjohnson Date 2016-06-28 Time 17:03 Rev Time 0.00
Received By gjohnson Date 2016-06-28 Time 17:03 Sent To  
Notes
2016-06-28 17:16:101ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. PLAN SHALL SHOW WORK TO COMPLY WITH FBC 2014 5TH
 EDITION.
  
 2. PLEASE CLARIFY ARE ALL FIXTURES BEING REMOVED AND
 BEING REPLACED IN SAME LOCATION EXCEPT BIDET,SHOWER IN
 POWDER ROOM AND KITCHEN SINK. PER WPB AMEND. TP FBC
 107.2.1
  
 3. PLANS ARE TO LITE TO BE SCANNED PLANS SHALL COMPLY
 WITH. WPB AMEND. TO FBC 107.2.1.4 QUALITY OF BUILDING
 PLANS. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN
 ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF
 FLORIDA STATUTES.

Review Stop Z ZONING
Rev No 2 Status P Date 2016-07-22 Cont ID  
Sent By ajones Date 2016-07-22 Time 13:52 Rev Time 0.00
Received By ajones Date 2016-07-22 Time 13:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-06-30 Cont ID  
Sent By ajones Date 2016-06-30 Time 10:48 Rev Time 0.00
Received By ajones Date 2016-06-30 Time 10:48 Sent To  
Notes
***NONE***