Plan Review Details - Permit 16061287
Plan Review Stops For Permit 16061287
Review Stop E ELECTRICAL
Rev No 1 Status N Date 2016-08-04 Cont ID  
Sent By albarran Date 2016-07-19 Time 08:34 Rev Time 0.00
Received By albarran Date 2016-07-19 Time 08:19 Sent To FIRE
Notes
2016-08-04 14:03:24PER DK ELECTRICAL PLANS ARE A PART OF THE MASTER SET.
2016-07-19 08:40:57ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
 JOB NAME: KFC
 JOB ADDRESS: 4720 BROADWAY
 DESCRIPTION: INSTALL HOOD EXHAUST & SUPPLY PER PLANS
 MAST. PERMIT: 15010897
 REVISION: 16061287
  
  
 1. YOU ARE REFERRING TO THE ABOVE MENTIONED MASTER
 PERMIT FOR APPROVAL AND COMPARISON, BUT THE SUBMITTED
 EXHAUST AND SUPPLY (MAKE UP AIR) IS NOT SIMILAR AS ON
 THE PREVIOUSLY APPROVED DRAWING. THEREFORE AN
 ELECTRICAL PERMIT APPLICATION ACCOMPANIED BY SIGNED AND
 SEALED DRAWINGS REFLECTING THE PROPOSED WORK SHALL BE
 PROVIDED. THE DIAGRAM SHALL INCLUDE MOTOR LOAD CALCS,
 PANEL SCHEDULE AND SINGLE LINE WIRING DIAGRAM INCLUDING
 LIGHTING.
 2. IF THE SYSTEM IS TO BE TIED INTO AN EXISTING FIRE
 ALARM SYSTEM, A SEPARATE FIRE ALARM PERMIT SHALL BE
 SECURED.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-04 Cont ID  
Sent By albarran Date 2016-08-04 Time 14:03 Rev Time 0.00
Received By wjolin Date 2016-08-04 Time 12:25 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-21 Cont ID  
Sent By J.Walker Date 2016-07-21 Time   Rev Time 0.20
Received By   Date 2016-07-21 Time   Sent To M
Notes
2016-07-21 16:38:22PENDING MECHANICAL AND ELECTRICAL APPROVAL.
 WILL REQUIRE SUPPRESSION DRAWINGS AND SPECS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-04 Cont ID  
Sent By hmoser Date 2016-08-04 Time 14:04 Rev Time 0.00
Received By hmoser Date 2016-08-04 Time 12:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-25 Cont ID  
Sent By scaldero Date 2016-07-25 Time 11:39 Rev Time 0.00
Received By scaldero Date 2016-07-15 Time 13:17 Sent To  
Notes
2016-07-15 13:18:10ROUTED TO JORGE VALIDO'S DESK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-08-04 Cont ID  
Sent By hmoser Date 2016-08-04 Time 09:28 Rev Time 0.00
Received By hmoser Date 2016-08-04 Time 09:28 Sent To FIRE
Notes
2016-08-04 09:33:33PASS PROVISO
 1) PROVIDE A DETAIL FROM THE ENGINEER
 ON EXHAUST FAN TO CURB TIEDOWN
 PER SECTION 301.15 WIND RESISTANCE
 2014 FBC (M) FOR FINAL INSPECTION
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-18 Cont ID  
Sent By jvalido Date 2016-07-18 Time 14:57 Rev Time 0.00
Received By jvalido Date 2016-07-18 Time 14:41 Sent To  
Notes
2016-07-18 14:53:26CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE A SIGNED AND SEALED SET OF PLANS.
 (2) PROVIDE EQUIPMENT TIE DOWN SCHEDULE. (AS PER THE
 MECHANICAL CODE FBC 2014).
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 (3) PROVIDE A SIGNED CONTRACT WITH THE ENTIRE SCOPE OF
 WORK INCLUDED AS PER 109.3. (SEE ABOVE).
  
 FIRE SUPPRESSION SYSTEM REQUIRES A SEPERATE SET OF
 PLANS AND MUST BE INSTALLED BY A LICENSED FIRE
 SUPPRESSION CONTRACTOR.
  
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  