Plan Review Details - Permit 16061261
Plan Review Stops For Permit 16061261
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-07-01 Cont ID  
Sent By cthroop Date 2016-07-01 Time 12:13 Rev Time 0.00
Received By cthroop Date 2016-07-01 Time 12:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-06-30 Cont ID  
Sent By mvaldes Date 2016-06-30 Time 17:00 Rev Time 0.00
Received By mvaldes Date 2016-06-30 Time 16:20 Sent To B
Notes
2016-06-30 17:03:17REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - WATER SKIMMER DEVICE MUST COMPLY WITH NEC 680.26(C)
 POOL WATER BONDING. ( RED LINED ON PLANS )
  
 AN INTENTIONAL BOND OF A MINIMUM CONDUCTIVE SURFACE
 AREA OF 5800 MM2 (9 IN.2) SHALL BE INSTALLED IN CONTACT
 WITH THE POOL WATER.
 THIS BOND SHALL BE PERMITTED TO CONSIST OF PARTS THAT
 ARE REQUIRED TO BE BONDED IN 680.26(B).

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-06-30 Cont ID  
Sent By tklarge Date 2016-06-30 Time 05:35 Rev Time 0.00
Received By tklarge Date 2016-06-30 Time 05:35 Sent To  
Notes
2016-06-30 05:36:45GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-01 Cont ID  
Sent By cthroop Date 2016-07-01 Time 12:13 Rev Time 0.00
Received By cthroop Date 2016-06-22 Time 13:40 Sent To  
Notes
2016-06-22 13:40:41ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-06-30 Cont ID  
Sent By njwira Date 2016-06-30 Time 05:34 Rev Time 0.00
Received By tklarge Date 2016-06-30 Time 05:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-06-23 Cont ID  
Sent By njwira Date 2016-06-23 Time 13:12 Rev Time 0.00
Received By njwira Date 2016-06-23 Time 13:12 Sent To P
Notes
2016-06-23 13:13:246/23/16- PASSED
  
 1. POOL EQUIPMENT MEETS SETBACK REQUIREMENTS 4FT. FROM
 THE SIDE PROPERTY LINE.
 2. POOL SIDE SETBACK IS 33FT. AND 30FT. MEETING THE
 5FT. SETBACK REQUIREMENT.
 3. POOL REAR SETBACK IS 5FT. POOL ACTUAL SETBAK IS
 23FT. MEETING THIS REQUIREMENT.
  
 NATHAN WIRA