Plan Review Details - Permit 16061253
Plan Review Stops For Permit 16061253
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-06-25 Cont ID  
Sent By vperez Date 2016-06-25 Time 08:48 Rev Time 0.00
Received By vperez Date 2016-06-25 Time 08:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-06-24 Cont ID  
Sent By pleduc Date 2016-06-24 Time   Rev Time 0.00
Received By pleduc Date 2016-06-24 Time 14:07 Sent To E
Notes
2016-06-24 14:18:27THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) SHEET 1 OF 4 - PER NFPA 72, CONFIRM AND VERIFY 75DB
 AT THE PILLOW.
  
 18.4.5 SLEEPING AREA REQUIREMENTS.
 18.4.5.1* WHERE AUDIBLE APPLIANCES ARE INSTALLED TO
 PROVIDE SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A
 SOUND LEVEL OF AT LEAST 15 DB ABOVE THE AVERAGE AMBIENT
 SOUND LEVEL OR 5 DB ABOVE THE MAXIMUM SOUND LEVEL
 HAVING A DURATION OF AT LEAST 60 SECONDS OR A SOUND
 LEVEL OF AT LEAST 75 DBA, WHICHEVER IS GREATER,
 MEASURED AT THE PILLOW LEVEL IN THE AREA REQUIRED TO BE
 SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA).
  
 18.4.5.2 IF ANY BARRIER, SUCH AS A DOOR, CURTAIN, OR
 RETRACTABLE PARTITION, IS LOCATED BETWEEN THE
 NOTIFICATION APPLIANCE AND THE PILLOW, THE SOUND
 PRESSURE LEVEL SHALL BE MEASURED WITH THE BARRIER
 PLACED BETWEEN THE APPLIANCE AND THE PILLOW.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-25 Cont ID  
Sent By vperez Date 2016-06-25 Time 08:48 Rev Time 0.00
Received By vperez Date 2016-06-25 Time 08:48 Sent To  
Notes
2016-06-22 11:15:50ROUTED TO FIRE