Plan Review Details - Permit 16061232
Plan Review Stops For Permit 16061232
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-06-29 Cont ID  
Sent By   Date 2016-06-29 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2016-06-29 Time 05:58 Sent To  
Notes
2016-06-29 06:18:26BUILDING PROVISO:
 2014 FBC-ACCESSIBILITY CODE 703.2 RAISED CHARACTERS.
 RAISED CHARACTERS SHALL COMPLY WITH 703.2 AND SHALL BE
 DUPLICATED IN BRAILLE COMPLYING WITH 703.3. RAISED
 CHARACTERS SHALL BE INSTALLED IN ACCORDANCE WITH 703.4.
 703.4 INSTALLATION HEIGHT AND LOCATION. SIGNS WITH
 TACTILE CHARACTERS SHALL COMPLY WITH 703.4.
  
 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND.
 TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES
 (1220 MM) MINIMUM ABOVE THE FINISH FLOOR OR GROUND
 SURFACE, MEASURED FROM THE BASELINE OF THE LOWEST
 TACTILE CHARACTER AND 60 INCHES (1525 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-09-02 Cont ID  
Sent By vperez Date 2016-09-02 Time 14:52 Rev Time 0.00
Received By vperez Date 2016-09-02 Time 14:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-12 Cont ID  
Sent By vperez Date 2016-08-12 Time 10:44 Rev Time 0.00
Received By vperez Date 2016-08-12 Time 11:09 Sent To  
Notes
2016-08-12 11:08:24PROVISO- APPROVED PENDING BELOW:
  
 NEED 1 MORE COPY OF NEW ELECTRICAL SHEET AND NEED TO
 REMOVE VOID SHEET AND INSERT NEW ONE
  
 VAL PEREZ
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-05 Cont ID  
Sent By vperez Date 2016-07-05 Time 08:45 Rev Time 0.00
Received By vperez Date 2016-07-02 Time 12:05 Sent To  
Notes
2016-07-05 08:54:21INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. UPDATE ALL CODE REFERENCES SHOWN ON SHEET E.01 TO
 SHOW FLORIDA BUILDING CODE 2014 5TH EDITION AND AS
 STATED ABOVE.
 2. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR GENERATOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE, PHONE
 AND DATA, SIGNAGE ETC. A NOTE WILL SUFFICE.
 3. PLEASE LABEL RECEPTACLE IN TO BE GFCI PROTECTED PER
 NEC 210.8B5- IF WITHIN 6FT OF SINK ALL TO BE GFCI.
 4. PLEASE LABEL RECEPTACLE IN PREP AREA ALL TO BE GFCI
 PROTECTED PER NEC 210.8B5- IF WITHIN 6FT OF SINK, ALL
 TO BE GFCI.
 5. ADDRESS FIRE AND MECHANICAL COMMENTS RELATED TO THE
 ELECTRICAL SCOPE OF WORK.
 6. PROVIDE MANUFACTURED DATA SHEETS FOR THE NEW
 TANKLESS WATER HEATER SHOWN. FBC 107.3.5. ALSO SHOW ON
 ELECTRICAL PANEL SCHEDULE CALCULATION.
 7. ALL NEW DEVICES TO REFLECT CIRCUIT DESIGNATIONS ID.
 FBC 107.3.5
 8. NOTE SHOWN IS MISLEADING, STATES THAT NO NEW WORK IS
 BEING PERFORMED BUT NEW DEVICES SHOWN. PLEASE CORRELATE
 NOTES.
 9. FURTHER COMMENTS MAY FOLLOW. PLEASE FEEL FREE TO
 CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING THIS
 PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-06-23 Cont ID  
Sent By wjolin Date 2016-06-23 Time 13:04 Rev Time 0.00
Received By wjolin Date 2016-06-23 Time 12:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-09-09 Cont ID  
Sent By ccole Date 2016-09-09 Time 16:12 Rev Time 0.00
Received By ccole Date 2016-09-08 Time 09:37 Sent To  
Notes
2016-09-09 09:37:48RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status F Date 2016-09-07 Cont ID  
Sent By ccole Date 2016-09-07 Time 14:26 Rev Time 0.00
Received By ccole Date 2016-08-26 Time 11:12 Sent To  
Notes
2016-08-29 11:12:39B31

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-23 Cont ID  
Sent By gjohnson Date 2016-08-23 Time 16:01 Rev Time 0.00
Received By gjohnson Date 2016-08-08 Time 15:28 Sent To  
Notes
2016-08-08 15:29:03B32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-05 Cont ID  
Sent By gjohnson Date 2016-07-05 Time 15:41 Rev Time 0.00
Received By gjohnson Date 2016-06-21 Time 10:10 Sent To  
Notes
2016-06-22 10:10:54B07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-06-29 Cont ID  
Sent By jwitmer Date 2016-06-29 Time 06:06 Rev Time 0.00
Received By jwitmer Date 2016-06-29 Time 06:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-09-09 Cont ID  
Sent By ccole Date 2016-09-09 Time 16:12 Rev Time 0.00
Received By ccole Date 2016-09-09 Time 16:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-09-07 Cont ID  
Sent By ccole Date 2016-09-07 Time 14:01 Rev Time 0.00
Received By ccole Date 2016-09-07 Time 14:01 Sent To  
Notes
2016-09-07 14:26:023RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16061232
 9/7/16
  
 1) THE REVISED ENERGYGAUGE COMPLIANCE SUBMITTAL LISTS
 DATA FOR TWO 4-TON AC SYSTEMS AT 16 AND 15 SEER,
 HOWEVER THE REVISED HVAC PLAN INDICATES A 3-TON SYSTEM
 AT 11.8 EER. PLEASE CORRECT AND NOTE THAT THE
 OWNER/AGENT SHALL PROVIDE HIS/HER SIGNATURE AND DATE ON
 THE CERTIFICATIONS PAGE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-08-16 Cont ID  
Sent By ccole Date 2016-08-16 Time 13:54 Rev Time 0.00
Received By ccole Date 2016-08-16 Time 13:54 Sent To P
Notes
2016-08-16 14:14:012ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16061232
 8/16/16
  
 1) 2ND REQUEST FOR MINIMUM VENTILATION CALCULATIONS-
 SEE COMMENT #1 FROM THE 1ST REVIEW.
  
 2) THE ENERGYGAUGE CALCULATION SUBMITTAL IS A REDUCED
 SIZE COPY, ALL ENERGY COMPLIANCE DOCUMENTS TO BE
 SUBMITTED SHALL BE ORIGINAL COPIES, AND SHALL BEAR THE
 ORIGINAL SIGNATURES AND REGISTRATION NUMBERS OF THE
 DESIGN PROFESSIONALS- SECTION C103.1.1.1.2 FBC-14
 ENERGY CONSERVATION. ADDITIONALLY, THE BUILDING'S
 OWNER, THE OWNER'S ARCHITECT, OR THE OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER SHALL CERTIFY
 THAT THE BUILDING IS IN COMPLIANCE BY PROVIDING
 SIGNATURES- C103.1.1.2.
  
 3) THE SUBMITTED HVAC LOAD ANALYSIS PREPARED BY KO
 DESIGN IS FOR DULCE PECATTO INC. 2523 DUDLEY DR. IS NOT
 FOR THIS PROPOSED PROJECT AT 4047 OKEECHOBEE RD. PLEASE
 NOTE THAT ONLY THE DESIGN PROFESSIONAL OF RECORD OR THE
 INSTALLING AC CONTRACTOR IS PERMITTED TO DESIGN AC
 PLANS AND SPECIFICATIONS PER SECTION 105.3.1.2 FBC-14
 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-24 Cont ID  
Sent By ccole Date 2016-06-24 Time 12:08 Rev Time 0.00
Received By ccole Date 2016-06-24 Time 12:08 Sent To  
Notes
2016-06-24 12:15:241ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16061232
 6/24/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE:
  
 A) MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND
 SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
  
 B) AC COOLING AND HEATING CALCULATIONS. BECAUSE OF THE
 CHANGE IN USE OF THE SPACE RESULTING IN AN INCREASED
 OCCUPANT LOAD, AND THE ADDITION OF HEAT PRODUCING
 APPLIANCES AND EQUIPMENT, IT NEEDS TO BE VERIFIED THAT
 THE EXISTING AC SYSTEM HAS THE CAPACITY TO HANDLE THE
 INCREASED LOADS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-09-06 Cont ID  
Sent By gjohnson Date 2016-09-06 Time 09:19 Rev Time 0.00
Received By gjohnson Date 2016-09-06 Time 09:19 Sent To  
Notes
2016-09-06 09:30:34PLUMBING PROVISO
 1. PROVIDE MANUFACTURE INSTALLATION GUIDE FOR GREASE
 INTERCEPTOR. REQUIRED FOR FINAL INSPECTION. PER WPB
 AMEND TO FBC 107.2.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-08-23 Cont ID  
Sent By gjohnson Date 2016-08-23 Time 15:59 Rev Time 0.00
Received By gjohnson Date 2016-08-23 Time 15:59 Sent To  
Notes
2016-08-23 16:00:352NDT REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS: 2ND REQUEST
  
 1. A GREASE INTERCEPTOR IS REQUIRED FOR 3 COMP SINK AND
 MOP SINK. PER FBC PL SEC. 1003.3.1
 2. THE 3 COMP SINK SHALL DRAIN INDIRECTLY INTO SANITARY
 SYSTEM. FBC PL SEC. 802.1.8 FOOD UTENSILS, DISHES, POTS
 AND PANS SINKS.
 SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF
 UTENSILS, DISHES, POTS, PANS OR SERVICE WARE USED IN
 THE PREPARATION, SERVING OR EATING OF FOOD SHALL
 DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK
 TO THE DRAINAGE SYSTEM.

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-07-05 Cont ID  
Sent By gjohnson Date 2016-07-05 Time 15:26 Rev Time 0.00
Received By gjohnson Date 2016-07-05 Time 15:26 Sent To  
Notes
2016-07-05 15:41:231ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
 1. A GREASE INTERCEPTOR IS REQUIRED FOR 3 COMP SINK AND
 MOP SINK. PER FBC PL SEC. 1003.3.1
 2. THE 3 COMP SINK SHALL DRAIN INDIRECTLY INTO SANITARY
 SYSTEM. FBC PL SEC. 802.1.8 FOOD UTENSILS, DISHES, POTS
 AND PANS SINKS.
 SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF
 UTENSILS, DISHES, POTS, PANS OR SERVICE WARE USED IN
 THE PREPARATION, SERVING OR EATING OF FOOD SHALL
 DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK
 TO THE DRAINAGE SYSTEM.

Review Stop Z ZONING
Rev No 1 Status P Date 2016-08-12 Cont ID  
Sent By eschneid Date 2016-08-12 Time 14:57 Rev Time 0.25
Received By eschneid Date 2016-08-12 Time 14:57 Sent To  
Notes
***NONE***