| 2016-06-22 07:22:13 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16061204 | | | 6/22/16 | | | | | | 1) PROVIDE THE WIND LOAD DESIGN CRITERIA PER SECTION | | | 301.15 MECHANICAL, AND SECTION 1609 FBC-14: | | | | | | WIND DESIGN CRITERIA | | | 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- | | | CHAPTER 6 OF ASCE 7-10. | | | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C | | | 1609.3 WIND SPEED CONVERSION | | | A) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN | | | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 | | | B) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. | | | C) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN | | | ACCORDANCE WITH 1609.4 & ASCE 7-10 | | | D) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * | | | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. | | | E) COMPONENTS & CLADDING PRESSURES POSITIVE & NEGATIVE | | | TABLE 1609.2(2). | | | | | | 2) REFER TO SECTION 1522.3.1 AND PROVIDE THE CLEARANCE | | | DISTANCE HEIGHT FROM THE FINISHED ROOF SURFACE TO THE | | | BOTTOM OF THE SUPPORT BEAM- SEE TABLE 1522.3. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |