Plan Review Details - Permit 16061069
Plan Review Stops For Permit 16061069
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-07 Cont ID  
Sent By mvaldes Date 2016-07-07 Time 17:35 Rev Time 0.00
Received By mvaldes Date 2016-07-07 Time 17:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-20 Cont ID  
Sent By mvaldes Date 2016-06-20 Time 13:26 Rev Time 0.00
Received By mvaldes Date 2016-06-20 Time 13:15 Sent To  
Notes
2016-06-20 13:25:57REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - PROVIDE THE EXISTING RISER DIAGRAM SHOWING RACEWAY,
 CONDUCTOR, AND BREAKER SIZES. IN ADDITION SHOW A SITE
 SPECIFIC FLOOR PLAN INDICATING THE SUB PANEL LOCATION
 INSIDE THE UNITS. FBC 107 INSUFFICIENT DOCUMENTS.
  
 - SMOKE ALARMS ARE REQUIRED PER RESIDENTIAL CODE
 SECTIONS 314 & 315 INCLUDE LOCATION ON PLANS.
  
 - PANEL SCHEDULE SHALL INCLUDE THE AIC RATING OF
 EQUIPMENT PER NEC 110.9 AND 110.10.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-07 Cont ID  
Sent By mvaldes Date 2016-07-07 Time 17:35 Rev Time 0.00
Received By mvaldes Date 2016-06-24 Time 15:42 Sent To  
Notes
2016-07-07 15:42:31RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-20 Cont ID  
Sent By mvaldes Date 2016-06-20 Time 13:26 Rev Time 0.00
Received By mvaldes Date 2016-06-17 Time 10:09 Sent To  
Notes
2016-06-20 10:09:33ROUTED TO ELECTRICAL INBOX