Plan Review Details - Permit 16061017
Plan Review Stops For Permit 16061017
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-03 Cont ID  
Sent By rmcdouga Date 2016-08-03 Time 15:19 Rev Time 0.00
Received By rmcdouga Date 2016-08-03 Time 10:40 Sent To  
Notes
2016-08-03 10:47:51PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC.
 THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE
 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT
 DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC
 FIFTH EDITION.
  
 2) THE 2014 FBC REFERENCES ASCE 7-10 AND 2010 NFPA-72.
 PLEASE UPDATE.
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE 8' X
 7' OVER HEAD SECTIONAL GARAGE DOORS AND THE 3' X 7'
 OUTSWING DOOR.
  
 4) THE NOA THAT FOR THE GAF ROOL ROOFING (NOA
 NO.15-0707.10) IS MISSING PAGES, IS FOR USE AS AN
 UNDERLAYMENT AND IS DESIGNED FOR ROOFS HAVING A MINIMUM
 SLOPE OF 2:12. SUBMIT TWO SETS OF PRODUCT APPROVALS FOR
 A ROOF COVERING FOR ROOFS WITH A 1/4" PER FOOT SLOPE
 THAT HAS DESIGN PRESSURES THAT MEET THE UPLIFT
 REQUIREMENTS FOR EXPOSURE C WITH A 170 MPH VULT
 WINDSPEED. SUBMIT SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING FOR PERIMETER AND
 CORNER ROOF AREAS IF REQUIRED. FBC R301.2.1
  
 5) SPECIFY THE SLOPE OF THE GARAGE ROOF ON THE PLANS.
 FBC 107.2.1
  
 6) SHOW COMPLIANCE WITH FBC R309.1 THE AREA OF FLOOR
 USED FOR PARKING OF AUTOMOBILES OR OTHER VEHICLES SHALL
 BE SLOPED TO FACILITATE THE MOVEMENT OF LIQUIDS TO A
 DRAIN OR TOWARD THE MAIN VEHICLE ENTRY DOORWAY.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-08 Cont ID  
Sent By vperez Date 2016-07-08 Time 08:46 Rev Time 0.00
Received By vperez Date 2016-07-08 Time 08:46 Sent To  
Notes
2016-07-08 08:47:14INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE UPDATE ALL CODE REFERENCES TO REFLECT ABOVE
 STATED STANDARDS.
 2. LABEL NEW RECEPTACLE AT GARAGE TO GFCI PROTECTED
 E3902.6
 3. SHOW AND PROVIDE A COMPLETE ELECTRICAL LOAD
 CALCULATION REFLECTING ALL NEW LOADS. FBC 107.3.5
 4. THE STRUCTURE SHOWN IS A DETACHED GARAGE WHICH WILL
 REQUIRE A PANELBOARDS AT THE GARAGE LOCATION PER NEC
 225.30.
 5. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2016-06-21 Cont ID  
Sent By fmittner Date 2016-06-21 Time 15:12 Rev Time 0.00
Received By fmittner Date 2016-06-21 Time 15:12 Sent To  
Notes
2016-06-21 15:14:40PER HPB 11-16, THE WROUGHT IRON SUPPORTS ARE REQUIRED
 TO BE RETAINED. THIS PLAN DOES NOT INDICATE SUCH.
 PLEASE REVISE AND SHOW ELEVATION OF PRIMARY STRUCTURE
 WITH NEW FRONT ENTRY AND RETAINTION OF ORIGINAL
 SUPPORTS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-03 Cont ID  
Sent By rmcdouga Date 2016-08-03 Time 15:20 Rev Time 0.00
Received By rmcdouga Date 2016-06-16 Time 11:05 Sent To  
Notes
2016-07-05 14:07:32R05
2016-06-17 11:07:15LIBRARY

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-08-03 Cont ID  
Sent By rmcdouga Date 2016-08-03 Time 10:25 Rev Time 0.00
Received By rmcdouga Date 2016-08-03 Time 10:25 Sent To  
Notes
2016-08-03 10:38:17NO HABITABLE SPACE IS SHOWN ON PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2016-08-03 Cont ID  
Sent By rmcdouga Date 2016-08-03 Time 15:20 Rev Time 0.00
Received By rmcdouga Date 2016-08-03 Time 15:19 Sent To  
Notes
2016-08-03 15:20:52NO MECHANICAL WORK IS SHOWN ON THE PLANS.

Review Stop Z ZONING
Rev No 1 Status P Date 2016-06-21 Cont ID  
Sent By fmittner Date 2016-06-21 Time 15:11 Rev Time 0.00
Received By fmittner Date 2016-06-21 Time 15:11 Sent To  
Notes
***NONE***