Plan Review Details - Permit 16060998
Plan Review Stops For Permit 16060998
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-20 Cont ID  
Sent By jwitmer Date 2016-07-20 Time 16:48 Rev Time 0.00
Received By jwitmer Date 2016-07-20 Time 16:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-24 Cont ID  
Sent By jwitmer Date 2016-06-24 Time 07:30 Rev Time  
Received By jwitmer Date 2016-06-24 Time 07:01 Sent To  
Notes
2016-06-24 07:28:23BUILDING PLAN REVIEW
 W. P. B. PERMIT: 26060998
 ADD: 310 OKEECHOBEE BLVD.
 CONT: GREENVIEW CONSTRUCTION
 TEL: 561-727-5013
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 24/2016
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION UNDER THE HEADING DESCRIPTION
 OF WORK INDICATES TO DEMO KITCHEN AREA, REMODEL & SWAP
 OUT HVAC UNIT. NOTE THE WORK AHOWN ON THE A-1 PLAN
 SHOWS WORK IN WORK ROOM # 105, THE REMOVAL OF OLD WATER
 HEATER AND RELOCATION AND TO REMOVE SINK AND CAP. THE
 PLANS DO NOT INCLUDE ANY DEMO AND REMODEL OF KITCHEN
 AREA.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS. THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS: A FLOOR PLAN.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 FLOOR PLAN
 ELEVATIONS OF CABINETS
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 ACCESSIBLE ROUTE
 ACCESSIBLE SINKS 2014 FBC- ACCESS. CODE 606.1-5.
 POSSIBLE REACH RANGES & OPERABLE PARTS (MICROWAVE)
 ACCESS. CODE 308,2.1, 308.3.1, 309(1-4).
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-17 Cont ID  
Sent By jwitmer Date 2016-07-20 Time 16:48 Rev Time 0.00
Received By vperez Date 2016-07-17 Time 07:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-06-30 Cont ID  
Sent By vperez Date 2016-06-30 Time 14:37 Rev Time 0.00
Received By vperez Date 2016-06-30 Time 14:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-06-21 Cont ID  
Sent By fstall Date 2016-06-21 Time   Rev Time 0.00
Received By fstal Date 2016-06-21 Time 12:32 Sent To M
Notes
2016-06-21 12:31:53NFPA 90A-6.4, 2012 EDITION: SMOKE DETECTION FOR
 AUTOMATIC CONTROL.
 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE
 TESTED AT LEAST ANNUALLY.
 6.4.2 LOCATION.
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A
 CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND
 SERVING MORE THAN ONE STORY. OR 5 TON UNITS.
  
 NFPA 90A-6.4.4.3 WHERE SMOKE DETECTORS REQUIRED BY
 SECTION 6.4 ARE INSTALLED IN A BUILDING NOT EQUIPPED
 WITH AN APPROVED FIRE
 ALARM SYSTEM AS SPECIFIED BY 6.4.4.2, THE FOLLOWING
 SHALL OCCUR:
 (1) SMOKE DETECTOR ACTIVATION REQUIRED BY SECTION 6.4
 SHALL CAUSE A VISUAL SIGNAL AND AN AUDIBLE SIGNAL IN A
 NORMALLY OCCUPIED AREA.
 (2) SMOKE DETECTOR TROUBLE CONDITIONS SHALL BE
 INDICATED VISUALLY OR AUDIBLY IN A NORMALLY OCCUPIED
 AREA AND SHALL BE IDENTIFIED AS AIR DUCT DETECTOR
 TROUBLE.
 6.4.4.4 SMOKE DETECTORS POWERED SEPARATELY FROM THE
 FIRE ALARM SYSTEM FOR THE SOLE FUNCTION OF STOPPING
 FANS SHALL NOT REQUIRE STANDBY POWER.
  
  
 FRANK STALLWORTH, FIRE INSPECTOR I
 WEST PALM BEACH FIRE PREVENTION BUREAU
 500 N. DIXIE HWY
 WEST PALM BEACH, FLORIDA 33401
 OFFFICE: 561-840-4780
 FAX: 561-840-4774
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-20 Cont ID  
Sent By jwitmer Date 2016-07-20 Time 16:48 Rev Time 0.00
Received By jwitmer Date 2016-07-15 Time 13:30 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-30 Cont ID  
Sent By vperez Date 2016-06-30 Time 14:37 Rev Time 0.00
Received By vperez Date 2016-06-30 Time 14:37 Sent To  
Notes
2016-06-16 13:33:53B03

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-06-23 Cont ID  
Sent By ccole Date 2016-06-23 Time 11:57 Rev Time 0.00
Received By ccole Date 2016-06-23 Time 11:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-07-19 Cont ID  
Sent By tklarge Date 2016-07-19 Time 08:52 Rev Time 0.00
Received By tklarge Date 2016-07-19 Time 07:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-06-23 Cont ID  
Sent By gearl Date 2016-06-23 Time   Rev Time 0.00
Received By gearl Date 2016-06-23 Time 12:27 Sent To  
Notes
***NONE***