| 2016-06-27 06:59:25 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16060980 |
| | ADD: 2087 PALM BEACH LAKES BLVD. |
| | CONT: ALUMA-PRO ENTERPRISES |
| | TEL: 786-400-0560 |
| | E-MAIL: JTELLOCALUMA-PRO.COM |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: MON. JUNE 27/2016 |
| | ACTION: DENIED |
| | |
| | 1) STRUCTURAL CALCULATIONS BY P.E. ROBERT WARR ONLY THE |
| | FRONT PAGE OF THE CALCULATIONS ARE SIGNED AND SEALED. |
| | PROVIDE COMPLIANCE WITH FLORIDA ADMINISTRATIVE STATUTE |
| | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| | PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| | ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE |
| | COVERED UNDER THE COVER SHEET OR INDEX SHEET. |
| | |
| | 2) AWNING-CANOPY-SIGN CALCULATIONS & PLANS INDICATES IN |
| | THE WIND DESIGN CRITERIA THIS JOBSITE LOCATION IS |
| | LOCATED IN A EXPOSURE CATEGORY C. PLEASE CORRECT SEE |
| | THE 2014 FBC-B SECTION: 1609.4.2 SURFACE ROUGHNESS |
| | CATEGORIES. SURFACE ROUGHNESS C. OPEN TERRAIN WITH |
| | SCATTERED OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS |
| | THAN 30 FEET (9144 MM). THIS CATEGORY INCLUDES FLAT |
| | OPEN COUNTRY, AND GRASSLANDS. THIS SURFACE ROUGHNESS |
| | SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN SURFACE |
| | ROUGHNESS BTYPE TERRAIN WHERE THE BUILDING IS WITHIN |
| | 100 FEET HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF |
| | SURFACE ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE |
| | THAN 600 FEET IN THE UPWIND DIRECTION AND A WIDTH |
| | GREATER THAN 150 FEET. |
| | |
| | 3) PLEASE PROVIDE A SITE PLAN OF WHERE THESE AWNINGS |
| | ARE GOING TO BE INSTALLED. 2014 FLORIDA BUILDING CODE W |
| | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 4) PLEASE PROVIDE ELEVATIONS OF THE BUILDING AND AT |
| | WHAT HEIGHT FROM GRADE THESE AWNINGS ARE TO BE |
| | INSTALLED ,SHOW COMPLIANCE WITH: 2014 FBC-B SECTION |
| | 3105.3.1.1 |
| | FABRIC AWNINGS AND FABRIC-COVERED FRAMES LOCATED OVER |
| | PUBLIC PROPERTY OR IN AREAS ACCESSIBLE TO THE GENERAL |
| | PUBLIC SHALL BE CONSTRUCTED SO THAT NO RIGID PART OF |
| | SUCH FABRIC AWNINGS OR FABRIC-COVERED FRAMES SHALL BE |
| | LESS THAN 7 FEET 6 INCHES FROM THE GRADE DIRECTLY |
| | BELOW, AND NO PART OF THE CLOTH DROP SHALL BE LESS THAN |
| | 7 FEET. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |