Plan Review Details - Permit 16060973
Plan Review Stops For Permit 16060973
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-07 Cont ID  
Sent By jwitmer Date 2016-07-07 Time 09:55 Rev Time 0.00
Received By jwitmer Date 2016-07-07 Time 09:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-28 Cont ID  
Sent By jwitmer Date 2016-06-28 Time 09:38 Rev Time 0.00
Received By jwitmer Date 2016-06-28 Time 06:59 Sent To  
Notes
2016-06-28 09:19:30BUILDING PLAN REVIEW
 W. P. B. REVISION: 16060973
 W. P. B. PERMIT: 16030772
 ADD: 5500 VILLAGE BLVD. SUITE # 103
 CONT: BLACK DIAMOND
 TEL: 561-240-9903
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JUNE 28/ 2016
 ACTION: DENIED
  
 1) DEMOLITION SHEET D1 ROOMS 114 AND 115 ON THE
 ORIGINAL DEMOLITION SHEET WERE NOT SHOWN AS EXISITING
 RESTROOMS. THE NEW DEMOLITION SHEET SHOWS THESE UNITS
 AS EXISTING RESTROOMS. PLEASE REFERENCE PERMIT #
 04011145 REV. # 3 ON SHEET 2.1 AND 3.1 THAT THE
 RESTROOM AND BATHROOM WERE QUESTIONABLE AS COMPLIANT
 ACCESSIBLE UNITS UNDER THE CODE AT THAT TIME. WE ARE
 NOT REQUIRING A REVISION> UNDER THE 2014 FBC-ACCESS.
 CODE 202.4 ALTERATIONS AFFECTING PRIMARY FUNCTION
 AREAS.
 EXCEPTIONS:
 2. IF A PRIVATE ENTITY HAS CONSTRUCTED OR ALTERED
 REQUIRED ELEMENTS OF A PATH OF TRAVEL AT A PLACE OF
 PUBLIC ACCOMMODATION OR COMMERCIAL FACILITY IN
 ACCORDANCE WITH THE SPECIFICATIONS IN THE 1994 OR 1997
 FLORIDA ACCESSIBILITY CODE, THE PRIVATE ENTITY IS NOT
 REQUIRED TO RETROFIT SUCH ELEMENTS TO REFLECT
 INCREMENTAL CHANGES IN THE PROPOSED STANDARDS SOLELY
 BECAUSE OF AN ALTERATION TO A PRIMARY FUNCTION AREA
 SERVED BY THAT PATH OF TRAVEL.
  
 UNDER THE 1994 & 1997 ACCESS. CODE THE 60 INCHES CLEAR
 FROM THE SIDE WALL TO THE LAV, (SIDE CLEARANCE AT WATER
 CLOSET) WAS NOT A REQUIREMENT. UNDER THE 2001
 FBC-ACCESSIBILITY AND NEWER CODES IT HAS BEEN A
 REQUIREMENT. THERE ARE TO MANY VARIABLES OR UNKNOWNS
 THAT MAY HAVE COME INTO PLAY DEPENDING ON THE BUILDING
 OFFICIALS INTERPRETATION OF THE CODE. FOR EXAMPLE IF
 THE B. O. WENT WITH THESE ARE NOT REQUIRED FIXTURES BUT
 CONSIDERED PRIVATE RESTROOM AND OR BATHROOM THEY WOULD
 HAVE MET THE INTENT OF THE CODE. TODAYS CODE IS MORE
 RESTRICTIVE IN THE INTERPRETATION OF PRIVATE RESTROOMS
 AND BATHROOMS. THE TENANT MAY BE SUBJECT TO FEDERAL
 LAWSUITE UNDER THE 1990 ADA & FEDERAL BARRIER REMOVAL
 ACT.
  
 2) SHEET 3.1 DOOR # 110 REVISION # 3 SHOWS THE COPIER
 IN THE REQUIRED MANEUVERING CLEARANCES OF THE 2014
 FBC-ACCESS. CODE 404.2.4. AND FIGURE 404.2.4.1. (G).
  
 3) SHEET 3.1 DOOR # 104A ALSO MISSING THE 18 INCHES FOR
 MANEUVERING CLEARANCES ON THE PULL SIDE OF THE DOOR.
 2014 FBC-ACCESS. CODE 404.2.4. AND FIGURE
 404.2.4.1.(A). PLEASE NOTE TO DATE THERE HAS BEEN NO
 DOCUMENTATION OF MEETING THE REQUIREMENT OF
 DISPROPORTIONATE COST. 2014 FBC-ACCESS. CODE 202.4.1.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-06-27 Cont ID  
Sent By vperez Date 2016-06-27 Time 14:13 Rev Time 0.00
Received By vperez Date 2016-06-27 Time 14:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-06-24 Cont ID  
Sent By pleduc Date 2016-06-24 Time   Rev Time 0.00
Received By pleduc Date 2016-06-24 Time 13:54 Sent To  
Notes
2016-06-24 14:04:17THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 2) ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-07-07 Cont ID  
Sent By jwitmer Date 2016-07-07 Time 09:55 Rev Time 0.00
Received By jwitmer Date 2016-07-06 Time 14:51 Sent To  
Notes
2016-07-06 14:51:45RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-28 Cont ID  
Sent By jwitmer Date 2016-06-28 Time 09:38 Rev Time 0.00
Received By jwitmer Date 2016-06-22 Time 10:49 Sent To  
Notes
2016-06-22 10:49:08C26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-17 Cont ID  
Sent By ccole Date 2016-06-17 Time 08:00 Rev Time 0.00
Received By ccole Date 2016-06-16 Time 15:33 Sent To  
Notes
2016-06-16 15:34:01TLARGE'S DESK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-27 Cont ID  
Sent By ccole Date 2016-06-27 Time 17:05 Rev Time 0.00
Received By ccole Date 2016-06-27 Time 17:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-06-17 Cont ID  
Sent By ccole Date 2016-06-17 Time 08:00 Rev Time 0.00
Received By ccole Date 2016-06-17 Time 07:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-23 Cont ID  
Sent By tklarge Date 2016-06-23 Time   Rev Time 0.00
Received By gearl Date 2016-06-23 Time 12:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-17 Cont ID  
Sent By tklarge Date 2016-06-17 Time 05:39 Rev Time 0.00
Received By tklarge Date 2016-06-17 Time 05:31 Sent To  
Notes
2016-06-17 05:39:171) THE CHANGES IN THE CONSTUCTION RENOVATIONS TO RETAIN
 THE TWO EXISTING TOILET ROOMS ( #114 & #115) AFFECTS
 THE ENTIRE SET OF PLANS AND NOT JUST THE MECHANICAL
 SHEET. SUBMIT TWO COPIES OF COMPLETELY REVISED PLANS
 FOR REVIEW.WPB AMEND. TO FBC SEC.107.1, 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  