Plan Review Details - Permit 16060972
Plan Review Stops For Permit 16060972
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-11 Cont ID  
Sent By cthroop Date 2016-07-11 Time 13:07 Rev Time 0.00
Received By cthroop Date 2016-07-11 Time 13:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-30 Cont ID  
Sent By cthroop Date 2016-06-30 Time 14:15 Rev Time 0.00
Received By cthroop Date 2016-06-30 Time 14:15 Sent To  
Notes
2016-06-30 14:17:47BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 6/30/16
  
 1. PROVIDE SITE PLAN WITH LOCATION OF GENERATOR. SHOW
 COMPLIANCE WITH BUILDING SETBACKS AND CLEARANCES TO
 BUILDING OPENINGS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-11 Cont ID  
Sent By mvaldes Date 2016-07-11 Time 10:17 Rev Time 0.00
Received By mvaldes Date 2016-07-11 Time 09:58 Sent To B
Notes
2016-07-11 10:18:32ROUTED TO CHRIS THROOP

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-20 Cont ID  
Sent By mvaldes Date 2016-06-20 Time 15:04 Rev Time 0.00
Received By mvaldes Date 2016-06-20 Time 14:24 Sent To B
Notes
2016-06-20 15:09:43REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - PLEASE HIGHLIGHT ON SPEC CUT SHEETS THE ATS YOUR
 USING. THERE IS 2 MODELS CLARIFY ?
  
 - IF THE EQUIPMENT IS SERVICE RATED IT SHALL BE LISTED.
 NEC 230.66

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-11 Cont ID  
Sent By cthroop Date 2016-07-11 Time 13:07 Rev Time 0.00
Received By cthroop Date 2016-07-06 Time 13:50 Sent To  
Notes
2016-07-06 13:50:37RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-30 Cont ID  
Sent By cthroop Date 2016-06-30 Time 14:15 Rev Time 0.00
Received By cthroop Date 2016-06-16 Time 11:52 Sent To  
Notes
2016-06-16 11:52:21ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2016-07-08 Cont ID  
Sent By njwira Date 2016-07-08 Time 15:06 Rev Time 0.00
Received By njwira Date 2016-07-08 Time 15:06 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-16 Cont ID  
Sent By njwira Date 2016-06-16 Time 16:40 Rev Time 0.00
Received By njwira Date 2016-06-16 Time 16:40 Sent To E
Notes
2016-06-16 16:41:486/16/16- FAILED
 1. GENERATOR MUST BE ON THE PROPERTY.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved