Plan Review Details - Permit 16060843
Plan Review Stops For Permit 16060843
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-22 Cont ID  
Sent By jwitmer Date 2016-07-22 Time 16:54 Rev Time 0.00
Received By jwitmer Date 2016-07-22 Time 16:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-17 Cont ID  
Sent By jwitmer Date 2016-06-17 Time 09:35 Rev Time 0.00
Received By jwitmer Date 2016-06-17 Time 09:11 Sent To  
Notes
2016-06-17 09:35:29BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060843
 ADD: 525 OKEECHOBEE BLVD. SUITE # 970
 CONT: HOLT LEE
 TEL: 954-725-4881
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI, JUNE 17/ 2016
 ACTION: DENIED
  
 1) PLEASE NOTE, IN BOTH SETS OF PLANS NEITHER OF THE
 ARCHITECTURAL PLANS NOR THE MEP AND FIRE ALARM DRAWINGS
 ARE SIGNED AND SEALED.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G16.003 ARCHITECTS
  
 FL ADMIN CODE 61G15-23.002 ENGINEERSEFFECTIVE DATE
 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER
 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
  
 2) SHEET A.1.1.1 SHOWS THE TENANT SEPERATION WALLS AND
 CORRIDOR WALLS TO BE ONE HOUR FIRE RATED WALLS. THE
 ENTRY DOOR # 901 DOES NOT SHOW ANY RATING SEE DOOR
 SCHEDULE SAME PAGE. 2014 FBC-B TABLE 716.5.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-15 Cont ID  
Sent By vperez Date 2016-07-15 Time 13:03 Rev Time 0.00
Received By vperez Date 2016-07-15 Time 13:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-27 Cont ID  
Sent By vperez Date 2016-06-27 Time 11:36 Rev Time 0.00
Received By vperez Date 2016-06-27 Time 11:29 Sent To  
Notes
2016-06-27 11:37:00INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED
 TO PHONE AND DATA, ETC. A NOTE WILL SUFFICE.
 2. PROVIDE A NOTE TO COMPLY WITH FBC ENERGY
 CONSERVATION 2014- 50% OF RECEPTACLES TO BE
 AUTOMATICALLY CONTROLLED. FBC EC C407.7
 3. EOR TO SIGN AND SEAL DRAWINGS SUBMITTED.
 4. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-07-19 Cont ID  
Sent By pleduc Date 2016-07-19 Time   Rev Time 0.00
Received By pleduc Date 2016-07-18 Time 16:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-06-21 Cont ID  
Sent By pleduc Date 2016-06-21 Time   Rev Time 0.00
Received By pleduc Date 2016-06-21 Time 16:09 Sent To  
Notes
2016-06-21 16:33:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 1.1.1 - THE OFFICE ENTRY WALL IS INDICATED
 AS A WALL TO EXTEND TO ABOVE CEILING. SHEET AD 1.1
 INDICATES THE REMOVAL OF A 1 HOUR WALL SECTION TO
 ACCOMODATE THIS ENTRY WAY. A 1 HOUR RATED WALL AND DOOR
 SHALL BE INSTALLED AT THIS LOCATION.
  
 PLEASE PROVIDE REVISED DETAILS FOR A 1 HOUR WALL OR
 CLARIFY.
  
 2) SHEET A 1.1.1 - DOOR 901 IS NOT INDICATED AS A FIRE
 RATED DOOR. PER THE ABOVE NOTED WALL REVISION, DOOR 901
 IS REQUIRED TO BE RATED.
  
 PLEASE CORRECT OR CLARIFY.
  
 3) PLEASE SEE BUILDING COMMENTS REGARDING PLAN SIGNED
 AND SEALED REQUIREMENTS.
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-30 Cont ID  
Sent By tklarge Date 2016-07-30 Time 04:40 Rev Time 0.00
Received By tklarge Date 2016-07-08 Time 14:15 Sent To  
Notes
2016-07-08 14:17:06B33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-27 Cont ID  
Sent By vperez Date 2016-06-27 Time 11:37 Rev Time 0.00
Received By vperez Date 2016-06-27 Time 11:37 Sent To  
Notes
2016-06-14 13:12:04B25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-06-17 Cont ID  
Sent By jwitmer Date 2016-06-17 Time 09:35 Rev Time 0.00
Received By jwitmer Date 2016-06-17 Time 09:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-07-18 Cont ID  
Sent By ccole Date 2016-07-18 Time 11:32 Rev Time 0.00
Received By ccole Date 2016-07-18 Time 11:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-22 Cont ID  
Sent By ccole Date 2016-06-20 Time 16:53 Rev Time 0.00
Received By ccole Date 2016-06-20 Time 11:03 Sent To  
Notes
2016-06-20 11:30:521ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16060843
 6/20/16
  
 1) CLARIFY HOW THE COOLING AND HEATING FOR THE PROPOSED
 NEW OCCUPANCY WAS SIZED- PROVIDE CALCULATIONS.
  
 2) SPACE HEATING IS REQUIRED FOR ALL OCCUPIED ROOMS AND
 SPACES PER SECTION 309.1, HOWEVER VAV'S #2 & 3 ARE NOT
 EQUIPPED WITH HEAT- PLEASE CLARIFY.
  
 3) THE 12X10 TRANSFER DUCT FROM OFFICE 904 IS
 UNDERSIZED- SECTION 601.5.
  
 4) PLEASE INDICATE THE RETURN AIR CFM'S AT THE THE
 60X16 TRANSFER- IT APPEARS TO BE UNDERSIZED PER SECTION
 601.5.
  
 5) THE ENGINEER OF RECORD MUST PLACE HIS SIGNATURE AND
 SEAL ON THE MECHANICAL PLAN SHEETS- SECTION
 61G15-23.002 FORIDA ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-07-30 Cont ID  
Sent By tklarge Date 2016-07-30 Time 04:39 Rev Time 0.00
Received By tklarge Date 2016-07-30 Time 04:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-22 Cont ID  
Sent By gjohnson Date 2016-06-22 Time 16:37 Rev Time 0.00
Received By gjohnson Date 2016-06-22 Time 16:01 Sent To  
Notes
2016-06-22 16:42:091ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
  
 1. PLANS MUST BE SIGNED AND SEALED BY DESIGNER OF
 RECORD ALL SHEETS. PER FAC 61G15-23.001 AND
 61G15-23.003