Plan Review Details - Permit 16060834
Plan Review Stops For Permit 16060834
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-12-08 Cont ID  
Sent By rmcdouga Date 2016-12-08 Time 09:24 Rev Time 0.00
Received By rmcdouga Date 2016-12-08 Time 08:51 Sent To E
Notes
2016-12-08 09:24:46PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORM 402 DOES NOT INCLUDE THE FLOOR AREA
 OF THE LAUNDRY ROOM. THE MECHANICAL PLAN ON SHEET A3.0
 SHOWS AN A/C DUCT SUPPLYING THE LAUNDRY ROOM. THIS
 MAKES IT CONDITIONED SPACE WHICH IS REQUIRED TO COMPLY
 WITH THE ENERGY CODE. SHOW COMPLIANCE WITH 2014 FBC
 ENERGY CONSERVATION SECTIONS 101.5.1 & 103.1 BY
 SUBMITTING THE PROPER CONSTRUCTION DOCUMENTS. SEE
 RESIDENTIAL BUILDING FORMS 402 OR 405.
  
 2) THE NEW DUCT WORK THAT IS LOCATED IN THE ATTIC IS
 REQUIRED TO INSULATED TO A MINIMUM OF R-8 WHEN USING
 THE PRESCRIPTIVE METHOD OF COMPLIANCE. FBC ENERGY
 R403.2.1
  
 3) ONLY ONE SET OF PRODUCT APPROVALS WERE SUBMITTED.
 SUBMIT AN ADDITIONAL SET FOR EACH ITEM. FBC 107.3.4 -
 PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW/GLASS TYPES, AND EXTERIOR
 DOOR TYPES.
  
 4) THE PRODUCT APPROVAL FL735-R9 (NOA NO.12-0716.18)
 THAT WAS SUBMITTED FOR THE TAMKO MODIFIED BITUMEN ROOF
 SYSTEM WILL REQUIRE ENHANCED FASTENING AT THE PERIMETER
 AND CORNER ROOF AREAS. LIMITATION NUMBER 6 ON PAGE 15
 REQUIRES SIGNED AND SEALED ENHANCED FASTENING
 CALCULATIONS IN ACCORDANCE WITH RAS 117 FROM A FLORIDA
 REGISTERED ENGINEER, ARCHITECT OR REGISTERED ROOF
 CONSULTANT.
  
 IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-02 Cont ID  
Sent By rmcdouga Date 2016-08-02 Time 09:11 Rev Time 0.00
Received By rmcdouga Date 2016-08-01 Time 18:28 Sent To  
Notes
2016-08-02 09:11:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION
 SECTIONS 101.5.1 & 103.1 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405.
  
 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES,
 AND EXTERIOR DOOR TYPES.
  
 3) THE VALUE OF THE WORK OF $6000.00 ON THE APPLICATION
 APPEARS TO BE LOW. I HAVE INCREASED THE VALUE TO
 $13,389.00 BASED ON ICC VALUATION DATA. FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-08 Cont ID  
Sent By mvaldes Date 2016-12-08 Time 10:18 Rev Time 0.00
Received By mvaldes Date 2016-12-08 Time 10:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-07 Cont ID  
Sent By mvaldes Date 2016-07-07 Time 12:51 Rev Time 0.00
Received By mvaldes Date 2016-06-30 Time 17:19 Sent To  
Notes
2016-07-07 12:55:05REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL.
 NEC 210.52 (A)(2) WALL SPACE. ANY WALL SPACE 2 FT. OR
 MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. ( SEEMS TO BE
 MISSING A RECEPTACLE BY THE DOOR. )
  
 - NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE
 SUPPORT OF CEILING FANS SHALL BE MARKED BY THE
 MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE
 THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT
 PADDLE FANS HEAVIER THAN 70 LBS.
 ( ADD A NOTE )
  
 - PLEASE MODIFY THE EXTERIOR GFCI OUTLET TO HAVE SLASH
 RATING "WR/WP" .NEC 406.9(B) RECEPTACLES IN WET
 LOCATIONS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-08 Cont ID  
Sent By mvaldes Date 2016-12-08 Time 10:20 Rev Time 0.00
Received By mvaldes Date 2016-11-28 Time 17:19 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-02 Cont ID  
Sent By rmcdouga Date 2016-08-02 Time 09:11 Rev Time 0.00
Received By rmcdouga Date 2016-06-14 Time 09:51 Sent To  
Notes
2016-06-14 11:28:53R13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-12-07 Cont ID  
Sent By rmcdouga Date 2016-12-07 Time 14:09 Rev Time 0.00
Received By rmcdouga Date 2016-12-07 Time 14:09 Sent To  
Notes
2016-12-07 14:17:23MU 2016-29044

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-08-01 Cont ID  
Sent By rmcdouga Date 2016-08-01 Time 18:26 Rev Time 0.00
Received By rmcdouga Date 2016-08-01 Time 18:26 Sent To  
Notes
2016-08-01 18:26:27BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-12-08 Cont ID  
Sent By rmcdouga Date 2016-12-08 Time 08:50 Rev Time 0.00
Received By rmcdouga Date 2016-12-08 Time 08:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-02 Cont ID  
Sent By rmcdouga Date 2016-08-02 Time 07:34 Rev Time 0.00
Received By rmcdouga Date 2016-08-02 Time 07:06 Sent To  
Notes
2016-08-02 07:34:39M1602.4 BALANCED RETURN AIR. EXCEPTIONS: 1. TRANSFER
 DUCTS MAY ACHIEVE THIS BY INCREASING THE RETURN
 TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA (SQUARE
 INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR SPACE
 IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCH (25 MM) UNDERCUT TO ACHIEVE PROPER
 RETURN AIR BALANCE. THE 10 INCH DIAMETER TRANSFER DUCT
 IS TOO SMALL FOR A 9 INCH DIAMETER SUPPLY.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2016-12-08 Cont ID  
Sent By rmcdouga Date 2016-12-08 Time 09:35 Rev Time 0.00
Received By rmcdouga Date 2016-12-08 Time 09:35 Sent To  
Notes
2016-12-08 09:37:55TAMKO MODIFIED BITUMEN ROOF SYSTEM FL735-R9 (NOA NO.
 12-0716.18) - NEEDS SIGNED AND SEALED RAS 117
 CALCULATIONS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-08-02 Cont ID  
Sent By rmcdouga Date 2016-08-02 Time 08:38 Rev Time 0.00
Received By rmcdouga Date 2016-08-02 Time 08:38 Sent To  
Notes
2016-08-02 08:38:50NO ROOFING PRODUCT APPROVALS WERE SUBMITTED.

Review Stop Z ZONING
Rev No 2 Status F Date 2016-12-02 Cont ID  
Sent By mvaldes Date 2016-12-08 Time 10:20 Rev Time 0.00
Received By njwira Date 2016-11-29 Time 16:20 Sent To E
Notes
2016-12-02 17:00:0312/2/16- FAILED
  
 SF-7
  
 94-74(3)D- SIDE SETBACK IS 3FT. MINIMUM 10FT. TOTAL
 WHICH DOESN'T MEET THE 5FT. MINIMUM 15FT. TOTAL
  
 PASSED
 1. MEETS FRONT 25FT. SETBACK
 2. NOT IN THE REAR SETBACK
 3. NO TREES BEING REMOVED
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-17 Cont ID  
Sent By njwira Date 2016-06-17 Time 15:42 Rev Time 0.00
Received By njwira Date 2016-06-17 Time 15:42 Sent To  
Notes
2016-06-17 15:44:306/17/16- FAILED
 1. NEED A COPY OF A CERTIFIED SURVEY SHOWING THE
 SETBACK DIMENSIONS FROM THE HOUSE.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  