| 2016-06-20 12:07:40 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16060788 |
| | ADD: 1801 S. FLAGLER DR. SUITE # PH-11 |
| | CONT: K. L. BREEN BUILDER |
| | TEL: 561-856-0232 |
| | E-MAIL: |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JUNE 20/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-00/ COVERSHEET UNDER THE HEADING CODE |
| | RESEARCH: |
| | 1A) THE CONSTRUCTION TYPE IS LISTED AS A IIIB. THIS IS |
| | A 19 STORY CONDOMINIMUM. PLEASE REFER TO THE 2014 FBC-B |
| | TABLE 503 FOR A R2 OCCUPANCY. THE BUILDING TYPE IS A |
| | TYPE : IA. |
| | |
| | 1B) THE CODE RESEARCH INDICATES THE OCCUPANCY ONLY AS |
| | R. PLEASE REFERENCE TO WHICH SUB-CATEGORY OF R THE |
| | PLANS WERE DESIGNED TOO? 2014 FBC-B 310.1. |
| | |
| | 1C) THE DESIGNER OF RECORD INDICATES THE PLANS WERE |
| | DESIGNED TO THE 2014 EXISITNG BUILDING CODE, BUT TO |
| | WHAT COMPLIANCE METHOD. SHOW COMPLIANCE WITH 2014 |
| | FBC-EXISITNG SECTION 301.1. THE REPAIR, ALTERATION, |
| | CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL |
| | EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS |
| | LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED |
| | BY THE APPLICANT. |
| | |
| | 2) SHEET A-02: |
| | 2A) PLEASE CLARIFY WHAT THE TEERM SUB-FLOOR MEANS. THE |
| | FLOOR PLAN INDICATES NEW WOOD ANS TILE SUBFLOORS. THIS |
| | BUILDING BEING A HIGH-RISE HAS CONCRETE DECK FLOORS. |
| | RESIDENTIAL UNITS REQUIRE FLOOR INSULATION BETWEEN THE |
| | CONCRETE DECK AND THE FINISH FLOORS TILE AND OR WOOD |
| | FLOORS. IF THE DESIGNER IS TRUELY USING PLYWOOD |
| | SUB-FLOORS AND APPLYING EITHER TILE OR WOOD FLOORING |
| | OVER PLYWOOD SUB-FLOORS THE SUB-FLOORING NEEDS TO |
| | COMPLY WITH FBC-B 805.1.1 SUBFLOOR CONSTRUCTION. |
| | FLOOR SLEEPERS, BUCKS AND NAILING BLOCKS SHALL NOT BE |
| | CONSTRUCTED OF COMBUSTIBLE MATERIALS, UNLESS THE SPACE |
| | BETWEEN THE FIRE-RESISTANCE-RATED FLOOR ASSEMBLY AND |
| | THE FLOORING IS EITHER SOLIDLY FILLED WITH |
| | NONCOMBUSTIBLE MATERIALS OR FIREBLOCKED IN ACCORDANCE |
| | WITH SECTION 718, AND PROVIDED THAT SUCH OPEN SPACES |
| | SHALL NOT EXTEND UNDER OR THROUGH PERMANENT PARTITIONS |
| | OR WALLS. COMPLIANCE WITH THE 3 TEST LISTED BELOW WILL |
| | ALSO BE REQUIRED. |
| | |
| | 2B) IF THE DESIGNER OF RECORD IS GOING TO USE |
| | INSULATION AS PART OF THE SOUND PROOFING THEN |
| | COMPLIANCE WITH THE (3) LISTED TEST HAS TO BE ACHIEVED: |
| | |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS, PROVIDE THE ACTUAL |
| | TEST: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 2B)(1) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B)(2) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2B)(3) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 2C) THE FLOOR PLAN INDICATES THE USE OF NEW RAISED |
| | CEILINGS. THE FLOOR/ CEILING ASSEMBLY IS A CONCRETE |
| | DECK AND CAN NOT BE MOVED. PLEASE CLARIFY IF THESE |
| | CEILINGS ARE TO BE CONSIDERED DROPPED CEILINGS AS IN |
| | DETAIL # 3? IF SO THE DETAIL WILL NEED TO CLARIFY THE |
| | TYPE OF FRAMING MEMBER, GAUGE OF STEEL, SPACING OF THE |
| | FRAMING MEMBERS, SPANS OF THE FRAMING MEMBERS, SPACING |
| | OF STIFFBACKS AND SIZE OF STIFF BACKS, THICKNESS OF |
| | GYPSUM BOARD TO BE INSTALLED. IF ANCHORS ARE TO OCCUR |
| | INTO THE CONCRETE DECK PLEASE PROVIDE THE TYPE OF |
| | ANCHOR AND LENGTH OF ANCHOR. ALSO DECLARE WHAT THE |
| | FINISHED CEILING HEIGHT WILL BE IN EACH ROOM. |
| | 2014 FBC-B TABLE 2508.1/ ASTM C 754 STEEL FRAMING FOR |
| | GYPSUM BOARD. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |