Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-06-22 Cont ID  
Sent By wjolin Date 2016-06-22 Time 12:02 Rev Time 0.00
Received By wjolin Date 2016-06-22 Time 12:02 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-06-15 Cont ID  
Sent By wjolin Date 2016-06-15 Time 14:08 Rev Time 0.00
Received By wjolin Date 2016-06-15 Time 14:00 Sent To M
Notes
2016-06-15 14:08:521617 NORTH FLAGLER DRIVE #12A
 PERMIT #16060727
 MASTER #16040257
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A HYDRAULIC CALCULATION SUPPORTING THE 4
 SPRINKLERS SUPPLIED BY A 1-INCH BRANCHLINE
 (BREAKFAST/DINING/KITCHEN AREA).
  
 PLAN GENERAL NOTE INDICATES SYSTEM DESIGNED FOR NFPA
 13-RESIDENTIAL. NFPA 13R IS LIMITED TO RESIDENTIAL
 BUILDINGS 4-STORIES OR LESS.
  
 INDICATE THE HYDROSTATIC TEST PRESSURE TO BE UTILIZED
 FOR THE PRESSURE TEST.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-27 Cont ID  
Sent By hmoser Date 2016-06-27 Time 14:35 Rev Time 0.00
Received By hmoser Date 2016-06-17 Time 11:06 Sent To  
Notes
2016-06-20 11:06:22RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-17 Cont ID  
Sent By hmoser Date 2016-06-17 Time 10:23 Rev Time 0.00
Received By hmoser Date 2016-06-10 Time 16:19 Sent To  
Notes
2016-06-10 16:19:09ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-27 Cont ID  
Sent By hmoser Date 2016-06-27 Time 14:35 Rev Time 0.00
Received By hmoser Date 2016-06-27 Time 14:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-17 Cont ID  
Sent By hmoser Date 2016-06-17 Time 10:22 Rev Time 0.00
Received By hmoser Date 2016-06-17 Time 09:50 Sent To  
Notes
2016-06-17 10:21:35PLAN DENIED
 PROVIDE TWO SETS OF HYDRAULIC CALCULATIONS
 WITH PLANS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676