Plan Review Details - Permit 16060598
Plan Review Stops For Permit 16060598
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-07-31 Cont ID  
Sent By skennedy Date 2017-07-31 Time 15:20 Rev Time 0.00
Received By skennedy Date 2017-07-31 Time 15:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-16 Cont ID  
Sent By cthroop Date 2016-06-16 Time 15:16 Rev Time 0.00
Received By cthroop Date 2016-06-16 Time 15:16 Sent To  
Notes
2016-06-16 15:31:53BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 DATE: 6/16/16
 ACTION: DENIED
  
 NO PLAN REVIEW CAN BE PERFORMED AT THIS TIME.
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
  
 NO PLAN SUBMITTED FOR DECK.
  
 1. PROVIDE PLAN WITH DETAILS FOR DECK.
 2. PROVIDE SITE PLAN, IDENTIFY SETBACKS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-07-31 Cont ID  
Sent By skennedy Date 2017-07-31 Time 15:20 Rev Time 0.00
Received By skennedy Date 2017-07-31 Time 15:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-15 Cont ID  
Sent By mvaldes Date 2016-06-15 Time 18:50 Rev Time 0.00
Received By mvaldes Date 2016-06-15 Time 18:50 Sent To  
Notes
2016-06-15 18:56:44REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - PLEASE PROVIDE A RISER DIAGRAM SHOWING WIRE SIZE,
 BREAKER SIZE, AND CONDUIT SIZE OR SPECIFY INFORMATION
 ON THE FLOOR PLAN WHICH SHOULD BE SITE SPECIFIC AND
 SHOW LOCATION OF ELECTRICAL EQUIPMENT. IN ADDITION
 PROVIDE HOT TUB MANUFACTURE SPEC CUT SHEET. FBC 107
  
 - NEC 680.71 PROTECTION. HYDROMASSAGE BATHTUBS AND
 THEIR ASSOCIATED ELECTRICAL COMPONENTS SHALL BE ON AN
 INDIVIDUAL BRANCH CIRCUIT(S) AND PROTECTED BY A READILY
 ACCESSIBLE GROUND-FAULT CIRCUIT INTERRUPTER. ALL
 125-VOLT, SINGLE-PHASE RECEPTACLES NOT
 EXCEEDING 30 AMPERES AND LOCATED WITHIN 1.83 M (6 FT)
 MEASURED HORIZONTALLY OF THE INSIDE WALLS OF A
 HYDROMASSAGE TUB SHALL BE PROTECTED BY A GROUND-FAULT
 CIRCUIT INTERRUPTER.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-03 Cont ID  
Sent By njwira Date 2017-08-03 Time 11:39 Rev Time 0.00
Received By njwira Date 2017-07-31 Time 15:32 Sent To  
Notes
2017-07-31 15:23:20SPOKE TO PHIL PETTY HE INDICATED THE APPLICANT
 CONTACTED HIM PRIOR TO PERMIT APPLICATION EXPIRATION
 AND ELECTRICAL APPROVAL WAS INADVERTANTLY DELAYED
 CAUSING THE APPLICATION TO APPEAR TO BE ABANDONED BUT
 IN FACT WAS IN PROCESS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-16 Cont ID  
Sent By cthroop Date 2016-06-16 Time 15:16 Rev Time 0.00
Received By cthroop Date 2016-06-09 Time 10:01 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2017-08-09 Cont ID  
Sent By njwira Date 2017-08-09 Time 10:20 Rev Time 0.00
Received By njwira Date 2017-08-09 Time 10:20 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2017-08-03 Cont ID  
Sent By njwira Date 2017-08-03 Time 11:39 Rev Time 0.00
Received By njwira Date 2017-07-31 Time 16:23 Sent To I
Notes
2017-08-03 11:39:398/3/17- FAILED
  
 WHERE IS THE POOL EQUIPMENT GOING?
 IS THERE A PAVER DECK?
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-13 Cont ID  
Sent By cthroop Date 2016-06-16 Time 15:16 Rev Time 0.00
Received By njwira Date 2016-06-13 Time 16:53 Sent To E
Notes
2016-06-13 16:54:536/13/16- FAILED
 1. SPA SIDE SETBACK IS 8FT AND HAMILTON BAY REQUIRES
 10FT.
 2. SPA REAR SETBACK IS NOT MEASURED AND HAMILTON BAY
 REQUIRES 5FT.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  